Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | Ist₹3.9 LAccepted-AOC | Ist | Accepted-AOC L-1 Bidder | |
| 2 | IInd₹4.0 LRejected-Finance | IInd | Rejected-Finance L-2 Bidder | |
| 3 | IIIrd₹4.0 LRejected-Finance | IIIrd | Rejected-Finance L-3 Bidder |
Tender Value
₹4.0 L
EMD Value
₹4,000
Closing Date
11 Jan 2024, 12:00 pmClosed
SE, ETC, Varanasi
Bhikharipur, DLW, Varanasi
INSTALLATION AND COMMISSIONING OF 400KV DUPLICATE BUS BAR PROTECTION PANEL (NELUMBO MAKE) ALONG WITH OTHER ASSOCIATED WORKS
2023_UPTCL_867740_1
E-Tender no. 51/2023-24/ETC/VNS
Open Tender
Electrical Works
Item Rate
45 days
400KV SUB STATION SARNATH
Fee/EMD/PAN/GST Registration and experience for execution of work as per specification
2 documents required · 2 mandatory
₹590
SE ETC-VARANASI
₹4,000
13 Mar 2024
8 Dec 2023
12 Jan 2024
8 Dec 2023
11 Jan 2024
25 Dec 2023
Amount
Installation & Commissioning of 400KV Duplicate Bus Bar Protection Panel (Nelumbo make) along with other associated Works at 400KV Sub Station Sarnath, Varanasi, with all Cost of Men, Misc. Consumables, T&Ps, etc. Required for Satisfactory Completion of the Job, as per Technical Specifications & Direction of the Supervising Engineer, as per Details below :
Preparation of Inter Connection Wiring Diagram and cable schedule for new 400KV Duplicate Bus Bar Protection Panel (Nelumbo make) drawing and 400KV Isolators and CBs (as required) to complete the job satisfactory and providing of Wiring Schedule Drawing in 3 Set as per executed Inter Connection Wiring Diagram.
Erection of new 400KV Duplicate Bus Bar Protection Panel (Nelumbo make) at suitable place in control room as per instruction of Supervising Engineer after shifting of the same from storage place to erection site including earthing of panels, filling of the gap between Panels by MS sheet and painting it by appropriate colour.
Making Inter Connection Wiring of 12 No. 400KV Feeder Bay to connect each feeder to 400KV Duplicate Bus Bar Protection Panel, Termination of all internal connection wiring of all 12 Nos. 400KV Bays as per prepared Internal Connection Wiring Diagram. Internal wiring shall be made with crimping type and tinned copper lug with insulation sleeves and shall be provided with proper ferrules at both ends and ferrules should be marked with corresponding panels at both ends wire including all consumable materials such as : 1.5/2.5 mm2 flexible cables, lugs, gland, ferrules etc. excluding control cable and manpower to assist the panel manufacturing company commissioning engineer at site till works complete in all respect.
Separation of 1 Core of CT from LBB relay and make it in series with Main-II Protection Core and change the CT ratio in CT Terminal Box (spared Core) from 1000/1 to 2000/1 Amp. To use this Spare Core for 400KV Duplicate Bus Bar Protection. Laying & Termination of 4C x 2.5 mm2 cable from each 400KV Feeder Panel to 400KV Duplicate Bus Bar Protection Panel.
Laying of control cable from different 400KV Isolators / CBs to appropriate C&R Panels / BMKs / Bus Bar Control Panels in control room as required for status in 400KV Duplicate Bus Bar Protection Panel. The work also includes checking and tracing of existing control cables from different 400KV Isolators to C&R Panels.
4C / 5C x 2.5 mm2
Termination of above laid Control Cable from both sides as per schematic drawing & cable schedule including glanding, proper ferruling, dressing, Tying and Tagging of Cables. (Both ends Termination of Control cable will be considered as 1 No.)
Meena Elect & Engg. Works
Perfect Power Transformer Associates
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .