Loading…
Loading…
Tender Value
₹4.1 Cr
EMD Value
₹8.2 L
Closing Date
21 Sept 2026, 3:00 pm
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
DRM Priority Work
GENERAL
14 conditions · 3 needing a document upload
The tenderer must have minimum average annual contractual turnover of 'V/N' crores or 'V' crores whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIIB of PART-V of Tender Document , along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet. Please refer Clause 3.5 of PART-I of Tender Document.
Technical Eligibility Criteria:- The tenderer must have successfully completed or substantially completed any one of the following categories of work(s) during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: Three similar works each costing not less than the amount equal to 30% of advertised value of the tender, or Two similar works each costing not less than the amount equal to 40% of advertised value of the tender, or One similar work each costing not less than the amount equal to 60% of advertised value of the t e n d e r . Definition of Similar Nature of work:- Design,Supply,Installation,Testing & Commissioning of 11kV or above Sub-station including associated electrical works with or without AMC. Please refer Clause 3.4 and Clause 3.5 of PART-I of Tender Document. NOTE:- Work experience certificate from private individual shall not be considered. However, in addition to work experience certificates issued by any Govt. Organization, work experience certificate issued by Public listed company having average annual turnover of Rs 500 crore and above in last 3 financial years excluding the current financial year, listed on National Stock Exchange or Bombay Stock Exchange, incorporated/registered at least 5 years prior to closing of tender, shall also be considered provided the work experience certificate has been issued by a person authorized by the Public listed company to issue such certificates. In case tenderer submits work experience certificate issued by public listed company, the tenderer shall also submit along with work experience certificate, the relevant copy of work order, bill of quantities, bill wise details of payment received duly certified by Chartered Accountant, TDS certificates for all payments received and copy of final/last bill paid by company in support of above work experience certificate.
Special Eligibility Criteria:- Tenderers should possess a valid electrical contractor license at the time of opening of tender, issued by any state government & same should be submitted along with tender documents by all bidders including working contractors of this unit otherwise offer shall be SUMMARILY REJECTED.
29 conditions · 4 needing a document upload
Tenderer Shall submit COVER LETTER (TENDER FORM-1) as per Section 4.2 of PART-I of Tender Document duly filled. The Cover Letter must be submitted by the Tenderer on its letter head. Please refer Section 4.2 COVER LETTER , TENDER FORM-1 of PART-I of Tender Document.
The tenderer shall clearly specify whether the tender is submitted on his own (Proprietary Firm) or on behalf of a Partnership Firm / Company / Joint Venture (JV) / Registered Society / Registered Trust / Hindu Undivided Family (HUF) / Limited Liability Partnership (LLP) etc. The tenderer(s) shall enclose the attested copies of the constitution of their concern, and copy of PAN Card along with their tender. Tender Documents in such cases are to be signed by such persons as may be legally competent to sign them on behalf of the firm, company, association, trust or society, as the case may be.Tenderer shall submit the documents as mentioned in Clause 3.7 of of PART-I of Tender Document. The tenderer whether sole proprietor / a company or a partnership firm / joint venture (JV) / registered society / registered trust / HUF/ LLP etc. if they want to act through agent or individual partner(s), should submit along with the tender, a copy of power of attorney duly stamped and authenticated by a Notary Public or by Magistrate in favour of the specific person whether he/they be partner(s) of the firm or any other person, specifically authorizing him/them to sign the tender, submit the tender and further to deal with the Tender/ Contract up to the stage of signing the agreement except in case where such specific person is authorized for above purposes through a provision made in the partnership deed / Memorandum of Understanding / Article of Association /Board resolution, failing which tender shall be summarily rejected . Format of POA is given in TENDER FORM-3 of PART-I of Tender Document. A separate power of attorney duly stamped and authenticated by a Notary Public or by Magistrate in favour of the specific person whether he/they be partner(s) of the firm or any other person, shall be submitted after award of work, specifically authorizing him/them to deal with all other contractual activities subsequent to signing of agreement, if required. Note: A Power of Attorney executed and issued overseas, the document will also have to be legalized by the Indian Embassy and notarized in the jurisdiction where the Power of Attorney is being issued. However, the Power of Attorney provided by Bidders from countries that have signed the Hague Legislation Convention 1961 are not required to be legalized by the Indian Embassy if it carries a conforming Appostille certificate. The tenderer shall submit all the relevant documents mandatorily as mentioned in Clause 3.7 of PART-I of Tender Document.
Necessary information about Employment/Partnership etc. of Retired Railway Employee as per details mentioned in Clause 3.12 of PART-I of Tender Document should be given by tenderer . If no Retired Railway Employee is employed by tenderer then the tenderer shall submit an Undertaking as in Annexure-XXVI of PART-V of Tender Document that no railway employee is employed. Note:- If information as required as per above clause has not been furnished, contract is liable to be dealt in accordance with provision of clause 62 of PART-II of GCC-2022.
Tenderer should submit documents related to registration Details, PAN, GSTIN, Registered Address, Bank Details etc.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
The tenderer shall submit along with the tender document, documents in support of his/their claim to fulfill the eligibility criteria as mentioned in the tender document. Each page of the copy of documents/certificates in support of credentials, submitted by the tenderer, shall be self-attested/digitally signed by the tenderer or authorized representative of the tendering firm. Self attestation shall include signature, stamp and date (on each page). Only those documents which are declared explicitly by the tenderer as "documents supporting the claim of qualifying the laid down eligibility criteria", will be considered for evaluating his/their tender.
The Railway reserves the right to verify all statements, information and documents submitted by the bidder in his tender offer, and the bidder shall, when so required by the Railway, make available all such information, evidence and documents as may be necessary for such verification. Any such verification or lack of such verification, by the railway shall not relieve the bidder of its obligations or liabilities hereunder nor will it affect any rights of the railway there under.
In case of any wrong information submitted by tenderer, the contract shall be terminated, Bid security, Performance Guarantee (PG) and Security Deposit (SD) of contract forfeited and agency barred for doing business on entire Indian Railways for 5 (five) years.
The GST Act 2017 will be applicable as per extant policy as notified by Central/State Govt. and as amended from time to time. All the bidders/tenderers should ensure that they are GST compliant and their quoted rates are inclusive of taxes and GST @ 18%.
No Post Tender correspondence for submission of additional documents shall be entertained after opening of the Technical & Commercial offers. Even suo-moto post tender letters of the tenderers shall be treated as NULL & VOID. (Authority HQ Letter No. 74-W/O/Pt.XXV/WA/Loose dated 07.04.15).
The contract will be governed by Indian Railways Standard General Conditions of Contract updated with correction slips issued up to date of inviting tender or as otherwise specified in the tender documents.
Conditional offer and Alternative proposal by Tenderer: Tenderers shall submit offers that fully comply with the requirements of the Tender documents including the conditions of contract, design and specification requirements if any. Conditional offer or alternative offers will not be considered in tender evaluation and will be summarily rejected. The Tenderer shall have no claims in this regard whatsoever. "Any unconditional rebate offered by the tenderer should be mentioned on of 'Schedule of Quantities' specifically. To attract the rebate mentioned each page of schedule may refer the note for the conditional rebate mentioned in the end. Any rebate mentioned at any other place in tender document shall not be considered. The unconditional rebate mentioned in "Scheduled of Quantities" shall be considered while evaluation of bid." mentioned in the end. Any rebate mentioned at any other place in tender document shall not be considered. The unconditional rebate mentioned in "Scheduled of Quantities" shall be considered while evaluation of bid."
Electrical work for New Sub-Station and other Power Supply Arrangements at HW station and Kumbh Area.
30_SrDEE_G_MB_2026~NR
30_SrDEE_G_MB_2026
Open
Works - General
4 Months
Moradabad, Uttar Pradesh
₹0
₹8.2 L
28 Aug 2026
28 Aug 2026
7 Sept 2026
64 items across 2 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 3,76,95,901.31 | ||
| — | — | — | 54,62,220 | ||
| Design, Manufacture, Supply, Transportation, Installation, Testing & Commissioning (SITC) of outdoor type 500 kVA, 11/0.415 kV compact packaged substation comprising of followings: (a) HT switch gear 3 way, 11 KV 630 Amps 21 kA for 3 sec consist 03 nos. Vacuum Circuit Breaker (VCB) having inbuilt load break switch and Earth switch within SF6 insulated robotically welded Non ferrite nonmagnetic Stainless steel Tank of Thickness 2.5 mm & SS-304 with Series trip, self- powered microprocessor based numerical 3 O/C & 1 E/F relay (IDMTL + Inst.) protection. (b) Transformer 500 KVA, 11KV/415Volts DYn.11, oil filled, hermetically sealed transformer with corrugated wall designed and top bushing for HT and LT with off load type switch including all associated accessories etc. One no. (c) LT PANEL- 1000 A Aluminium Busbar (100% for Phase & 50% for Neutrals) Current density 1amp/sq mm, having IP2X, Fabrication using 1.5/2mm CRCA sheet steel complete with internal wiring consisting of 1000Amps 4P 50Hz 50KA Draw out Type (EDO) Air Circuit Breaker (ACB) with microprocessor based trip release for Overload (O/L), Short circuit (S/C) & Earth Fault (E/F) protection= 1 No., LED type Indicating Lamp - RYB, ON-OFF-TRIP, LT side metering CT 1000A/ 5A, 5VA, Cl:0.5, Digital Multifunction Meter (MFM), Cl:0.5 Accuracy with RS485 Port etc. (d) Outdoor Enclosure: Outdoor type enclosure having construction of Galvanised Sheet Steel having 1.5mm thickness for Non-load bearing & 2.0mm for Load bearing partition sheets & Door with HRCA 4.0 mm base frame. The Enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP23 degree of protection for Transformer compartment. The enclosure exterior shall be Powder Coated. Paint Shade Shall be, Encl. Body: Light Gray (RAL 7035) & Encl. Canopy: Dark Admiral Gray. Each compartment will be provided with the Door and Pad locking arrangement. The Compartment illumination lamp (LED) with door operated switch shall be provided for MV & LV compartment. As per IEC 62271-202. e) Inter connection and earthing: - Inter connection between HT switchgear & Transformer using 1Cx3Rx95 Sq.mm XLPE Single Core Aluminium Unarmoured Cable & Interconnection between Transformer & LT switchgear using Aluminium Busbars with Aluminium flexible. Internal earthing connections by using 50X6mm GI strips including Transformer Neutral. CSS enclosure should be duly type tested for internal Arc Test and as per as per technical specification with civil work as making foundation, proper fencing etc. complete in all respects. (Make: ABB,Schneider, Siemens or similar reputed make only). | — | 1.00 | — | — | |
| — | — | — | 26,77,906.16 | ||
| LT Panel (Specification IEC 61439, Panel and switchgear make shall be same, PU Gasket) Design, Supply, fixing, testing and commissioning dust & vermin proof LT panel (floor/plinth mounted, IP:54) fabricated with 2mm thick CRCA sheet steel powder coated with siemens grey, FRP coated etc. as per detailed specification, comprising with the following ACB and MCCBs fixed in it conforming to IEC 60947 or latest with digital measuring instrument & Aluminium bus-bar arrangement panel should be confirming to IEC/IS 61439 or latest and as per IE rules and site requirement & as per explanatory note. a) 1000A ACB (EDO type- electrically operated mechanism with motorized spring charging and with manual handle) type having Breaking capacity 50 KA having Closing release (XF),Opening Release (MX),Under Voltage release, Breaker Control Switch, Phase sequence relay, VMR Single phase Preventer, Auxiliary Contactor(2 NO +2 NC) ,A/M selector switch,8 inch exhaust fan with air filter ,CTs, Overload, Short-circuit, Instantaneous & Earth-fault protection, Multifunction meter RS .485 with port and 6 amp control SP MCBs complete in all respect with all standard accessories and hardware required at site =03 Nos. (2 Nos. Incoming and 1 nos. bus coupler). b) 800A ACB (EDO type- electrically operated mechanism with motorized spring charging and with manual handle) type having Breaking capacity 50 KA having Closing release (XF),Opening Release (MX),Under Voltage release, Breaker Control Switch, Phase sequence relay, VMR Single phase Preventer, Auxiliary Contactor(2 NO +2 NC) ,A/M selector switch,8 inch exhaust fan with air filter ,CTs, Overload, Short-circuit, Instantaneous & Earth-fault protection, Multifunction meter RS .485 with port and 6 amp control SP MCBs complete in all respect with all standard accessories and hardware required at site =02 Nos. Incoming (including 24V DC 25A Automatic Battery charger, Automatic Generator controller & other required accessories for 01 Nos. Incoming from DG set, Solar controller & other required accessories for 01 Nos. Incoming from Solar plant) c) 4P MCCB 400Amps 36 KA with adjustable thermal & fixed magnetic release = 02 Nos. (Outgoing). d) 4P MCCB 250Amps 36 kA with adjustable thermal & fixed magnetic release =03 Nos. (Outgoing). e) 4P MCCB 125 Amps 36 kA with adjustable thermal & fixed magnetic release =07 Nos. (Outgoing). All MCCB in Outgoing circuit will be provided with Extended Rotary Handle and Spreader Terminals - 4 Pole (Set of 4). Panel shall be complete with Aluminium busbar of 1000 A, spreader terminals, handle, meters, indication lamps & other accessories. | — | 1.00 | — | — | |
| — | — | — | 36,02,353.56 | ||
| LT Panel (Specification IEC 61439, Panel and switchgear make shall be same, PU Gasket) Design, Supply, fixing, testing and commissioning dust & vermin proof LT panel (floor/plinth mounted, IP:54) fabricated with 2mm thick CRCA sheet steel powder coated with siemens grey, FRP coated etc. as per detailed specification, comprising with the following ACB and MCCBs fixed in it conforming to IEC 60947 or latest with digital measuring instrument & Aluminium bus-bar arrangement panel should be confirming to IEC/IS 61439 or latest and as per IE rules and site requirement & as per explanatory note. a) 1000A ACB (EDO type- electrically operated mechanism with motorized spring charging and with manual handle) type having Breaking capacity 50 KA having Closing release (XF),Opening Release (MX),Under Voltage release, Breaker Control Switch, Phase sequence relay, VMR Single phase Preventer, Auxiliary Contactor(2 NO +2 NC) ,A/M selector switch,8 inch exhaust fan with air filter ,CTs, Overload, Short-circuit, Instantaneous & Earth-fault protection, Multifunction meter RS .485 with port and 6 amp control SP MCBs complete in all respect with all standard accessories and hardware required at site =03 Nos. (2 Nos. Incoming and 1 nos. bus coupler). b) 800A ACB (EDO type- electrically operated mechanism with motorized spring charging and with manual handle) type having Breaking capacity 50 KA having Closing release (XF),Opening Release (MX),Under Voltage release, Breaker Control Switch, Phase sequence relay, VMR Single phase Preventer, Auxiliary Contactor(2 NO +2 NC) ,A/M selector switch,8 inch exhaust fan with air filter ,CTs, Overload, Short-circuit, Instantaneous & Earth-fault protection, Multifunction meter RS .485 with port and 6 amp control SP MCBs complete in all respect with all standard accessories and hardware required at site =03 Nos. Incoming (including 24V DC Battery charger, Automatic Generator controller & other required accessories for 02 Nos. Incoming from DG set, Solar controller & other required accessories for 01 Nos. Incoming from Solar plant). c) 4P MCCB 400Amps 36 KA with adjustable thermal & fixed magnetic release = 05Nos. (Outgoing). d) 4P MCCB 250Amps 36 kA with adjustable thermal & fixed magnetic release =04 Nos. (Outgoing). e) 4P MCCB 125 Amps 36 kA with adjustable thermal & fixed magnetic release =08 Nos. (Outgoing). All MCCB in Outgoing circuit will be provided with Extended Rotary Handle and Spreader Terminals - 4 Pole (Set of 4). Panel shall be complete with Aluminium busbar of 1000 A, spreader terminals, handle, meters, indication lamps & other accessories. | — | 1.00 | — | — | |
| — | — | — | 7,26,935.46 | ||
| LT Panel (Specification IEC 61439, Panel and switchgear make shall be same, PU Gasket) Design, Supply, fixing, testing and commissioning dust & vermin proof LT panel (floor/plinth mounted, IP:54) fabricated with 2mm thick CRCA sheet steel powder coated with siemens grey, FRP coated etc. as per detailed specification, comprising with the following ACB and MCCBs fixed in it conforming to IEC 60947 or latest with digital measuring instrument & Aluminium bus-bar arrangement panel should be confirming to IEC/IS 61439 or latest and as per IE rules and site requirement & as per explanatory note. a) 1000A ACB (EDO type- electrically operated mechanism with motorized spring charging and with manual handle) type having Breaking capacity 50 KA having Closing release (XF),Opening Release (MX),Under Voltage release, Breaker Control Switch, Phase sequence relay, VMR Single phase Preventer, Auxiliary Contactor(2 NO +2 NC) ,A/M selector switch,8 inch exhaust fan with air filter ,CTs, Overload, Short-circuit, Instantaneous & Earth-fault protection, Multifunction meter RS .485 with port and 6 amp control SP MCBs complete in all respect with all standard accessories and hardware required at site =01 Nos. Incoming. b) 800A ACB (EDO type- electrically operated mechanism with motorized spring charging and with manual handle) type having Breaking capacity 50 KA having Closing release (XF),Opening Release (MX),Under Voltage release, Breaker Control Switch, Phase sequence relay, VMR Single phase Preventer, Auxiliary Contactor(2 NO +2 NC) ,A/M selector switch,8 inch exhaust fan with air filter ,CTs, Overload, Shortcircuit, Instantaneous & Earth-fault protection, Multifunction meter RS .485 with port and 6 amp control SP MCBs complete in all respect with all standard accessories and hardware required at site =01 Nos. Incoming (including solar controller & other required accessories for 01 Nos. Incoming from Solar plant). c) 4P MCCB 400Amps 36 KA with adjustable thermal & fixed magnetic release = 01 Nos. (Outgoing). d) 4P MCCB 250Amps 36 kA with adjustable thermal & fixed magnetic release =02 Nos. (Outgoing). e) 4P MCCB 125 Amps 36 kA with adjustable thermal & fixed magnetic release =04 Nos. (Outgoing). All MCCB in Outgoing circuit will be provided with Extended Rotary Handle and Spreader Terminals- 4 Pole (Set of 4). Panel shall be complete with Aluminium busbar of 1000 A, spreader terminals, handle, meters, indication lamps & other accessories. | — | 1.00 | — | — | |
| — | — | — | 26,96,125.36 | ||
| LT Panel (Specification IEC 61439, Panel and switchgear make shall be same, PU Gasket) Design, Supply, fixing, testing and commissioning dust & vermin proof LT panel (floor/plinth mounted, IP:54) fabricated with 2mm thick CRCA sheet steel powder coated with siemens grey, FRP coated etc. as per detailed specification, comprising with the following ACB and MCCBs fixed in it conforming to IEC 60947 or latest with digital measuring instrument & Aluminium bus-bar arrangement panel should be confirming to IEC/IS 61439 or latest and as per IE rules and site requirement & as per explanatory note. a) 1000A ACB (EDO type- electrically operated mechanism with motorized spring charging and with manual handle) type having Breaking capacity 50 KA having Closing release (XF),Opening Release (MX),Under Voltage release, Breaker Control Switch, Phase sequence relay, VMR Single phase Preventer, Auxiliary Contactor(2 NO +2 NC) ,A/M selector switch,8 inch exhaust fan with air filter ,CTs, Overload, Short-circuit, Instantaneous & Earth-fault protection, Multifunction meter RS .485 with port and 6 amp control SP MCBs complete in all respect with all standard accessories and hardware required at site =02 Nos. (1 Nos. Incoming and 1 nos. bus coupler). b) 800A ACB (EDO type- electrically operated mechanism with motorized spring charging and with manual handle) type having Breaking capacity 50 KA having Closing release (XF),Opening Release (MX),Under Voltage release, Breaker Control Switch, Phase sequence relay, VMR Single phase Preventer, Auxiliary Contactor(2 NO +2 NC) ,A/M selector switch,8 inch exhaust fan with air filter ,CTs, Overload, Short-circuit, Instantaneous & Earth-fault protection, Multifunction meter RS .485 with port and 6 amp control SP MCBs complete in all respect with all standard accessories and hardware required at site =03 Nos. Incoming (including 24V DC 25A Automatic Battery charger, Automatic Generator controller & other required accessories for 01 Nos. Incoming from DG set, Solar controller & other required accessories for 01 Nos. Incoming from Solar plant). c) 4P MCCB 400Amps 36 KA with adjustable thermal & fixed magnetic release = 01 Nos. (Outgoing). d) 4P MCCB 250Amps 36 kA with adjustable thermal & fixed magnetic release =05 Nos. (Outgoing). e) 4P MCCB 125 Amps 36 kA with adjustable thermal & fixed magnetic release =02 Nos. (Outgoing). All MCCB in Outgoing circuit will be provided with Extended Rotary Handle and Spreader Terminals - 4 Pole (Set of 4). Panel shall be complete with Aluminium busbar of 1000 A, spreader terminals, handle, meters, indication lamps & other accessories. | — | 1.00 | — | — | |
| — | — | — | 7,26,935.46 | ||
| LT Panel (Specification IEC 61439, Panel and switchgear make shall be same, PU Gasket) Design, Supply, fixing, testing and commissioning dust & vermin proof LT panel (floor/plinth mounted, IP:54 ) fabricated with 2mm thick CRCA sheet steel powder coated with siemens grey, FRP coated etc. as per detailed specification, comprising with the following ACB and MCCBs fixed in it conforming to IEC 60947 or latest with digital measuring instrument & Aluminium bus-bar arrangement panel should be confirming to IEC/IS 61439 or latest and as per IE rules and site requirement & as per explanatory note. a) 800A ACB (EDO type- electrically operated mechanism with motorized spring charging and with manual handle) type having Breaking capacity 50 KA having Closing release (XF),Opening Release (MX),Under Voltage release, Breaker Control Switch, Phase sequence relay, VMR Single phase Preventer, Auxiliary Contactor(2 NO +2 NC) ,A/M selector switch,8 inch exhaust fan with air filter ,CTs, Overload, Short-circuit, Instantaneous & Earth-fault protection, Multifunction meter RS .485 with port and 6 amp control SP MCBs complete in all respect with all standard accessories and hardware required at site =01 Nos. Incoming. b) 4P MCCB 630Amps 36 KA with adjustable thermal & fixed magnetic release = 01 Nos. (Outgoing). c) 4P MCCB 125 Amps 36 kA with adjustable thermal & fixed magnetic release =05 Nos. (Outgoing). All MCCB in Outgoing circuit will be provided with Extended Rotary Handle and Spreader Terminals - 4 Pole (Set of 4). Panel shall be complete with Aluminium busbar of 1000 A, spreader terminals, handle, meters, indication lamps & other accessories. | — | 1.00 | — | — | |
| — | — | — | 6,07,250.42 | ||
| LT Panel (Specification IEC 61439, Panel and switchgear make shall be same, PU Gasket) Design, Supply, fixing, testing and commissioning dust & vermin proof LT panel (floor/plinth mounted, IP:54) fabricated with 2mm thick CRCA sheet steel powder coated with siemens grey, FRP coated etc. as per detailed specification, comprising with the following ACB and MCCBs fixed in it conforming to IEC 60947 or latest with digital measuring instrument & Aluminium bus-bar arrangement panel should be confirming to IEC/IS 61439 or latest and as per IE rules and site requirement & as per explanatory note. a) 800A ACB (EDO type- electrically operated mechanism with motorized spring charging and with manual handle) type having Breaking capacity 50 KA having Closing release (XF),Opening Release (MX),Under Voltage release, Breaker Control Switch, Phase sequence relay, VMR Single phase Preventer, Auxiliary Contactor(2 NO +2 NC) ,A/M selector switch,8 inch exhaust fan with air filter ,CTs, Overload, Short-circuit, Instantaneous & Earth-fault protection, Multifunction meter RS .485 with port and 6 amp control SP MCBs complete in all respect with all standard accessories and hardware required at site =01 Nos. Incoming. b) 4P MCCB 250Amps 36 KA with adjustable thermal & fixed magnetic release = 01 Nos. (Outgoing). c) 4P MCCB 125 Amps 36 kA with adjustable thermal & fixed magnetic release =04 Nos. (Outgoing). All MCCB in Outgoing circuit will be provided with Extended Rotary Handle and Spreader Terminals - 4 Pole (Set of 4). Panel shall be complete with Aluminium busbar of 1000 A, spreader terminals, handle, meters, indication lamps & other accessories. | — | 1.00 | — | — | |
| — | — | — | 14,16,302.08 | ||
| Design, Fabrication, Supply, installation, testing and commissioning of complete set of APFC panel of capacity 200 KVAR with 25 KVAR-06 Nos., 15 KVAR-02 Nos., 10 KVAR - 01 Nos, 5 KVAR- 2 Nos, comprising of housing made of CRCA sheet of 2 mm thick, IP 55, corrosion proof powder coating, Heavy duty capacitors banks, Automatic Power Factor Controllers (APFC) ,Capacitor contactors, MCCB/MCB protection for all incomers and outgoing etc., suitable to work on three phase 440 Volts, 50Hz AC complete with all accessories including mounting arrangements. | — | 4.00 | — | — | |
| — | — | — | 14,83,280 | ||
| Provision, supply and laying by Horizontal Boring Trench less method 2.5 meter deep or more as per relevant IS suitable for laying HDPE Pipe of 110 mm outer dia with 6 mm wall thickness in the bore for laying of cable under track/road/culvertetc. Excavation shall be done complying with code of safety as per IS 3764/1992 and as per site requirement & technical specification. (Supply of HDPE pipe as per IS:4984-1995 (latest version) included). | — | 1000.00 | — | — | |
| — | — | — | 1,36,215.03 | ||
| Supply, installation, testing and commissioning of Straight through joint Heat Shrinkable type for 3 core 120 to 185 sq.mm XLPE insulated 11 KV(E) aluminum conductor cable with conforming to relevant IS (latest version) as per technical specification. | — | 7.00 | — | — | |
| — | — | — | 41,930.64 | ||
| Supply, installation, testing and commissioning of End termination of 3 core 120 to 185 sq.mm XLPE insulated 11 KV(E) aluminum conductor cable with heat shrinkable indoor/outdoor type cable jointing box conforming to relevant IS (latest version) as per technical specification. | — | 6.00 | — | — | |
| — | — | — | 1,27,832.04 | ||
| Earthing with 600x600x3 mm thick GI plate earth eletcrode as per IS : 3043 ( latest version ) to achieve earth resistance less than 1 ohm including construction of masonry enclosure with hinged cover plate of cast iron with locking arrangement ( Approximate size 600x600 mm. on top, watering pipe, connections from earth plate to top with 40x6 mm. GI strip in 50 mm. dia GI pipe class ' B ' provsion of earth plate as per drawing and technical specification. | — | 36.00 | — | — | |
| — | — | — | 57,488.4 | ||
| Connections with GI strips in 300 mm deep in ground / recessing in floor clamping in trenches of sub-station by grouting clamps manufacture with MS sheet 14 SWG from Earth electrode strip to HT Panel/LT Panel/AMF Panel /Transformer/ DG Set etc. as per approved drawing and technical specification including supply of material size ( 2 Nos. 40 x 5 mm. or 40 x 10 mm ). | — | 360.00 | — | — | |
| — | — | — | 54,07,371.24 | ||
| Bus Bar Trunking System Supply, Installation, Testing & Commissioning (SITC) of 250A, AIR Insulated, 3P + 100% Neutral, 25KA For 1 Sec, AL Busduct, IP 55, Enclosure in GI as per site requirement & technical specification with following accessories: (Make: Legrand,Schneider,Siemens or similar reputed make only) | details. | Breakup for | — | — | |
| — | — | — | 93,09,552.18 | ||
| "Bus Bar Trunking System Supply, Installation, Testing & Commissioning (SITC) of 630 A, 415 V, 3-Phase, 4-Wire, Aluminium Bus Trunking System, IP55 as per site requirement & technical specification with following accessories: (Make: Legrand,Schneider,Siemens or similar reputed make only)" | details. | Breakup for | — | — | |
| — | — | — | 10,21,273.48 | ||
| "Bus Bar Trunking System: Supply, Installation, Testing & Commissioning of 63 Apmps Copper, Lighting Bus Trunking System in easy detachable and conveninet assembly suitable for 415 +-10% Volts, 3 Phase+ Single Phase, 4 Wire, 50 Hz A C System with Cu Bus Conductors of 2nos x 5.73sq mm section and stainless steel / hot galvanised steel enclosure, with tap off provision every 0.5 mtr. The Lighting Bus Trunking shall be confirming to latest IEC Standards (IEC-61439-6). It shall be with IP-55 Protection, halogen free and Fault Level Withstand Capacity of 2.7 kA min for 0.1 Sec (Icw) and as per site requirement & technical specification with following accessories:. (Make: Legrand,Schneider,Siemens or similar reputed make only)" | details. | Breakup for | — | — | |
| "Bus Bar Trunking System : Supply of 160A Copper, Air Insulated Bus Trunking System, IP55 as per site requirement & technical specification with following accessories (Minisbarre of legrand or similar range of other reputed makes):.(Make: Legrand,Schneider,Siemens or similar reputed make only)" | details. | Breakup for | — | — |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TenderDocument-30.pdf
ATTACHMENT
correctionslipsmerged_compressed.pdf GCC correction slips
ATTACHMENT
JPODigging.pdf
ATTACHMENT
I.R.GCC_April-2022.pdf
ATTACHMENT
Annexure-U.pdf
ATTACHMENT
letterofcredit.pdf
ATTACHMENT
correctionslipsmerged_compressed.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .