| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹48.7 CrAccepted-AOC | ₹48.7 Cr Quoted ₹39.9 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹40.2 Cr+₹31.6 L (0.79%)Rejected-AOC | ₹40.2 Cr+₹31.6 L (0.79%) | L2 | Rejected-AOC L2 |
| 3 | L3₹40.7 Cr+₹81.5 L (2.04%)Rejected-AOC B 3 RAVAJI SOJPAL BUILDING S D LANJEKAR MARG SEWREE MUMBAI 400015 | MUMBAI | MUMBAI | MAHARASHTRA | 400015 | ₹40.7 Cr+₹81.5 L (2.04%) | L3 | Rejected-AOC L3 |
| Sl No | Description | Qty | Unit | Sai Electricals and Engineers L2 | ELECTROCOOL ENGINEERING L3 | CHAITRA ELECTRICALS AND ENGINEERING L1 |
|---|---|---|---|---|---|---|
| 1.00 | Supply,Installation,Testing & Commissioning of 3000 KVA, 11/0.433 kV Natural Ester Oil (KNAN), Indoor Type, ON LOAD Tap Changer (OLTC) Hermetically Sealed Corrugated Tank Dist. Transformer. The Cable termination bushings shall be horizontally placed to avoid any stress on the bushings. No deviation on cable termination system is acceptable.
ACCESSORIES FOR TRANSFORMER:
• Rating & Diagram Plate • Earthing Terminals • Lifting Lugs • Plain Oil Level Gauge • Bottom Filter cum Drain Valve with Plug • Top Filter Valve with Plug • Pulling Lugs • Thermometer Pocket • Silica Gel Breather • Conservator • Cover Lifting Lugs • Inspection Window • Air Release Plug • Dial type OTI • Dial type WTI • HV Termination- Cable Box • LV Termination- Bus-Duct • Bidirectional Rollers - Yes • OLTC (EASUNMR/CTR) - Yes • Marshalling Box with OTI and WTI - Yes • MOG - Yes • BUCHHOLZ RELAY – Yes • RTCC Panel • QR Code based digital documents • Temperature Sensors • Condition Health Monitoring • C3 Painting Scheme
Make & Model : Toshiba, Schneider, CGL, Siemens | 2 | NOS | 2,08,90,000 ₹4,17,80,000 Lowest | 2,11,00,000 ₹4,22,00,000 | - |
| 2.00 | Supply,Installation,Testing & Commissioning of 1250 KVA, 11/0.433 kV Natural Ester Oil (KNAN), Indoor Type, ON LOAD Tap Changer (OLTC) Hermetically Sealed Corrugated Tank Dist. Transformer. The Cable termination bushings shall be horizontally placed to avoid any stress on the bushings. No deviation on cable termination system is acceptable.
ACCESSORIES FOR TRANSFORMER:
• Rating & Diagram Plate • Earthing Terminals • Lifting Lugs • Plain Oil Level Gauge • Bottom Filter cum Drain Valve with Plug • Top Filter Valve with Plug • Pulling Lugs • Thermometer Pocket • Silica Gel Breather • Conservator • Cover Lifting Lugs • Inspection Window • Air Release Plug • Dial type OTI • Dial type WTI • HV Termination- Cable Box • LV Termination- Bus-Duct • Bidirectional Rollers - Yes • OLTC (EASUNMR/CTR) - Yes • Marshalling Box with OTI and WTI - Yes • MOG - Yes • BUCHHOLZ RELAY – Yes • RTCC Panel • QR Code based digital documents • Temperature Sensors • Condition Health Monitoring • C3 Painting Scheme
Make & Model : Toshiba, Schneider, CGL, Siemens | 3 | NOS | 75,00,000 ₹2,25,00,000 Lowest | 76,00,000 ₹2,28,00,000 | - |
| 3.00 | Supply,Installation,Testing & Commissioning of 630 KVA, 11/0.433 kV Natural Ester Oil (KNAN), Indoor Type, ON LOAD Tap Changer (OLTC) Hermetically Sealed Corrugated Tank Dist. Transformer. The Cable termination bushings shall be horizontally placed to avoid any stress on the bushings. No deviation on cable termination system is acceptable.
ACCESSORIES FOR TRANSFORMER:
• Rating & Diagram Plate • Earthing Terminals • Lifting Lugs • Plain Oil Level Gauge • Bottom Filter cum Drain Valve with Plug • Top Filter Valve with Plug • Pulling Lugs • Thermometer Pocket • Silica Gel Breather • Conservator • Cover Lifting Lugs • Inspection Window • Air Release Plug • Dial type OTI • Dial type WTI • HV Termination- Cable Box • LV Termination- Bus-Duct • Bidirectional Rollers - Yes • OLTC (EASUNMR/CTR) - Yes • Marshalling Box with OTI and WTI - Yes • MOG - Yes • BUCHHOLZ RELAY – Yes • RTCC Panel • QR Code based digital documents • Temperature Sensors • Condition Health Monitoring • C3 Painting Scheme
Make & Model : Toshiba, Schneider, CGL, Siemens | 1 | NOS | 56,25,000 ₹56,25,000 Lowest | 56,85,000 ₹56,85,000 | - |
| 4.00 | Supply, Erection, Testing and Commissioning of 11 KV, 630A, 20kA to 25kA for 3sec, SF6-Free / Solid Insulation, Motorized, Indoor, Non-Extensible RMU , type tested in line with latest IEC standards. The RMU shall be suitable for operations at a height up to 1000 meters above sea level and at 40 degree ambient temperature without any derating. The switchgear and busbar shall all be contained in a stainless steel enclosure filled with SF6-Free Gas/ Solid insulation. The RMU tank shall provide full insulation, making the switchgear insensitive to the environment with degrees of protection of IP67 . The switchgear operating mechanism shall have an IP4X protection and cable chamber shall have IP4X. Accidental overpressure due to an internal arc is limited by the opening of the safety valve, at the bottom of the metal enclosure, away from the operator. An operator situated in front, lateral and rear (A-FLR 20kA to 25kA – 1sec, downwards exhaust, for tank as well as cable compartment) of the RMU switchboard during an internal fault will not be exposed to the effects of arcing. Plug in type of extensibility must be provided and coupling busbar should not be exposed to air to avoid oxidation of busbars. All operations shall be from front of the RMU, including access to cable bushings. Cable bushings along the sides or the rear of the RMU are not acceptable. There shall be no toxic by-products generation due to breaking operations inside SF6-Free Gas /Solid insulation tank. No requirement of special processing of gas recovery at the end-of-life of product. The RMU shall be integrated with FRTU for SCADA connectivity & remote operations. For reliability & certainity of earthing operation, there shall be provision of earth switch contact visibility on the front LV box of RMU. -11kV, 4 Way Ring Main Units -
A. Each of the above Ring Main Unit shall comprise of the followings:
1. Vacuum circuit breaker (VCB) each comprising of the following: - 4nos
2. 11 KV, 630A, 20KA for 3sec Motorized VCB with spring charged mechanism and series trip coil; with built in manual line side three position disconnector cum earth switch. Earthing should be completed within 3 operations only (i.e 1. Breaker - OFF; 2. Disconnector - OFF, 2. Earth switch - ON). Vaccuum interrupter should be of same make as that of RMU. The circuit breakers shall have 2 positions: open or disconnected and closed. A separate and independent 3 position earthing switch and disconnector shall be fitted to open and earth the cables in such way that interlocks prevent all unauthorized operations. An independent mechanism shall be fitted for the 3 positions earthing switch and disconnector. Circit breaker shall have a min of 10000 mechanical (M2). Disconnector and earthswitch shall have a min of 1000 (M1) mechanical operations. The earthing switch shall be fitted with its own operating mechanism and manual closing shall be driven by a fast-acting mechanism, independent of operator action. - 4Nos
3. Position indicator through clear front mimic in line with IEC 62271-103 - 4Nos
4.. Self powered relay with O/C , E/F protection. Relay should have a front USB port for laptop interface , LCD display ,10 event records, 5 fault records with time stamp, min 2 setting group and keypad for setting parameters for the relay. Relay should be of same make as that of RMU - 4Nos
5. Suitable ratio CT, Class 5P10, 2.5VA for protection - 4 set
6. Suitable ratio CT, Class 0.5, 2.5VA for metering - 4 set
7. Live cable indicator with indications (Voltage Presence Indicator) at the front and three inlets provision to check the synchronization of phases.VPI should be of same make as that of RMU - 4 set
8. Cable box with termination bushing suitable for upto 1 RUN 3Cx300 Sq mm, XLPE cable - 4 set
9. Cable Boots suitable for actual cable size - 4 set
10. Mechanical operation counter - 4 set
11. Mechanical On, Off push button - 4 set
B .Accessories :
Operating handle Battery 24V DC , 12Ah, Battery charger (I/P-230V AC, O/P - 24V DC) , Manometer with remote contact - 1 set
C. Metering Panel Line Connected - this panel shall be connected by cable to RMU Incomer - Cable-in Cable-out type panel -
Single Phase PTs 11 kV/rt3 / 110V/rt3; Class 0.5; 25 VA - 3 nos, MFM - EM 6400NG Class 0.5 , RYB Phase Indicating Lamps - 1 set
D. FRTU - Feeder Remote Terminal Unit with Modular Units for each function with built-in Mimic and Modem - 1 set
Make & Model : ABB (PrimeGear ZX0), Siemens(Nxplus C Blu GIS), Eaton (Xiria) and Schneider Infra (GM-AirSet). | 6 | Set | 84,00,000 ₹5,04,00,000 Lowest | 85,00,000 ₹5,10,00,000 | - |
| 5.00 | Supply, Erection, Testing and Commissioning of 11 KV, 630A, 20kA to 25 kA for 3sec, SF6-Free / Solid Insulation, Motorized, Indoor, Non-Extensible RMU , type tested in line with latest IEC standards. The RMU shall be suitable for operations at a height up to 1000 meters above sea level and at 40 degree ambient temperature without any derating. The switchgear and busbar shall all be contained in a stainless steel enclosure filled with SF6-Free Gas / Solid insulation. The RMU tank shall provide full insulation, making the switchgear insensitive to the environment with degrees of protection of IP67 . The switchgear operating mechanism shall have an IP4X protection and cable chamber shall have IP4X. Accidental overpressure due to an internal arc is limited by the opening of the safety valve, at the bottom of the metal enclosure, away from the operator. An operator situated in front, lateral and rear (A-FLR 20 kA to 25 kA – 1sec, downwards exhaust, for tank as well as cable compartment) of the RMU switchboard during an internal fault will not be exposed to the effects of arcing. Plug in type of extensibility must be provided and coupling busbar should not be exposed to air to avoid oxidation of busbars. All operations shall be from front of the RMU, including access to cable bushings. Cable bushings along the sides or the rear of the RMU are not acceptable. There shall be no toxic by-products generation due to breaking operations inside SF6-Free Gas Tank. No requirement of special processing of gas recovery at the end-of-life of product. The RMU shall be integrated with FRTU for SCADA connectivity & remote operations. For reliability & certainity of earthing operation, there shall be provision of earth switch contact visibility on the front LV box of RMU. 11kV, 4 Way Ring Main Units .
A. Each of the above Ring Main Unit shall comprise of the followings:
1. Load Break Switch (LBS) each comprising of the following - 4 sets
2. 11 KV, 630A, 20KA for 3sec Motorized Load break switch; with built in line side manual earth switch. Earthing should be completed within 2 operations only (i.e 1. Main switch - OFF, 2. Earth switch - ON). LBS shall have 3 positions, open or disconnected, closed and earthed, and will be constructed in such a way that interlocking prevents unauthorized operations. For earth switch, manual opening and closing will be driven by a fast-acting /snap action mechanism, independent of operator action. LBS shall have a min of 5000 (M2) mechanical operations , and 5 nos closing operations at rated SC current. Earth Switch shall have 1000 (M1) mechanical operations. LBS should have 100 electrical operations at rated current. Switching operation should not generate toxic by-products inside SF6-Free Gas tank. - 4 Nos
3. Position indicator through clear front mimic in line with IEC 62271-103 - 4 Nos
4. Live cable indicator with indications (Voltage Presence Indicator) at the front and three inlets provision to check the synchronization of phases. VPI should be of same make as that of RMU - 4 nos
5. Cable box with termination bushing suitable for upto 1 RUN 3Cx300 Sq mm, XLPE cable - 4 nos
6. Fault passage indicator (FPI) with in-built Overcurrent, Short Circuit and earth fault indication . The FPI should be self-powered and should have internal lithium battery for external indication and setting of FPI in the absence of current. FPI should have 4 digit LCD display, ammeter feature and should be of same make as that of RMU - 4 nos
7. Cable Boots suitable for actual cable size - 4 Nos
8. Auxilary switch : LBS - 2 NO +2 NC, Earth switch - 1 NO + 1 NC - 4 Nos
9. 400/1A, Class 0.5, 2.5 VA Metering CT in Incomer LBS - 4 Nos
B. Accessories
Operating handle, Battery 24V DC , 12Ah, Battery charger (I/P-230V AC, O/P - 24V DC), Manometer with remote contact - 1 set
C. Metering Panel Line Connected - this panel shall be connected by cable to RMU Incomer - Cable-in Cable-out type panel -
Single Phase PTs 11 kV/rt3 / 110V/rt3; Class 0.5; 25 VA -3 nos, MFM - EM 6400NG Class 0.5, RYB Phase Indicating Lamps - 1 set
D. FRTU -
Feeder Remote Terminal Unit with Modular Units for each function with built-in Mimic and Modem - 1 set
Make & Model : ABB (PrimeGear ZX0), Siemens(Nxplus C Blu GIS), Eaton (Xiria) and Schneider Infra (GM-AirSet). | 2 | Set | 56,00,000 ₹1,12,00,000 Lowest | 56,50,000 ₹1,13,00,000 | - |
| 6.00 | 11kV Right angle silicone Coated Touchproof Terminations with Bimetallic Lugs and complete Accessories with complete cable end sealing elements at GIS Switchgears as per OEM recommendations
Make list of Bus Bar : - 3M, Hongshang, Raychem | 56 | NOS | 55,000 ₹30,80,000 Lowest | 55,375 ₹31,01,000 | 55,250 ₹30,94,000 |
| 7.00 | 3M make Cable masking, vermin proffing of cable entry and all trenches entry and exit points, HT Tapes and all required special sundry items | 1 | JOB | 70,000 ₹70,000 Lowest | 75,675 ₹75,675 | 74,000 ₹74,000 |
| 8.00 | 11kV Arc Flash Suit | 2 | NOS | 1,20,000 ₹2,40,000 Lowest | 1,26,000 ₹2,52,000 | - |
| 9.00 | S.I.T.C of Wireless Temperature Sensor [Wireless and self- powered (no auxiliary supply, no battery)] and Energy Management System and Power Quality Monitoring & Analysis with EPMNS Software Make list of WTS : - Schneider , Siemens, EATON & ABB | 1 | JOB | 8,50,000 ₹8,50,000 Lowest | 8,82,000 ₹8,82,000 | - |
| 10.00 | S.I.T.C of HMI (Panel mounted) for wireless temp sensor and complete control desk for HT and LT Panels
Make list of HMI : - Schneider, Siemens, Eaton & ABB | 1 | JOB | 5,50,000 ₹5,50,000 Lowest | 5,61,000 ₹5,61,000 | 5,53,000 ₹5,53,000 |
Tender Value
Refer Docs
EMD Value
₹49.2 L
Closing Date
4 Dec 2025, 4:00 pmClosed
EEMech(EI)const
Chief Engineer (Mechanical ,Electrical), Engineering Hub Building, Dr. E. Moses Road,
The Work of Upgradation of Electrical and Mechanical system at KEM Hospital.
2025_MCGM_1244606_1
Ch.Eng./MnE/5049 dtd. 12/11/2025
Open Tender
Electrical Works
Item Rate
730 days
KEM Hospital
please refer tender documents
3 documents required · 3 mandatory
₹35,695
₹49.2 L
Engineering Hub Building
27 Jul 2026
14 Nov 2025
5 Dec 2025
14 Nov 2025
4 Dec 2025
14 Nov 2025
20 Nov 2025
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply,Installation,Testing & Commissioning of 3000 KVA, 11/0.433 kV Natural Ester Oil (KNAN), Indoor Type, ON LOAD Tap Changer (OLTC) Hermetically Sealed Corrugated Tank Dist. Transformer. The Cable termination bushings shall be horizontally placed to avoid any stress on the bushings. No deviation on cable termination system is acceptable.
ACCESSORIES FOR TRANSFORMER:
• Rating & Diagram Plate • Earthing Terminals • Lifting Lugs • Plain Oil Level Gauge • Bottom Filter cum Drain Valve with Plug • Top Filter Valve with Plug • Pulling Lugs • Thermometer Pocket • Silica Gel Breather • Conservator • Cover Lifting Lugs • Inspection Window • Air Release Plug • Dial type OTI • Dial type WTI • HV Termination- Cable Box • LV Termination- Bus-Duct • Bidirectional Rollers - Yes • OLTC (EASUNMR/CTR) - Yes • Marshalling Box with OTI and WTI - Yes • MOG - Yes • BUCHHOLZ RELAY – Yes • RTCC Panel • QR Code based digital documents • Temperature Sensors • Condition Health Monitoring • C3 Painting Scheme
Make & Model : Toshiba, Schneider, CGL, Siemens | 2 | NOS | - | - |
| 2 | Supply,Installation,Testing & Commissioning of 1250 KVA, 11/0.433 kV Natural Ester Oil (KNAN), Indoor Type, ON LOAD Tap Changer (OLTC) Hermetically Sealed Corrugated Tank Dist. Transformer. The Cable termination bushings shall be horizontally placed to avoid any stress on the bushings. No deviation on cable termination system is acceptable.
ACCESSORIES FOR TRANSFORMER:
• Rating & Diagram Plate • Earthing Terminals • Lifting Lugs • Plain Oil Level Gauge • Bottom Filter cum Drain Valve with Plug • Top Filter Valve with Plug • Pulling Lugs • Thermometer Pocket • Silica Gel Breather • Conservator • Cover Lifting Lugs • Inspection Window • Air Release Plug • Dial type OTI • Dial type WTI • HV Termination- Cable Box • LV Termination- Bus-Duct • Bidirectional Rollers - Yes • OLTC (EASUNMR/CTR) - Yes • Marshalling Box with OTI and WTI - Yes • MOG - Yes • BUCHHOLZ RELAY – Yes • RTCC Panel • QR Code based digital documents • Temperature Sensors • Condition Health Monitoring • C3 Painting Scheme
Make & Model : Toshiba, Schneider, CGL, Siemens | 3 | NOS | - | - |
| 3 | Supply,Installation,Testing & Commissioning of 630 KVA, 11/0.433 kV Natural Ester Oil (KNAN), Indoor Type, ON LOAD Tap Changer (OLTC) Hermetically Sealed Corrugated Tank Dist. Transformer. The Cable termination bushings shall be horizontally placed to avoid any stress on the bushings. No deviation on cable termination system is acceptable.
ACCESSORIES FOR TRANSFORMER:
• Rating & Diagram Plate • Earthing Terminals • Lifting Lugs • Plain Oil Level Gauge • Bottom Filter cum Drain Valve with Plug • Top Filter Valve with Plug • Pulling Lugs • Thermometer Pocket • Silica Gel Breather • Conservator • Cover Lifting Lugs • Inspection Window • Air Release Plug • Dial type OTI • Dial type WTI • HV Termination- Cable Box • LV Termination- Bus-Duct • Bidirectional Rollers - Yes • OLTC (EASUNMR/CTR) - Yes • Marshalling Box with OTI and WTI - Yes • MOG - Yes • BUCHHOLZ RELAY – Yes • RTCC Panel • QR Code based digital documents • Temperature Sensors • Condition Health Monitoring • C3 Painting Scheme
Make & Model : Toshiba, Schneider, CGL, Siemens | 1 | NOS | - | - |
| 4 | Supply, Erection, Testing and Commissioning of 11 KV, 630A, 20kA to 25kA for 3sec, SF6-Free / Solid Insulation, Motorized, Indoor, Non-Extensible RMU , type tested in line with latest IEC standards. The RMU shall be suitable for operations at a height up to 1000 meters above sea level and at 40 degree ambient temperature without any derating. The switchgear and busbar shall all be contained in a stainless steel enclosure filled with SF6-Free Gas/ Solid insulation. The RMU tank shall provide full insulation, making the switchgear insensitive to the environment with degrees of protection of IP67 . The switchgear operating mechanism shall have an IP4X protection and cable chamber shall have IP4X. Accidental overpressure due to an internal arc is limited by the opening of the safety valve, at the bottom of the metal enclosure, away from the operator. An operator situated in front, lateral and rear (A-FLR 20kA to 25kA – 1sec, downwards exhaust, for tank as well as cable compartment) of the RMU switchboard during an internal fault will not be exposed to the effects of arcing. Plug in type of extensibility must be provided and coupling busbar should not be exposed to air to avoid oxidation of busbars. All operations shall be from front of the RMU, including access to cable bushings. Cable bushings along the sides or the rear of the RMU are not acceptable. There shall be no toxic by-products generation due to breaking operations inside SF6-Free Gas /Solid insulation tank. No requirement of special processing of gas recovery at the end-of-life of product. The RMU shall be integrated with FRTU for SCADA connectivity & remote operations. For reliability & certainity of earthing operation, there shall be provision of earth switch contact visibility on the front LV box of RMU. -11kV, 4 Way Ring Main Units -
A. Each of the above Ring Main Unit shall comprise of the followings:
1. Vacuum circuit breaker (VCB) each comprising of the following: - 4nos
2. 11 KV, 630A, 20KA for 3sec Motorized VCB with spring charged mechanism and series trip coil; with built in manual line side three position disconnector cum earth switch. Earthing should be completed within 3 operations only (i.e 1. Breaker - OFF; 2. Disconnector - OFF, 2. Earth switch - ON). Vaccuum interrupter should be of same make as that of RMU. The circuit breakers shall have 2 positions: open or disconnected and closed. A separate and independent 3 position earthing switch and disconnector shall be fitted to open and earth the cables in such way that interlocks prevent all unauthorized operations. An independent mechanism shall be fitted for the 3 positions earthing switch and disconnector. Circit breaker shall have a min of 10000 mechanical (M2). Disconnector and earthswitch shall have a min of 1000 (M1) mechanical operations. The earthing switch shall be fitted with its own operating mechanism and manual closing shall be driven by a fast-acting mechanism, independent of operator action. - 4Nos
3. Position indicator through clear front mimic in line with IEC 62271-103 - 4Nos
4.. Self powered relay with O/C , E/F protection. Relay should have a front USB port for laptop interface , LCD display ,10 event records, 5 fault records with time stamp, min 2 setting group and keypad for setting parameters for the relay. Relay should be of same make as that of RMU - 4Nos
5. Suitable ratio CT, Class 5P10, 2.5VA for protection - 4 set
6. Suitable ratio CT, Class 0.5, 2.5VA for metering - 4 set
7. Live cable indicator with indications (Voltage Presence Indicator) at the front and three inlets provision to check the synchronization of phases.VPI should be of same make as that of RMU - 4 set
8. Cable box with termination bushing suitable for upto 1 RUN 3Cx300 Sq mm, XLPE cable - 4 set
9. Cable Boots suitable for actual cable size - 4 set
10. Mechanical operation counter - 4 set
11. Mechanical On, Off push button - 4 set
B .Accessories :
Operating handle Battery 24V DC , 12Ah, Battery charger (I/P-230V AC, O/P - 24V DC) , Manometer with remote contact - 1 set
C. Metering Panel Line Connected - this panel shall be connected by cable to RMU Incomer - Cable-in Cable-out type panel -
Single Phase PTs 11 kV/rt3 / 110V/rt3; Class 0.5; 25 VA - 3 nos, MFM - EM 6400NG Class 0.5 , RYB Phase Indicating Lamps - 1 set
D. FRTU - Feeder Remote Terminal Unit with Modular Units for each function with built-in Mimic and Modem - 1 set
Make & Model : ABB (PrimeGear ZX0), Siemens(Nxplus C Blu GIS), Eaton (Xiria) and Schneider Infra (GM-AirSet). | 6 | Set | - | - |
| 5 | Supply, Erection, Testing and Commissioning of 11 KV, 630A, 20kA to 25 kA for 3sec, SF6-Free / Solid Insulation, Motorized, Indoor, Non-Extensible RMU , type tested in line with latest IEC standards. The RMU shall be suitable for operations at a height up to 1000 meters above sea level and at 40 degree ambient temperature without any derating. The switchgear and busbar shall all be contained in a stainless steel enclosure filled with SF6-Free Gas / Solid insulation. The RMU tank shall provide full insulation, making the switchgear insensitive to the environment with degrees of protection of IP67 . The switchgear operating mechanism shall have an IP4X protection and cable chamber shall have IP4X. Accidental overpressure due to an internal arc is limited by the opening of the safety valve, at the bottom of the metal enclosure, away from the operator. An operator situated in front, lateral and rear (A-FLR 20 kA to 25 kA – 1sec, downwards exhaust, for tank as well as cable compartment) of the RMU switchboard during an internal fault will not be exposed to the effects of arcing. Plug in type of extensibility must be provided and coupling busbar should not be exposed to air to avoid oxidation of busbars. All operations shall be from front of the RMU, including access to cable bushings. Cable bushings along the sides or the rear of the RMU are not acceptable. There shall be no toxic by-products generation due to breaking operations inside SF6-Free Gas Tank. No requirement of special processing of gas recovery at the end-of-life of product. The RMU shall be integrated with FRTU for SCADA connectivity & remote operations. For reliability & certainity of earthing operation, there shall be provision of earth switch contact visibility on the front LV box of RMU. 11kV, 4 Way Ring Main Units .
A. Each of the above Ring Main Unit shall comprise of the followings:
1. Load Break Switch (LBS) each comprising of the following - 4 sets
2. 11 KV, 630A, 20KA for 3sec Motorized Load break switch; with built in line side manual earth switch. Earthing should be completed within 2 operations only (i.e 1. Main switch - OFF, 2. Earth switch - ON). LBS shall have 3 positions, open or disconnected, closed and earthed, and will be constructed in such a way that interlocking prevents unauthorized operations. For earth switch, manual opening and closing will be driven by a fast-acting /snap action mechanism, independent of operator action. LBS shall have a min of 5000 (M2) mechanical operations , and 5 nos closing operations at rated SC current. Earth Switch shall have 1000 (M1) mechanical operations. LBS should have 100 electrical operations at rated current. Switching operation should not generate toxic by-products inside SF6-Free Gas tank. - 4 Nos
3. Position indicator through clear front mimic in line with IEC 62271-103 - 4 Nos
4. Live cable indicator with indications (Voltage Presence Indicator) at the front and three inlets provision to check the synchronization of phases. VPI should be of same make as that of RMU - 4 nos
5. Cable box with termination bushing suitable for upto 1 RUN 3Cx300 Sq mm, XLPE cable - 4 nos
6. Fault passage indicator (FPI) with in-built Overcurrent, Short Circuit and earth fault indication . The FPI should be self-powered and should have internal lithium battery for external indication and setting of FPI in the absence of current. FPI should have 4 digit LCD display, ammeter feature and should be of same make as that of RMU - 4 nos
7. Cable Boots suitable for actual cable size - 4 Nos
8. Auxilary switch : LBS - 2 NO +2 NC, Earth switch - 1 NO + 1 NC - 4 Nos
9. 400/1A, Class 0.5, 2.5 VA Metering CT in Incomer LBS - 4 Nos
B. Accessories
Operating handle, Battery 24V DC , 12Ah, Battery charger (I/P-230V AC, O/P - 24V DC), Manometer with remote contact - 1 set
C. Metering Panel Line Connected - this panel shall be connected by cable to RMU Incomer - Cable-in Cable-out type panel -
Single Phase PTs 11 kV/rt3 / 110V/rt3; Class 0.5; 25 VA -3 nos, MFM - EM 6400NG Class 0.5, RYB Phase Indicating Lamps - 1 set
D. FRTU -
Feeder Remote Terminal Unit with Modular Units for each function with built-in Mimic and Modem - 1 set
Make & Model : ABB (PrimeGear ZX0), Siemens(Nxplus C Blu GIS), Eaton (Xiria) and Schneider Infra (GM-AirSet). | 2 | Set | - | - |
| 6 | 11kV Right angle silicone Coated Touchproof Terminations with Bimetallic Lugs and complete Accessories with complete cable end sealing elements at GIS Switchgears as per OEM recommendations
Make list of Bus Bar : - 3M, Hongshang, Raychem | 56 | NOS | - | - |
| 7 | 3M make Cable masking, vermin proffing of cable entry and all trenches entry and exit points, HT Tapes and all required special sundry items | 1 | JOB | - | - |
| 8 | 11kV Arc Flash Suit | 2 | NOS | - | - |
| 9 | S.I.T.C of Wireless Temperature Sensor [Wireless and self- powered (no auxiliary supply, no battery)] and Energy Management System and Power Quality Monitoring & Analysis with EPMNS Software Make list of WTS : - Schneider , Siemens, EATON & ABB | 1 | JOB | - | - |
| 10 | S.I.T.C of HMI (Panel mounted) for wireless temp sensor and complete control desk for HT and LT Panels
Make list of HMI : - Schneider, Siemens, Eaton & ABB | 1 | JOB | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.60 MB
SBD.pdf
Tender Documents • 2.09 MB
GCC.pdf
Other Document • 0.86 MB
BOQ_2146973.xls
BOQ • 0.38 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .