Loading…
Loading…
Tender Value
Refer Docs
EMD Value
₹10,100
Closing Date
7 Sept 2026, 12:00 pm
Executive Engineer, Bardhaman Electrical Division,
Purta Bhavan, 1st Floor, Purba Bardhaman
Repair and Renovation of toilet blocks at Old and New Judges Court Building, Purba Bardhaman - EI work with exhaust fan and Lights
2026_WBPWD_5019524_1
WBPWD/EEBED/NIQ-59/2026-27
Open Tender
ELECTRICAL WORKS ORG
Item Rate
15 days
Purba Bardhaman
Please refer Tender documents.
4 documents required · 4 mandatory
₹10,100
office of the E.E,BED, PWD
20 Aug 2026
20 Aug 2026
9 Sept 2026
20 Aug 2026
7 Sept 2026
29 Aug 2026
27 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, on wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment [D9/13). (Make ABB ITUS, SIEMENS, L&T ) b) (2 + 4 way) | |||||
| 2Supplying and fixing 240/415 V , 40 A MCB Isolator on din rail of existing DBs and necessary connection.(D-5/6) | |||||
| 3Supplying and fixing 240/415 V(6-32 A) SP MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection for SPN Outgoing ( make- Make: Legrand, ABB, SIEMENS)(D-6/7) | |||||
| 4Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Make:-Hevells/Polycab/Finolex/RR Kabel ) partly in 20mm size PVC rigid conduit 'FR' (Precision mms make) [for ceiling portion & horizontal runs ] and in 19mm bore, 3mm thick polythene pipe [for vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish. [PVC Rigid Conduit only for horizontal run & on ceiling and vertical run concealed] (Avg. Run- 8 mtr) (E 25 / 5 c) | |||||
| 5Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Make:-Hevells/Polycab/Finolex /RR Kabel ) in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to 240 V 6A 5 pin plug point incl. S/F 240 V 6A 31 pin Modular1 type plug socket & Mod. type switch (approved by E!IC) incl. S!&F earth continuity wire1 fixed on G I Mod. switch board with Mod. top cover plate flusged in wall incl. mending good the damages as to original finish. 2x22/0.3 (Ph. & N) and 1x22/0.3 as ECC .. on board ( E-20/3(i) ) | |||||
| 6Supplying and fixing PVC Rigid Conduit 'FR' [ Make Precision Medium] on wall, ceiling with saddles and other accessories as required and mending good damages to building works (E16/7) a. 20 mm size | |||||
| 7Cutting channel of on masonry wall electric operated cutting machine incl. S&F heavy gauge polythene pipe dia as stated below, by means of iron hooks and supplying and drawing 18 SWG GI Wire as fish wire incl. mending good damages to building works, a) 19 mm dia 3 mm thick polythene pipe without earth continuity wire in 40 mm X 40 mm channel (E3/6 a) | |||||
| 8Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Make:-Hevells/Polycab/ Finolex/RR Kabel ) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required.(E-9/1) 2 x 84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC ( MS to SPN) [E-9/1y] | |||||
| 8.01 | 2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC.( SPN to power plug and Computer point) [E-9/1s] | - | mtrs | - | - |
| 9Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes etc..(F-5/9) 2x84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC .(F-5/9) | |||||
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.90 MB
NewForm2911.pdf
Tender Documents • 1.85 MB
BOQ_5092034.xls
BOQ • 0.32 MB
corri_NIQ_memo.pdf
PDF • 0.17 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].