AGE (I) (P) Niwaru
AGE (I) (P) Niwaru
AGE(I)(P)N-19 OF 2022-23 REPAIR AND MAINT HT CIRCUITS INCLUDING HT SWITCH GEAR AT MUNDOTA AND NIWARU MIL STNUNDER AGE I P NIWARU
2022_MES_531351_2
AGE (I) (P) N - 19 OF 2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
AGE (I) (P) Niwaru
Class E
6 documents required · 6 mandatory
₹500
Yes
AGE (I) (P) Niwaru
₹50,000
Yes
5 Aug 2022
9 Jul 2022
1 Aug 2022
9 Jul 2022
30 Jul 2022
16 Jul 2022
Amount
S&F in repair of cable end termination jointing kit, heat shrinkable, outdoor type complete with jointing material suitable for HT XLPE cable 240/300 Sqmm, 3 core,11 KV grade, Complete all as specified and directed by engineer in charge. NOTE:- Item rate quoted including required T&P. Complete all as specified and directed by Engr-in-charge.
All as per item No. 1 but for HT XLPE cable 95 Sq mm, 3 core,11 KV grade.
All as per item No. 1 but for indoor type, 240/300 Sqmm, 3 core,11 KV grade.
All as per item No. 1 but for indoor type, 95 Sqmm, 3 core,11 KV grade.
S&F in repair of cable straight through jointing kit, heat shrinkable, outdoor type complete with jointing material suitable for HT XLPE cable 240/300 Sqmm, 3 core, 11 KV grade, Complete all as specified and directed by engineer in charge. NOTE:- Item rate quoted including excavating/required T&P/Refixing & Refilling.
All as per item No. 1 but for HT XLPE cable 95 Sq mm, 3 core, 11 KV grade.
Taking shut down and carry out repair to off load rotating type 33KV/ 200 Amp Air break gang operated switch and alignment of isolators, blades, arcing horns moving mechanism oiling greasing to isolators gear box assembly tightening renewal/ replacement of unserviceable spare/components, nut and bolts complete air break switch unit after carrying out fresh lubrication using Lithium base grease/petroleum jelly, and re-fixing the spare parts/components complete all as directed at site, Complete all as specified and directed by engineer in charge. NOTE: New spares/components shall be measured and paid separately as under
(a) Supply only metallic (brass, alloy) fixed contact set, single pole including fixing screwed nuts and washers suitable for air break gang operated switch of capacity 200 Amps, 3 pole, 33000 Volts grade, Complete all as specified and directed by engineer in charge.
(b) Supply only Post insulator with GI post for holding fixed/moving contact assembly including fixing arrangements suitable for Air break gang operated switch 200 Amps, 33000 volts grade, Complete all as specified and directed by engineer in charge.
(c) Supply only GOD operating rod with cover 33000 Volts grade insulation including locking arrangements with 65mm pad lock (Godrej) with two keys, Complete all as specified and directed by engineer-in-charge.
S&F in repair of HT fuse 10 to 200 Amps capacity, Complete all as specified and directed by engineer-in-charge.
S&F in repair of power pack for 33KV and 11 KV Vacuum circuit breaker of incoming 110 volts AC, outgoing 24 Volt DC, Complete all as specified and directed by engineer-in-charge.
S&F lead acid battery 7 AH 24 volt suitable for power pack of 11 KV VCB complete all as per directed by EIC.
M&L for tracing the HT/ UG cable fault with HT cable fault locator of 33 KV/11KV System in any situation/position complete as directed. NOTE:-(i) One Single cable of any length for end to end termination with any number/type of faults will be considered to consitute only one qty for tracing and payment purpose., Complete all as specified and directed by engineer-in-charge.
Supply, laying and commissioning XLPE insulated screened, PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) with aluminium conductor 11000 Volts, 95 Sq mm, 3 core cable grade IS-7098 marked, suitable for HT 11 KV (E) System laid in trenches/ ducts/ encased in GI pipe/ fixed to poles including jointing & testing in repair, complete all as specified and directed. NOTE:- Item rate quoted including excavating/ refilling/additional HT PCC Cover as per IS if required on site.
All as per item No. 12 but for 240 Sq mm, 3 core cable.
Supply and fix in repair Plate type cable route indicator shall be made out of 100mmx5mm GI plate welded/bolted on 35mmx35mmx6mm angle iron, 60 Cm long duly inscribed "HT CABLE" on the plate. This plate type marker shall be mounted aong the cable trench at intervals not exceeding 30 meters.angle iron should be fixed on PCC foundation and base of the foundation prepared by aggregate of 20mm dia size of ratio 1:2:4 type B1 and size of the base 150x150x160mm thick all as specified and directed by EIC. (Note:- Item rate quoted includes grouting,excavating/required T&P & Refilling.)
M&L earthing complete as per electrical plate No 3 of MES SSR Part-I with galvanised steel earth plate electrode 60cmx60cmx6.0mm thick, buried directly vertically in ground in a pit depth not less than 2.25 metres below ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level connected to and including galvanised iron or steel earth strip 32mm x 6mm by means of bolts, nuts check nuts and washers of galvanised iron or steel. Earthing strip shall be protected by galvanised iron or steel pipe 40mm bore light grade and connected to continuous earth wire on pole/test point. Watering pipe shall be 20 mm bore GI medium grade. The earthing shall be of inclusive of excavation & earth work in any type of soil, charcoal, salt, funnel PCC pit and RCC cover complete all as specified & tested including taking down of existing earthing, Complete all as specified and directed by engineer-in-charge.
M&L for Dehydration /filtration of transformer oil existing transformer installed at site with portable plant to improve the dielectric strength to 60 KV or above during filling after initial filtration including testing of dielectric strength after dehydration at site. Note- Quoted rates shall be deem to include for following :- (i) Oil shall be tested after filtration and test result will be recorded before & after filtration of oil. (ii) Contractor should make his own arrangement for oil filtration plant including transportation complete. (iii) Transformer oil for topping up will be measured and paid in relevant item as required. (iv) Replacement of minor parts like Drain valve,oil seal etc.
S&F in repair of transformer oil in transformer installed/ at site for toping up the level of oil having dielectric strength 40-60 KV.Transformer oil conforming to IS-335 shall be supplied in sealed container , empty barrel of transformer oil will be deposited by contractor in E/M store yard, Complete all as specified and directed by engineer-in-charge.
M&L for testing and checking of di-electric strength of transformer oil with testing equipment/ instruments by maintaining a gap 2.5 mm between electrodes and applying voltage with rate of rise at 2 kV per sec as per indian standards and directed by Engr -incharge .
M&L for rectification of oil leakage from HT side of transformer 11/0.433KV upto 400 KVA by necessary repair/repalcement of bushing/Gasket/seal etc complete with brass terminal including testing complete all as specified and directed by Engineer in charge. Note :- (i) Contractor should make his own arrangement for all necessary T&P & transportation to work shop etc. (ii) Contractor has to rectify the leakage within 8 hrs after opening and dismentelling of transformer for repairing otherwise a penality of Rs 500/- per hrs would be imposed.
All as per item No. 19 above, but for rectification of oil leakage from LT side of transformer 11/0.433KV upto 400 KVA cmplete all as directed.
Supplying and spreading of gravels size 40-63 mm size around transformer plinth, two/ four pole structure and HT yard etc.
M&L for Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20cm size fixed in repair, complete all as specified and directed by engineer in charge.
M&L for Lightning arresters expulsion type for 33 KV complete with all fittings, transmission class, discharge capacity 65 kilo amp fixed in repair,, Complete all as specified and directed by engineer in charge.
M&L for Lightning arresters expulsion type for 11 KV complete with all fittings, transmission class, discharge capacity 65 kilo amp fixed in repair, complete all as specified and directed by engineer in charge.
M&L for Triple pole Switch air brake, Gang operated, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for 11 kV ¤t rating upto 200 amps fixed in repair,complete all as specified and directed by engineer in charge.
S&F breather with silica gel in replacement (for transformer of any type/cap) complete with end fitting etc, complete all as specified and directed by Engineer -in-Charge
M&L for disconnecting of defective transformer (indoor/outdoor type) 11KV/433 volts copper wound from power mains and dismantling the same from 2/4 pole structure/ platform mounted and transporting the same to workshop in the presence of rep of AGE (I) and opening the transformer cover, draining out of transformer oil and keep safely for reuse after filtration, assembling, removing of the burnt parts i.e. tape, paper insulating strings etc gently and carefully, washing of the dust, rust and dirt from all parts including taking out HT/LT leg coil core tank and cooling tubes, painting the inner side tank by zinc chromate paint and preparing the same for re-assembling after carrying out required repair and installation on existing 2/4 pole structure/ platform with necessary fixing arrangement including connecting up electrically, commissioning and testing etc complete all as specified and directed by Engineer-in-Charge and specified in particular specification of the following capacity :- NOTE: (i) Repair cost is deemed to be included labour,transportation, balancing or alignment of core etc in the quoted rate; and Unserviceable items required to be replaced shall be measured and paid separately. (ii) The burnt transformer oil will be contractor property & any new oil will be measured and paid separately under respective item. (iii) The coils and the oil shall be inspected for repair/replacement by department rep detailed by AGE (I)(P).
(a) 63 KVA to 160 KVA capacity
(b) 350 KVA to 400 KVA capacity
Supply only following parts for indoor /outdoor transformer :-
(a) HT/ LT leg coil with insulation for copper wound transformer of any type / capacity including rewinding.
Supply only HT porcelain bushing complete with brass/tinned copper rod with nuts and gasket set complete for following cap transformer :-
(a) 63 KVA to 160 KVA capacity
(b) 350 KVA to 400 KVA capacity
Supply only LT porcelain bushing complete with brass/tinned copper rod with nuts and gasket set complete for following cap transformer :-
(a) 63 KVA to 160 KVA capacity
(b) 350 KVA to 400 KVA capacity
M&L for disconnecting of defective power transformer (outdoor type) 33KV/11KV volts, 3 phase, 3.15 MVA copper wound from power mains and dismantling the same from platform and transporting the same to workshop in the presence of rep of AGE (I) and opening the transformer cover, draining out of transformer oil, assembling, removing of the burnt windings, defective parts i.e. tape, paper insulating strings, repair of core frame, balancing or aligment of core etc gently and carefully, washing of the dust, rust and dirt from all parts including taking out leg coil core tank and cooling tubes, painting the inner side tank by zinc chromate paint and preparing the same for re-assembling after carrying out required repair and installation on existing platform with necessary fixing arrangement including connecting up electrically, earthings, commissioning and testing etc. complete all as specified and directed by Engineer-in-Charge and specified in particular specification.
NOTE: (i) Repair cost is deemed to be included labour,transportation, balancing or alignment of core etc in the quoted rate; and Unserviceable items required to be replaced shall be measured and paid separately. (ii) The burnt transformer oil will be contractor property & any new oil will be measured and paid separately under respective item. (iii) The coils and the oil shall be inspected for repair/replacement by department rep detailed by GE.
Supply only following parts for outdoor transformer :-
(a) HT leg coil 33/11 KV with insulation for copper wound transformer of any type / capacity including rewinding.
(b) Supply only HT porcelain bushing 33 KV complete with brass/tinned copper rod with nuts and gasket set
(c) Supply only HT porcelain bushing 11 KV complete with brass/tinned copper rod with nuts and gasket set
(d) Supply only transformer oil having dielectric strength 40-60 KV and conforming to IS-335 complete.
M&L for refilling fresh Silica Gel into the breather including removal of unserviceable item. etc. complete all as specified and directed
Checking and calibration of various type of safety relays installed in HT VCB incoming panel 33 KV with secondary injuction test set including checking and coordination of relay settings. (a) Digital multifunction relay. (b) Trip circuit supervision relay. (c) Master trip relay. (d) Auxilary relay for Buch, WTI, OTI trip.
Checking and calibration of various type of safety relays installed in HT VCB outgoing panel 33 KV with secondary injuction test set including checking and coordination of relay settings. (a) Digital multifunction relay. (b) Trip circuit supervision relay. (c) Master trip relay. (d) Auxilary relay for Buch, WTI, OTI trip. (e) Auxilary relay for Buch, WTI, OTI Alarm. (f) Auxilary relay for PRV trip & MOG Alarm.
Checking and calibration of various type of safety relays, installed in HT incoming panel 11 KV with secondary injuction test set including checking and coordination of relay settings. (a) Over current & earth fault relay (b) Trip circuit supervision relay. (c) Master trip relay. (d) Fuse failure relay.
Checking and calibration of various type of safety relays, installed in HT outgoing panel 11 KV with secondary injuction test set including checking and coordination of relay settings. (a) Over current & earth fault relay (b) Trip circuit supervision relay. (c) Master trip relay.
Checking the functioning of buchholz relay, O.T.I & W.TI of 02 Nos of 3.15 MVA power transformers incl
Note for item No 34 to 38 :- (i) All testing eqpt & any minor parts required to functioning relays of VCB is incl in the quoted rate (ii) The report shall be submitted to the Dept in triplicate. (iii) Transportation, lodging & boarding of Visiting Engineer is deemed incl in the quoted rate..
M&L for disconnecting of defective HT Panel of 33KV volts, 3 phase from power mains and removing of the burnt or defective parts i.e. CT, PT,Insulator, Busbar, contact piece or any other connected item etc. gently and carefully, washing of the dust, rust, carbon and dirt from all parts, busbar, walls of panel and painting the inner side of panel by zinc chromate paint and preparing the same for re-assembling after carrying out required repair and installation new parts with necessary fixing arrangements, nut, bolts etc. including connecting up electrically and testing etc complete all as specified and directed by Engineer-in-Charge and specified in particular specification. Note:- (i) Repair cost is deemed to be included in the quoted rate; and Unserviceable items required to be replaced shall be measured and paid separately. (ii) The burnt parts will be contractor property & any new part will be measured and paid separately under respective item.
(a) Epoxy Insulator 100mm dia, 33KV, 4 holes of 16mm dia type, 300mm long as per existing make&model.
(b) CT suitable for 33 KV VCB Panel, copper wound, P1/P2 type of ratio 200-150/5-5A as per IS 2705-1992, Ins. Class B, HSV/IL : 36/70/170KVp, 50 Hz, Str-25 KA / 1 Sec, VA/class for core 1 - 15 VA /class 1.0 and for core 2 - 15 VA /class SP10 as per existing make and model or as directed by EIC.
(c) PT suitable for 33 KV VCB Panel, copper wound, P1/P2 type of ratio 33000/110 Volt as per IS 2705-1992, Ins. Class B, 50 Hz, Str-25 KA / 1 Sec, as per existing make and model or as directed by EIC.
All as per item No. 39 above, but for 11 KV HT VCB panel cmplete all as directed.
(a) Epoxy Insulator 40mm dia, 11KV, single holes of 12mm dia type, 150mm long as per existing make & model.
(a) CT suitable for 11 KV VCB Panel, copper wound, P1/P2 type of ratio 100-50/5-5A, 50 Hz as per IS-2705/1992, Ins. Class B, as per existing make and model or as directed by EIC.
(c) PT suitable for 11 KV VCB Panel, copper wound, P1/P2 type of ratio 11000/110 Volt, 50 Hz as per IS-3156/1992 , Ins. Class B, 50 Hz, as per existing make and model or as directed by EIC.
S&F porclain HRC AVT type fuse HT 11 KV, 1 Amps suitable for 11 KV VCB.
S&F 11 KV post type porclain insulator 320mm CD suitable for 11 KV rotating type GOD incl necessary fittings complete all as directed by EIC.
S.R.Enterprises
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .