Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹47.8 LAccepted-AOC NEAR TELEPHONE EXCHANGE DHANPURI DISTT SHAHDOL MADHYA PRADESH | DHANPURI | SHAHDOL | MADHYA PRADESH | 484114 | L-1 | Accepted-AOC Accepted as L-1 | |
| 2 | L-2₹49.0 L+₹1.2 L (2.55%)Rejected-Finance MISSION HOSPITAL CHOWK KEDARPUR AMBIKAPUR DIST SURGUJA CG 497001 | AMBIKAPUR | SURGUJA | CHHATTISGARH | 497001 | L-2 | Rejected-Finance Rejected as L-2 | |
| 3 | Rejected-Technical CAMP CHACHAI DISTT ANUPPUR MP 484220 | CHACHAI | ANUPPUR | MADHYA PRADESH | 484220 | - | Rejected-Technical Rejected |
Tender Value
₹72.7 L
EMD Value
₹90,900
Closing Date
16 May 2024, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Staff Officer EnM SECL Sohagpur Area
Staff Officer EnM SECL Sohagpur Area Dhanpuri Distt Shahdol MP 9424141331
Erection and dismantling of HT and LT overhead lines for Amlai OCM Sohagpur Area
2024_SECL_307168_1
SECL/SGP/EnM/eT/24-25/237 Dtd 27.04.2024
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
Amlai OCM Sohagpur Area
As per NIT and Tender documents
6 documents required · 6 mandatory
₹90,900
6 Jul 2024
29 Apr 2024
18 May 2024
29 Apr 2024
16 May 2024
30 Apr 2024
29 Apr 2024 - 9 May 2024
Amount
Erection and Dismantling of HT and LT overhead lines at Amlai OCM, Sohagpur Area
HT Line Erection - Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand :6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc.as required. Above 08.00 metre and upto 11.00 metre
Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand :6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc.as required. Above 11.00 metre and upto 13.00 metre
Supplying and erection of stay set complete (galvanised) with 19/20 mm dia X 1.8 metres long stay rod, anchor plate of size 45 cm X 45 cm X 7.5 mm, thimble, stay clamps, turn buckle ( 20 mm X 60 cm ), 7/ 4.00 mm dia G.I. stay wire and strain insulator etc in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling etc. as required.
Supplying and erection of a set of cross bracing frame work for 11 KV over head line double pole structure having four members fabricated out of 50 mm X 50 mm X 6 mm angle iron to form a rectangle of minimum size 1400 mm width X 2500 mm height, complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts and nuts etc (as per drawing) and painting with primer and finish paint as required (Required steel materials shall be supplied by the contractor)
Erection of pole top/ straight two wire/ V shape two wire, angle iron/ channel iron, cross arm on steel tubular/ rail/ PCC pole for 11/22/33 KV as required.
Erection of double pole 3 wire cross arm for 11KV/ 22KV/ 33 KV over head lines as required.
Erection of disc/ pin insulator for 11 KV over head lines as required.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. (All required materials shall be supplied by the contractor)
Fixing of 11 KV AB Switch
Stringing of Line (ACSR DOG conductor) ALL 03 Condtr
Stringing of Line (ACSR Rabbit conductor) single condtr
Carpet Guarding (Material will be supplied by the company)
Supply of flat iron Clamp ( 50mm x 6mm) for pipe/pole
HT Danger Notice plate 250mm x200mm
Painting of poles ( AL Paint) (All materials shall be supplied by the contractor)
HT Line Dismantling - Dismantling of over head lines comprising of copper/ aluminium over head conductor, G.I. wire, cross arms, insulators etc. as required.
Dismantling of pole/ street light standard/ strut embedded in cement concrete foundation etc. as required.
LT Line Erection - Erection of metallic pole of 8.0 meter and upto 11.0 meter following length in cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required.
Supplying and erection of stay set complete (galvanised) with 19/ 20 mm dia X 1.8 metres long stay rod, anchor plate of size 45 cm X 45 cm X 7.5 mm thick, thimble, stay clamps, bow tightener, 7/ 3.15 mm dia G.I. stay wire and strain insulator etc in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling etc. as required
Providing of Shackle insulator ( 100mm x110mm) WITH GI Bolts and nuts
Providing of Pin insulator (100mm x80mm) WITH GI Spindle and nut
Erection of angle iron/ channel iron cross arm on RCC/ PCC pole
Erection of LV/MV shackle/pin insulator Complete
Stringing of Line (acsr rabbit condtr) 03 wire
Erection of Cradle Guard (Material will be supplied by the company)
LT Line Dismantling - Dismantling of over head lines comprising of copper/ aluminium over head conductor, G.I. wire, cross arms, insulators etc. as required.
Dismantling of pole/ street light standard/ strut embedded in cement concrete foundation etc. as required.
Total impact of GST for the purpose of CTC
MS R.P. JAISWAL
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .