| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.6 CrAccepted-AOC | ₹30.6 Cr | L1 | Accepted-AOC Being the Lowest and Reasonable Tender |
| 2 | L2₹31.6 CrRejected-Finance | ₹31.6 Cr | L2 | Rejected-Finance Not Being the lowest |
| 3 | L3₹32.3 CrRejected-Finance SHREE SHYAM SADAN 10 2 PARAS SOCIETY PANCHVATI JAMNAGAR GUJARAT 361008 | JAMNAGAR | GUJARAT | 361008 | ₹32.3 Cr | L3 | Rejected-Finance Not Being the lowest |
| 4 | L4₹33.6 CrRejected-Finance K 99 LGF KALKAJI NEW DELHI 110 019 | NEW DELHI | SOUTH EAST DELHI | DELHI | 110019 | ₹33.6 Cr | L4 | Rejected-Finance Not Being the lowest |
Tender Value
₹29.5 Cr
EMD Value
₹15 L
Closing Date
20 Jan 2023, 6:00 pmClosed
Chief Engineer (Navy) Mumbai
HQ CE (Navy) Mumbai, 26, Assaye Building, Colaba, Mumbai-400005
PROVISION OF DEFICIENT INFRASTRUCTURE FOR DEEP REPAIR FACILITIES AT NAY GOA
2022_MES_516607_2
87910/E8
Open Tender
Civil Works
540 days
Garrison Engineer (P) Vasco
As per tender Documents
8 documents required · 8 mandatory
₹3,000
GE (P) Vasco
₹15 L
Yes
5 Sept 2023
23 Nov 2022
23 Jan 2023
23 Nov 2022
20 Jan 2023
30 Dec 2022
23 Nov 2022 - 30 Nov 2022
Amount
SCHEDULE "A" Part - I (BUILDINGS & STRUCTURES WORKS) Total of Sch-'A' Part-I B/F
SCHEDULE "A" PART-II (SITE CLEARANCE, AREA DEVELOPMENT, EXCAVATION & EARTHWORK) Total of Sch-'A' Part-II B/F
SCHEDULE "A" PART-III (DEMOLITION/ DISMANTLING) Total of Sch-'A' Part-III B/F
SCHEDULE "A" PART-IV (INTERNAL WATER SUPPLY) Total of Sch-'A' Part-IV B/F
SCHEDULE "A" PART-V (INTERNAL ELECTRIFICATION) Total of Sch-'A' Part-V B/F
SCHEDULE "A" PART-VI (ROAD & HARDSTANDING) Total of Sch-'A' Part-VI B/F
SCHEDULE "A" PART-VII (AREA DRAINAGE) Total of Sch-'A' Part-VII B/F
SCHEDULE "A" PART-VIII (SEWAGE DISPOSAL) Total of Sch-'A' Part-VIII B/F
SCHEDULE "A" PART-IX (STEEL GATE & CHAIN LINK FENCING) Total of Sch-'A' Part-IX B/F
SCHEDULE "A" PART-X (FIREPOINT) Total of Sch-'A' Part-X B/F
SCHEDULE "A" PART-XI (EXTERNAL ELECTRIFICATION) Total of Sch-'A' Part-XI B/F
SCHEDULE "A" PART-XII (EXTERNAL WATER SUPPLY) Total of Sch-'A' Part-XII B/F
SCHEDULE "A" PART-XIII (FIREFIGHTING) Total of Sch-'A' Part-XIII B/F
SCHEDULE "A" PART-XIV (FLAME PROOF LIGHTING) Total of Sch-'A' Part-XIV B/F
SCHEDULE "A" PART-XV (BOREWELL) Total of Sch-'A' Part-XV B/F
SCHEDULE "A" PART-XVI (AIR COMPRESSOR) Total of Sch-'A' Part-XVI B/F
SCHEDULE "A" PART-XVII (LIGHTNING PROTECTION) Total of Sch-'A' Part-XVII B/F
SCHEDULE "A" PART-XVIII (WATER COOLER) Total of Sch-'A' Part-XVIII B/F
SCHEDULE "A" PART-XIX (AVIATION OBSTRUCTION LIGHT) Total of Sch-'A' Part-XIX B/F
SCHEDULE "A" PART-XX ( CONDUITS FOR TELEPHONE/ TV ) Total of Sch-'A' Part-XX B/F
SCHEDULE "A" PART-XXI ( LIFTS ) Total of Sch-'A' Part-XXI B/F
SCHEDULE "A" PART -XXIII (MISCELLANEOUS ITEMS)
INTERNAL WATER SUPPLY
S & F, 16mm dia, two way bib cock with wall flange quarter turn (Low-flow) complete all as specified and directed by Engineer - In- Charge. Make- Jaquar Model No KUP-35041PMGE or equivalent in Crab Tree/ Kohler brand
S & F, 16mm dia, Pillar Cock (Low- flow) complete all as specified and directed by Engineer - In- Charge. Make- Jaquar Model No Each KUP-35001PMG or equivalent in Crab Tree/ Kohler brand
S & F Hand shower (Health faucet) with 1 meter long easy flex tube in chrome finish and wall hook with NRV (Back flow) preventer). Make- Jaquar Model No ALD-579 complete all as specified and directed by Engineer-in-charge.
S & F Angular stop cock 15mm bore of pipe (16mm outer dia) with Each wall flange chromium plated stop valves. Make - Jaquar Model No KLP-35053 PM or equivalent complete all as specified and directed.
INTERNAL ELECTRIFICATION
S & F LED tube light fittings decorative ultra slim linear fixture with extruded aluminium heat sink environment friendly Energy efficient ready to use pack, 1x28 Watt, 4 feet, surface mounting type extruded pvc, snap on installers and domestic electronic Driver, connector block etc. with all accessories internal prewired & including connecting up with 2 core flexible copper conductor cable with suitable size & suitable for and mounting clamps PVC square box 75x75mm - 2 nos etc. Make-WIPRO /HAVELLS /JAQUAR /PHILIPS
Supply & fix LED high bay 90 Watt comprises of die cast canopy control gear housing & glass to provide great lighting experience to industrial applications lamp compartment Make -WIPRO /HAVELLS /JAQUAR /PHILIPS
S & F LED Security/Street light fittings 25 Watt wall mounting type extruded metal/aluminium body, and electronic LED driver, etc. with all accessories internal prewired & including connecting up with 2 core flexible copper conductor cable with suitable size etc. Make- WIPRO /HAVELLS /JAQUAR /PHILIPS
Fabricate, supply & fix GI pipe bracket 25mm dia- 0.9m long & 2 set of clamps made out of 30x5mm MS flat & fixed with anchor bolt suitable for 25W security light fitting
S & F Fresh air Exhaust fan of size 300 mm sweep Metal body complete with and louvers connecting up including provision of three core flexible copper wire of size 23/0.0076 from ceiling rose to exhaust fan. Make: Havells/Crompton Greaves/ Bajaj
S & F Energy efficient BEE five star rated ceiling fan, 1200 mm sweep and connecting up including provision of three core flexible copper wire of size 23/0076 from ceiling rose to ceiling fan complete in all respect all as specified and directed. Make : Crompton Greaves/ Bajaj/ Orient
S & F Energy efficient star rated wall fan, 350 mm sweep and connecting up including provision of three core flexible copper wire of size 23/0076 from ceiling rose to ceiling fan complete in all respect all as specified and directed. Make : Crompton Greaves/ Bajaj/ Orient
S & F, MCCB DB Vertical type suitable for 250 amps MCCB as incomer made of sheet steel, powder painted with NEUTRAL bus bar 200 A, neutral link, IP-43-IK09 protection grade, 415Volts TPN with 8 way Double door, L&T CAT NO-DBVTH008DD/ LEGRAND / Schneider/ ABB (Main DB for DRF Ground floor)
S & F, MCCB DB Vertical type, suitable for 125 amps MCCB as incomer, made of sheet steel, powder painted with NEUTRAL bus bar 200 A, neutral link, IP-43-IK09 protection grade, 415Volts TPN with 6 way Double door, L&T CAT NO-DBVTL006DD/ Schneider/ ABB (Main DB for DRF floor- 01 No, Special power supply-3 Nos.)
S & F, MCCB DB Vertical type, suitable for 125 amps MCCB as incomer, made of sheet steel, powder painted with NEUTRAL bus bar 200 A, neutral link, IP-43-IK09 protection grade, 415Volts TPN with 4 way Double door, L&T CAT NO-DBVTL004DD/ LEGRAND CAT NO-607913/ Schneider/ ABB (main DB for Ejection Bay- 1 No , Sp. power supply - 6 Nos & For Split AC - 6 Nos)
S & F, MCB SP 63 Amps 'C' series, breaking capacity 10 KA of rating (For SPN 12 Way DB)
S & F, MCB SP 40 Amps 'C' series, breaking capacity 10 KA of rating (For SPN 8 Way DB)
S & F MCCB 160 A 25 KA, 4 POLE, thermal magnetic release, Ics=100% Icu
S & F, MCCB 125 A 25 KA,4 POLE, thermal magnetic release, Ics=100% Icu
Supply, Installation, test and Commissioning, factory fabricated LT panel board, type tested by CPRI /Authorised Govt. Agencies , confirming to IEC 60349-1 & 2,up to 400 Amps incomer OR confirming to IEC 61349-1 & 2, above 400 Amps incomer, LT panel board made out of 2 mm thick GI Sheet multifold design, chemically treated surface with multi tank process powder coating, indoor modular type, dust free ,Vermin Proof , totally enclosed with Confirming to IP 43 for indoor panel & Confirming to IP 54 for outdoor panel ,single door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Galvanised iron Angle Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Testing after Installation including complete all as specified and comprising of the following :– Make of panel board - L&T / ABB / Schneider/Siemens or by their authorised channel partners duly authenticated by the company.(For Panel DRF Building) Make of LT panel board - L&T / ABB / Schneider/Siemens or by their authorised channel partners duly authenticated by the company.
Supply & Fix MCCB DB VERTICAL TYPE suitable for 250 amps MCCB as incomer made of sheet steel , powder painted with neutral bus bar 200 A, neutral link, IP-43-IK09 protection grade , 415Volts TPN with 12 way Double door, Make- L&T / LEGRAND / Schneider/ ABB
S & F LED CLEAN ROOM light fittings decorative 80 Watt, minimum 100 lum/watt Recess/surface mounting type 2 feet x 2 feet fitting ,made out of extruded metal/CRCA sheet body, and electronic LED driver, connector block etc.. with all accessories internal prewired & including connecting up with 2 core flexible copper conductor cable with suitable size etc. (for rooms with higher illumination as per Drg) Make- WIPRO / BAJAJ / SURYA / PHILLIPS / POLYCAB
S & F LED CLEAN ROOM light fittings decorative 60 Watt , minimum 100 lum/watt , Recess/surface mounting type, 2 feet x 2 feet fitting , made out of extruded metal/CRCA sheet body, and electronic LED driver, connector block etc.. with all accessories internal prewired & including connecting up with 2 core flexible copper conductor cable with suitable size etc. ( for rooms with higher illumination as per Drg) Make- WIPRO / BAJAJ / SURYA / PHILLIPS / POLYCAB
Copper strip 32 x 6 mm as earth continuity conductor 600 mm long, duly drilled with 10 mm dia hole in every 50 mm on entire strip for taping earthing ,fixed on wall with PVC insulated back plate/FRP Insulator at 250 mm distance with copper nuts and bolts including anchor fastner pin type complete all as specified and directed.
CABLE NETWORK FOR SPECIALIZED ITEMS
Supply, Installation, test and Commissioning, factory fabricated LT panel board, type tested by CPRI /Authorised Govt. Agencies , confirming to IEC 60349-1 & 2,up to 400 Amps incomer OR confirming to IEC 61349-1 & 2, above 400 Amps incomer, LT panel board made out of 2 mm thick GI Sheet multifold design, chemically treated surface with multi tank process powder coating, indoor modular type, dust free ,Vermin Proof , totally enclosed with Confirming to IP 43 for indoor panel & Confirming to IP 54 for outdoor panel ,single door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Galvanised iron Angle Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Testing after Installation including complete all as specified and comprising of the following :– Make of panel board - L&T / ABB / Schneider/Siemens or by their authorised channel partners duly authenticated by the company. (For Ejection Seat Complex Building special power supply)
Supply, Installation, test and Commissioning, factory fabricated LT panel board, type tested by CPRI /Authorised Govt. Agencies , confirming to IEC 60349-1 & 2,up to 400 Amps incomer OR confirming to IEC 61349-1 & 2, above 400 Amps incomer, LT panel board made out of 2 mm thick GI Sheet multifold design, chemically treated surface with multi tank process powder coating, indoor modular type, dust free ,Vermin Proof , totally enclosed with Confirming to IP 43 for indoor panel & Confirming to IP 54 for outdoor panel ,single door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Galvanised iron Angle Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Testing after Installation including complete all as specified and comprising of the following :– Make of panel board - L&T / ABB / Schneider/Siemens or by their authorised channel partners duly authenticated by the company.(For DRF Building ,special power supply)
Supply, Installation, test and Commissioning, factory fabricated LT panel board, type tested by CPRI /Authorised Govt. Agencies , confirming to IEC 60349-1 & 2,up to 400 Amps incomer OR confirming to IEC 61349-1 & 2, above 400 Amps incomer, LT panel board made out of 2 mm thick GI Sheet multifold design, chemically treated surface with multi tank process powder coating, indoor modular type, dust free ,Vermin Proof , totally enclosed with Confirming to IP 43 for indoor panel & Confirming to IP 54 for outdoor panel ,single door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Galvanised iron Angle Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Testing after Installation including complete all as specified and comprising of the following :– Make of panel board - L&T / ABB / Schneider/Siemens or by their authorised channel partners duly authenticated by the company. ( Panel for DC supply DB )( DRF Building)
Supply, Installation, test and Commissioning, factory fabricated LT panel board, type tested by CPRI /Authorised Govt. Agencies , confirming to IEC 60349-1 & 2,up to 400 Amps incomer OR confirming to IEC 61349-1 & 2, above 400 Amps incomer, LT panel board made out of 2 mm thick GI Sheet multifold design, chemically treated surface with multi tank process powder coating, indoor modular type, dust free ,Vermin Proof , totally enclosed with Confirming to IP 43 for indoor panel & Confirming to IP 54 for outdoor panel ,single door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Galvanised iron Angle Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Testing after Installation including complete all as specified and comprising of the following :– Make of panel board - L&T / ABB / Schneider/Siemens or by their authorised channel partners duly authenticated by the company.(Panel for isolation transformer 150 KVA DRF Building)
Supply and fixing of cable tray made out of galvanised perforated sheet in 12 gauge, 50mm height including accessories like coupler, wall brackets up/down elbows, bend, tees etc., and fixing with duly supported on angle iron 40x40x3 mm made in triangular shape duly welded and fix to wall using appropriate size of anchor fastner bolts. in equal distances on wall crossing and making good to the surfaces as per direction. Note: The quantity will be calculated with length of cable tray multiplied by width of cable tray ( width of cable tray plus both the different width cable tray shall be used as per cable size & requirement)
Supply, laying in duct, connecting & testing LT UG cable XLPE insulated, screened PVC bedded, unarmoured, electric power cables (heavy duty) with copper conductor, 1100 volts of the following sizes complete all as specified and directed for single core 150 sqmm laying on cable tray with proper saddles on walls/floors/ ceiling etc. complete all as specified. (from conversion machine 27 V DC rectifier to DB )
S & F, MCCB 100 A 25 KA,4 POLE ,thermal magnetic release, Ics=100% Icu (For Special Power Supply)
S & F, DC panel board made out of 2mm thick CRCA sheet power coated with DC Voltmeter & comprising of following. (a) DC MCCB DP 160A - 01 No (b) DC MCB SP 32A -09 Nos
S & F 2 pin & earth plug socket enclosures with one No of DP, DC, MCB, 25 Amps, 27 V DC
Flame Proof Plug socket suitable for IP67 degree of protection 25 Amps 5 pin, 3 phase+neutral+earth ( for 415/420 V, 3 phase)
S & F Flame Proof 2 pin & earth plug socket enclosures with one No of SP, AC, MCB, 25 Amps, (for 220 V single phase)
S & F Flame Proof 2 pin & earth plug socket enclosures with one No of SP, AC, MCB, 25 Amps, (for 115 V single phase)
S & F Flame Proof 2 pin & earth plug socket enclosures with one No of DP, DC, MCB, 25 Amps, 27 V DC
S & F sheet metal enclosure with 160 to 200 Amps, MCCB, 4 poles 35 KA for 380 V & 450V isolation transformer complete all as specified and directed.
Supply and fix Mild steel cross arms angle, bracing, support, clamps etc. fabricated structured steel, sections, including nuts, bolts, washers etc. and cutting to required length beat to any shape drilling holes, fixed to wall or jointed by means of elect welding complete
Supply and fix galvanised steel anchor fastnar bolt of size 12/16 mm dia and 100/110 mm long
Supply and Fixing ERW metallic conduit 25 mm dia including of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe
Supply & Fix Beam Master Detector, Transceiver Type including power supply unit & module
Note: All Special Power supply Equipment's/Cabinets of required KVA rating shall be supplied by user authorities and not in the scope of this work . However electric connection between main panel to Special power supply and from Special power supply to distribution LT Panel or distribution board , From the distribution board to sockets point shall be in the scope of this tender
AIR-CONDITIONING SYSTEM (CENTRAL AC PLANT)
CENTRAL AIR CONDITIONING SYSTEM Supply, install, testing and commissioning of 110 TR running capacity chilled water type central air-condtioning plant consisting of 3 x 55 TR scroll chillers (2W+1 S/By) and consisting of minimum of following sub sytems and plants, machines, motors, pumps, AHUs, pipes, valves, ductings, equipments and fittings etc all specified and as required as per the drg of the building attached showing various rooms and spaces for air-conditioning and as per the user datasheet given in the tender and as mentioned herein after including commissioning, balancing & testing for accurate performance all complete:-
WATER-COOLED SCREW TYPE CHILLER UNIT - 3 Nos (2W + 1S) Supply, installation, testing and commissioning of factory designed, pre-fabricated and floor-mounted ISEER 3 star star rated scroll type water-cooled chiller machine of nominal capacity 55 TR, complete with scroll compressors having single refrigerant circuits and automatic stepless capacity control, water-cooled S/T type condenser, ASME stamped S/T horizontal flooded type evaporator with carbon steel shell and seamless copper tubes with elastomeric insulation, suitable numbers of squirrel cage induction motors of appropriate rating with class 'B' insulation, along with necessary drive arrangement, lubrication system as per manufacturer's design required for smooth and trouble-free operation of the chiller package, common base-frame, interconnected copper refrigerant piping along with elastomeric insulation, fittings, valves, expansion valves and accessories to interconnect compressor, condenser, chiller and expansion valve, microprocessor based control panel comprising of controls including sensors and equipped with a keyboard, LCD touchscreen access input system, protection and monitoring devices to perform control functions, wiring, vibration isolators, gauge panel, automatic safety controls, flow switch at evaporator and condenser connection ends and ozone friendly, CFC-HCFC free refrigerant complete all as specified and directed by the engineer-in-charge.
CHILLED WATER CIRCULATION PUMP - 3 Nos (2W + 1S) Supply, installation, testing and commissioning of Monoblock, self-priming, single-stage centrifugal pump, capable of 290USGPM discharge at 20 MWC head, having cast iron casing, enclosed type dynamically balanced cast iron impeller, carbon steel pump shaft, gland packed sealing, deep groove ball bearings, etc. with TEFC squirrel cage induction motor having class 'B' insulation, IE3 efficiency, conforming to IS 12615: 2018 and suitable for operation on 3-Ph, 415 V±10%, 50 Hz AC supply, base plate, mounting channel frame, accessories and fittings, viz. pressure gauges, thermometers, drains, coupling, coupling guard, vibration isolation arrangement by means of spring / rubber type mounting duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of 50 mm thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and directed by the engineer-in-charge. Make: Kirloskar , Crompton, Mahindra NOTES: [i] Necessary civil work viz. foundation for placement of pump and accessories shall be covered in the scope of work.
INDUCED DRAUGHT COUNTERFLOW TYPE FRP COOLING TOWER - 1 No Supply, installation, testing and commissioning of rectangular shape, vertical, induced draught counterflow type FRP cooling tower of 134 TR size with uniform water distribution and optimal heat transfer, having tough fiberglass reinforced plastic (FRP) casing of sufficient structural strength to withstand vibrations and wind velocity up to 60 m/s, FRP basin, rigid honeycomb type PVC fill of suitable thickness, SS sprinklers and non-clogging sprinkler pipes, FRP drift eliminator, energy efficient induced draught axial type fans with factory set and dynamically balanced blades pitch, IE3 TEFC squirrel cage induction motor, suitable for operation on 3- Ph, 415 V, 50 Hz AC supply with IP 65 protection for enclosure, conforming to IS 12615: 2018, inlet, outlet, drain and over-flow nozzle connections, etc. complete with accessories along with suitable foundation as per manufacturer's recommendations as specified and directed by the engineer-in-charge. Entering Water Temp. - 99.5° F Leaving Water Temp. - 90° F Flow Rate per Cell - 440 GPM Make: Advance, Delta, Artech, Paharpur NOTES: [i] Necessary civil work viz. foundation, supporting structure, etc. for placement of cooling tower shall be deemed included in the scope of work.
CONDENSER WATER PUMP - 3 Nos (2W + 1S) Supply, installation, testing and commissioning of Monoblock, self-priming, single-stage centrifugal pump, capable of 440 USGPM discharge at 15 MWC head, having cast iron casing, enclosed type dynamically balanced cast iron impeller, carbon steel pump shaft, gland packed sealing, deep groove ball bearings, etc. with TEFC squirrel cage induction motor having class 'B' insulation, IE3 efficiency, conforming to IS 12615: 2018 and suitable for operation on 3-Ph, 415 V±10%, 50 Hz AC supply, base plate, mounting channel frame, accessories and fittings, viz. pressure gauges, thermometers, drains, coupling, coupling guard, vibration isolation arrangement by means of spring / rubber type mounting complete all as specified and directed by the engineer-in-charge. Make: Kirloskar , Crompton, Mahindra NOTES: [i] Necessary civil work viz. foundation for placement of pump and accessories shall be covered in the scope of work.
STAINLESS STEEL EXPANSION TANK S & F SS- 304 closed expansion tank with pressure rating to suit the system pressure and sized adequately to compensate for water expansion due to operating temperature variations, conforming to IS: 2825- 1969 for 'non-fired pressure vessels' complete with inter-connection piping, non-return valve, safety relief valve and pressure gauge, insulated with 50 mm thick elastomeric insulation and cladded with 26 gauge aluminium complete with accessories as specified and directed by the engineer-in-charge. 300 litre (for chilled water circuit)
HDPE MAKE-UP WATER TANK S & F multi-layered HDPE make-up water tank of total 20000 litre (in configuration of 2 x 10000 litres) capacity made up of 100% virgin material, having 100% UV stabilized white outer layer, threaded lid, extra insert lid for protection against algae formation complete with inter-connection piping and non-return valve etc. complete all as specified and directed by the engineer-in-charge. NOTE. Staging platform of suitable height for the make up water tank , made with structurally sound masonry and concrete work is deemed to be included in the scope of work for this item.
M & L for 1.1 kV grade copper conductor, XLPE insulated armoured cable conforming to IS 7098 (Part 1): 1988, having stranded copper compact shaped conductors as per Cl. 2 of IS 8130: 1984, PVC inner sheath, single armouring of galvanised steel strip/wire and PVC Type ST-2 outer sheath conforming to IS 5831: 1984, including necessary laying on and including cable trays & conduits as required and clamping / dressing with cable ties and termination complete all as specified and directed by engineer-in-charge. Make: RR Kabel, Polycab, Havells
(a) 3.5 core, 35 mm² [for chillers]
(b) 3 core, 6 mm² [for cooling tower]
(c) 3 core, 4 mm² [for pump starter to motor terminals]
CONDENSER WATER PIPING MS ERW CLASS- C PIPE Supply, laying / fixing, testing and commissioning of condenser water piping including necessary fittings viz. bends, tees, reducers, flanges, air purge valves, drain valves, structural support, necessary clamps, vibration isolators, etc. including painting and supporting / fixing the pipe in excavated trenches or on floor / wall / ceiling with clamps, hangers, angles, channels (using anchor fasteners) with necessary accessories complete all as specified and directed by the engineer-in-charge. Make: Tata, Jindal, Surya
(a) 200 mm NB
(b)125 mm NB
(c) 40 mm NB NOTES: Quantities as required as per approved design and drgs [i] The pipe size 150 mm NB & below shall be MS 'C' class as per IS 1239 (Part- 1): 2004 & IS 1239 (Part- 2): 2011. [ii] The pipe size above 150 mm NB shall be welded black steel pipe heavy class as per IS 3589: 2001. [iii] Minimum thickness of MS sheet for pipe size above 150 mm NB and up to 350 mm NB shall be 6.35 mm and it shall be 7 mm for pipe size 400 mm NB and above.
Y- STRAINER- Condensor Supply, installation, testing and commissioning of 125 mm NB cast steel bolted cover Y-type strainer with CCS body conforming to ASTM A- 216 Gr. WCB, AISI 304 screen with 1.2 mm diameter perforation, 40 kg/cm2 body test pressure & 20 kg/cm2 maximum working pressure and standard flange end conforming to BS 10 Table F / Class-150 with necessary accessories complete all as specified and directed by the engineer-in-charge Make: Advance, Sant, Hindustan
BUTTERFLY VALVE - Condensor Supply, installation, testing and commissioning of wafer type PN 1.6 rated short pattern CI butterfly valve having Gr. FG-200 CI body conforming to IS 210: 2009, seat having EPDM rubber lining, CF 8 stainless steel disc, AISI- 410 stainless steel stem, 2.4 MPa body test pressure & 1.6 MPa seat test pressure and standard flange end conforming to BS 10 Table D/E & ANSI B 16.1 CI- 125 with necessary accessories complete all as specified and directed by the engineer-in-charge.- quantities as required Make: Advance, Sant, Hindustan
(a)125 mm NB
(b) 200 mm NB
(c) 40 mm NB
NON-RETURN VALVE - Condensor Supply, installation, testing and commissioning of 125 mm NB wafer type PN 1.6 rated swing check type multidoor reflux valve (NRV), designed & tested as per IS 5312 (Part- 2): 1986, suitable to handle clear water having turbidity up to 5000 PPM, having CI body, door and diaphram, leaded tin bronze seat rings and flange drilling standard end connection, etc. with other necessary accessories complete all as specified and directed by the engineer-in-charge Make: Advance, Sant, Hindustan
MANUAL BALANCING VALVE - Condensor Supply, installation, testing and commissioning of 125mm NB precise balancing, double regulation type cast iron balancing valve having FG 200 cast iron body conforming to IS 210: 2009, copper alloy trim, stainless steel 2 Cr. 13 stem, 2.4 MPa body test pressure & 1.6 MPa maximum working pressure and standard flange ends with necessary accessories complete all as specified and directed by the engineer-in-charge. Make: Advance, Sant, Hindustan
CHILLED WATER PIPING Supply, laying / fixing, testing and commissioning of chilled water circulation piping including necessary fittings viz. bends, tees, reducers, flanges, air purge valves, drain valves, structural support, necessary clamps, vibration isolators, etc. including painting and supporting / fixing the pipe in excavated trenches or on floor / wall / ceiling with clamps, hangers, angles, channels (using anchor fasteners) with necessary accessories duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and directed by engineer-in-charge. Quantities as required as per bldg drgs and as appd Make: Tata, Jindal, Surya for pipes & Armacell, K-Flex, Aeroflex for insulation
(a) 150 mm NB with 38 mm thick insulation
(b)100mm NB with 38 mm thick insulation
(c) 80 mm NB with 38 mm thick insulation
(d) 20 mm NB with 32 mm thick insulation NOTES: [i] The pipe size 150 mm NB & below shall be MS 'C' class as per IS 1239 (Part- 1): 2004 & IS 1239 (Part- 2): 2011. [ii] The pipe size above 150 mm NB shall be welded black steel pipe heavy class as per IS 3589: 2001. [iii] Minimum thickness of MS sheet for pipe size above 150 mm NB and up to 350 mm NB shall be 6.35 mm and it shall be 7 mm for pipe size 400 mm NB and above. [iv] Insulation: For pipes buried in ground or laid over ground exposed to atmosphere, the minimum thickness of insulation as above and HDPE jacketing of 3mm (upto 125 mmdia pipe) and 4.2mm (above 125 mm dia pipe) shall be provided
Y- STRAINER - Chilled Water Supply, installation, testing and commissioning of cast steel bolted cover Y-type strainer, 100mm NB with CCS body conforming to ASTM A- 216 Gr. WCB, AISI 304 screen with 1.2 mm diameter perforation, 40 kg/cm2 body test pressure & 20 kg/cm2 maximum working pressure and standard flange end conforming to BS 10 Table F / Class-150 duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and directed by the engineer-in-charge. Make: Advance, Sant, Hindustan for strainer & Armacell, K-Flex, Aeroflex for insulation
BUTTERFLY VALVE -Chilled Water Supply, installation, testing and commissioning of wafer type PN 1.6 rated short pattern CI butterfly valve having Gr. FG-200 CI body conforming to IS 210: 2009, seat having EPDM rubber lining, CF 8 stainless steel disc, AISI- 410 stainless steel stem, 2.4 MPa body test pressure & 1.6 MPa seat test pressure and standard flange end conforming to BS 10 Table D/E & ANSI B 16.1 CI- 125 duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and directed by the engineer-in-charge. Make: Advance, Sant, Hindustan for Butterfly valve & Armacell, K-Flex, Aeroflex for insulation
(a) 150 mm NB
(b) 100 mm NB
(c) 125 mm NB
(d) 80 mm NB
NON-RETURN VALVE -Chilled Water Supply, installation, testing and commissioning of 100 mm NB wafer type PN 1.6 rated swing check type multidoor reflux valve (NRV), designed & tested as per IS 5312 (Part- 2): 1986, suitable to handle clear water having turbidity up to 5000 PPM, having CI body, door and diaphram, leaded tin bronze seat rings and flange drilling standard end connection, etc. duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and directed by engineer-in-charge. Make: Advance, Sant, Hindustan for Reflux valve (NRV) & Armacell, K-Flex, Aeroflex for insulation
3-WAY TEMPERATURE CONTROL VALVE Supply, installation, testing and commissioning of electronic, self-balancing, pressure independent type dynamic balancing valve rated for minimum 25 bar working pressure with integrated 3-way modulating control valves in a single body and actuator capable of accepting up to 10 V DC and up to 20 mA electric signal and provide similar transduced feedback output to control system duly wired and conneceted with suitable cable upto theThermostat and duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and directed by the engineer-in-charge. Make: Honeywell, Danfoss, Advance for 3-Way Modulating Control valve & Armacell, K-Flex, Aeroflex for insulation
(a) 125 mm NB
(b) 80 mm NB NOTES: [i] Maximum close off pressure shall not be less than 6 bar for up to 50 mm valves. [ii] Maximum close off pressure shall not be less than 7 bar for 65 mm & above.
MANUAL BALANCING VALVE -Chilled Water Supply, installation, testing and commissioning of precise balancing, double regulation type cast iron balancing valve 100mm NB, having FG 200 cast iron body conforming to IS 210: 2009, copper alloy trim, stainless steel 2 Cr. 13 stem, 2.4 MPa body test pressure & 1.6 MPa maximum working pressure and standard flange ends duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and directed by engineer-in-charge. Make: Advance, Sant, Hindustan for Balancing valve & Armacell, K-Flex, Aeroflex for insulation
BALL VALVE S & F of SS 304 ball valve, having two piece design, SS 304 body & ball, PTFE seal/packing/gasket and screwed/socket weld end connection, etc. with accessories, etc. duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and directed by engineer-in-charge.
(a) 40 mm NB
(b) 32 mm NB
(c) 25 mm NB
(d) 20 mm Make: Advance, Sant, Hindustan for Ball valve & Armacell, K-Flex, Aeroflex for insulation
DRAIN & INSTRUMENTATION PIPING MS ERW CLASS- C PIPE Supply, laying / fixing, testing and commissioning of MS ERW Class- C drain piping including necessary fittings viz. bends, tees, reducers, flanges, air purge valves, drain valves, structural support, necessary clamps, vibration isolators, etc. including painting and supporting / fixing the pipe in excavated trenches or on floor / wall / ceiling with clamps, hangers, angles, channels (using anchor fasteners) with necessary accessories complete all as specified and directed by the engineer-in-charge. - Qty as reqd Make: Tata, Jindal, Surya
(a) 25 mm NB
(b) 20 mm NB
BALL VALVE S & F of SS 304 ball valve, having two piece design, SS 304 body & ball, PTFE seal/packing/gasket and screwed/socket weld end connection, etc. with accessories, etc. duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and directed by engineer-in-charge.
(a) 40 mm NB
(b) 25 mm NB
(c) 15 mm NB
AUTO AIR-VENT Supply, installation, testing and commissioning of automatic air-vent valve with 20 mm end connections, brass OT 58 body and cover, polyacetal lever, high density expanded polyethylene float, EPDM rubber plug, stainless steel spring, polyamide cap etc. suitable for maximum operating pressure of 16 bar and maximum operating temperature 115 °C respectively, installed on all high points in the water piping system to automatically remove the trapped air complete all as specified and directed by the engineer-in-charge Make: Advance, Sant, Hindustan
TEMPERATURE GAUGE S & F of 4" dual scale (°F/°C), lower mount (radial), bimetal thermometer having 0.5 NPT process connection, Grade A accuracy class as per ASME B40.200, stem diameter 6.35 mm, laminated safety glass window, stainless steel 304 case, steam, process connection & joint, aluminium dial & pointer, IP67 protection, scale range 0- 60 °C complete with accessories, etc. as specified and directed by the engineer-in-charge.
PRESSURE GAUGE S & F of 4" bourdon tube pressure gauge conforming to EN 837-1, having copper alloy process connection & pressure element, plastic black pointer & case, plastic crystal-clear window, snap-fitted in case, accuracy class 2.5, scale range 0- 25 bar complete with accessories, etc. as specified and directed by the engineer-in-charge. Make: General, WIKA, TSI
PROGRAMMABLE DIGITAL THERMOSTAT SITC programmable digital room thermostat for commercial HVAC application connected with and including temperature sensor fitted with return air in the AHU duly installed & wired with the Motorised balancing valves for independently prgaramming and controlling the chilled water flow/bypass Make - Johnson Control /Honeywell /Seimens
DOUBLE SKIN AIR HANDLING UNIT Supply, installation, testing and commissioning of double-skin type horizontal, floor-mounted, top / side discharge air handling unit capable of delivering required air at 3" W.G. static pressure and having thermal break profile complete with air-tight casing using gaskets and self-adhesive tapes and 0.8 mm thick pre-coated outer skin and 0.6 mm thick GI inner skin, 45±2 mm thick double skin panel with pressure injected CFC & HCFC free PUF having 'k' value of 0.02 W/°C/m & density 40 kg/m³, AMCA certified energy efficient plug fans with backward curved impellers for high static pressure mounted on aluminium extruded siderail base frame with VFD, EU4 pre-filter and EU7 fine filter (shall be mounted on a common frame), combination of 6/8 rows deep chilled water coils with anti-corrosion aluminium fins, suitable high efficiency (IE3) TEFC flameproof squirrel cage induction motor, electric step heater, PVC/nylon hinges & handles, view port and marine lamp, limit switch, SS-304 drain pan, vibration isolators/rubber pads (minimum 1" thick) inspection windows / doors, mixing box and supply / return / fresh air openings fitted with aluminium volume control dampers complete all as specified and directed by the engineer-in-charge - 2 Nos Make: Trane, Carrier, Daikin, Flak group/McQuay
(a) 75 TR/30000 CFM
(b) 36.5 TR/15000 CFM
The AHU shall comprise of the following: [a] Suitable SISW backward curved plug fan, dynamically balanced, with AMCA certified blower [b] Flameproof foot mounted (B3 construction) 3-Phase squirrel cage induction motor 415 V ± 10%, 50 Hz ± 5 %, combined variation ±10%, insulation class F, (for Blower of AHU) of 15 kW capacity, 35000 CFM with temperature rise limited to class B, degree of protection IP 55, duty 51, ambient temperature 45 ºC, conforming to IS 12615: 2011, IS/IEC 60079-1: 2007, IS 3682: 1966 gas group II A, II B [c] Flexible connection made with airtight ASTM E84 (Class I) polyester fire retardant cloth riveted on periphery of cloth with extruded aluminium 'L' angle flange as per fan size at discharge duct/plenum [d] Washable type of 'EU4' filter (pre-filter, efficiency 90% down to 10 micron) and 'EU7' filters (Micro Vee filters, efficiency 99% down to 3 micron) [e] 6 / 8 rows deep chilled water cooling coil section with 0.15 mm thick aluminium fins and 0.36 mm diameter copper tubes tested on 21 kg/cm², with SS sandwiched drain tray, etc. (a 350 mm service section between eliminator and heater is required) [f] Condensate drain pan fabricated from 18 gauge SS 304, powder coated and insulated with elastomeric insulation of suitable thickness [g] 2 row deep heating coil section with aluminium fins and copper tube tested on 21 kg/cm² with SS sandwiched drain tray, etc. [h] AHU panel made out of 2.00 mm thick mild steel CRCA sheet, duly powder coated in compartmentalised construction with incomer and outgoing feeders for AHU motor, 3-way valve actuator motor, fire damper actuator motor, etc. complete with required variable frequency drive (VFD), relays, timers, contactors, PT, push buttons, switches, internal wiring, etc.
FIRE DAMPER Supply, installation, testing and commissioning of 16 gauge GI fire damper, at least of 120 minutes fire-rating, spring activated on melting of fusible link having melting point 67.13° C complete with smoke detector / thermistor, fusible link etc. and actuator as required for operation, located in the SA / RA ducts, at all fire rated crossovers (shafts, walls, etc.). along with control panel (located in such a way that the reset can easily be done), interlocked with the building management system for the fire detection or HVAC to trip / close in the event of fire/smoke in the respective zone and tested as per ULL- 555 and certified by CBRI complete all as specified and directed by engineer-in-charge. Make: Ruskin Titus, Trox, Rola Star, Zeco The fire dampers shall meet the following criteria: [a] Bare fire dampers with 400 mm sleeve [b] Control panel actuator, including electrical spring type actuator, remote indication of the fire damper position. [c] Interconnection wire for the fire detection & alarm system with the AHU and the smoke dampers [d] Sealing any openings around the sleeve of the fire dampers with approved fire sealant as per the specification & recommendations of the manufacturer. Motorized, spring return type, combination fire and smoke damper Control panel actuator, including electrical spring type actuator, remote indication of the fire damper position. - Qty as reqd
GALVANIZED STEEL SHEET (GSS) DUCTING Supply, installation, balancing and commissioning of factory fabricated galvanized steel sheet metal (G.S.S.) round / rectangular ducting of following sheet thickness having zinc coating of 120 g/m² total on both sides and complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, volume control dampers, hangers, supports, etc. as per approved drawings and conforming to the latest edition of IS 655: 2006 & HVAC Duct Construction Standards - Metal and Flexible of SMACNA along with required scaffolding work to install the ducts at site complete all as specified and directed by engineer-in-charge.- Qty as reqd as per appd design. The duct layout with sizes is given with tender drgs. Make: Ruskin Titus, Trox, Rola Star
(a) 26 G (MS angle flanges)
(b) 24 G (MS angle flanges)
(c) 22 G (MS angle flanges)
AIR TERMINALS S & F of supply / return / exhaust air diffusers / grilles / louvers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core complete all as specified and directed by the engineer-in-charge. - Qty and size as per design and drawings. Make: Ruskin Titus, Zeco, Rola Star
S & F of FM approved black flexible closed-cell elastomeric thermal insulation made of elastomeric foam based on synthetic rubber (NBR / PVC) with self pre-covered self-adhering, UV treated glass cloth of thickness 7 mm / 200 GSM, tested for maximum service temperature 100 ºC as per ASTM C411 & minimum service temperature -50 ºC as per ASTM C534, thermal conductivity λ ≤ 0.037 W/mK at mean temperature θm = 24 ºC as per ASTM C518 / C177, ASTM C335, water absorption by volume ≤ 0.2% as per ASTM C1763, fire spread index (FSI) & smoke development index (SDI) 25/50 as per ASTM E84, flammability HB, V-0 as per UL 94, fungi resistance as per ASTM G21, mould growth resistance as per ASTM E2180-18 / UL 181 and ozone resistance as per ASTM D 1149-18 along with adhesives and other necessary accessories complete all as specified and directed by the engineer-in-charge. Make: Armacell, K-Flex, Aeroflex
13 mm thick thermal insulation
19 mm thick thermal insulation Notes: 1. Spaces on Ground floor and will have 13 mm thickness of insulation. 2. All ducts on first top floor shall be insulated with 19 mm thickness of insulation 3. Ducts passing through non AC area shall have minimum 19 mm thickness of insulation 4. All entry and exit of ducts inthe room and across walls shall be neatly sealed and finished to ensure clean look and protection against moths and rodents. 5. The area of the insulation shall be measured for the external surface area of the duct over which the insulation is running.
S & F of FM approved fibre-free, super-silent, microbe resistant, easy to apply 25 mm thick acoustic duct lining insulation of resin bonded mineral/glass wool tested for acoustic performance as per EN ISO 354, EN ISO 11654: 1997 & ASTM C 423, service temperature range -20- 85 ˚C as per EN 14706 & EN 14304, thermal conductivity λ ≤ 0.047 W/mK at mean temperature θm = 20 ˚C as per EN 12667, Class 1 surface spread of flame as per BS 476 7: 1997, flammability HB, V-0 as per UL- 94, anti-microbial behaviour (no fungal growth visible with the naked eye & no bacterial growth) as per EN ISO 846, air erosion resistance (no erosion, cracking or delamination at air velocity of 10000 FPM) as per ASTM C 1071- 05, density 140- 180 kg/m3 along with adhesives and other necessary accessories complete all as specified and directed by engineer-in-charge.- Qty as reqd Make: Armacell, K-Flex, Aeroflex
POT Strainer Supplying, installation, testing and commissioning of Pot strainer for chiled water lines 150mm dia. Pot Strainers body shall be fabricated out of MS plate IS 226. Thickness of sheet shall be as per size of the strainer chamfered pipes with flanges shall be provided at inlet /outlet connections of the strainer. A powerful magnet shall be provided in the body to arrest MS particles. Filter element of Pot Strainer shall be of non magnetic 18 gauge SS sheet properly reinforced to avoid damage of the element. A set of MS flanges with tongue and groove arrangement and neoprene rubber gasket shall be provided on the top cover and Pot Strainer flange with sufficient bolts and nuts to make the joint water light. The Pot strainer body shall be properly de-rusted and epoxy coated from inside and outside.
Air Separator Supply, installation, testing and commissioning of a ASME stamped combined Air and Dirt Separator of M.S construction as per specifications on the chilled water line located at the pump suction or at a suitable location as suggested. The air separator should be complete with high capacity air vent, service valve, butterfly valve, water inlet, flanges, drain valve ,duly weather protection paint on stand and air separator body etc. of below sizes
AIR CONDITIONING ( SPLIT AC )
Supply, installation, testing & commissioning Split Air Conditioner 2 Ton, 5 star rating, inverter type technology, 230 V, 50 Hz, refrigerant -R32, single phase, indoor/ outdoor unit complete with cordless remote control unit and compressor- inverter rotary type, condenser-100% Copper type, noise level outdoor-60 dB and high cooling performance and desirable cooling mode for different types of climate. Make- Blue star/Voltas/LG
Supply and fixing of voltage stabilizer for automatic operation single phase naturally air cooled indoor type and designed for input variation between 170volt to 250volt with output voltage stabilised at 230Volt with accuracy of ± 2.5% and of capacity of 5.0 KVA.
Supply, installation, testing & commissioning Split Air Conditioner 1.5 Ton, 5 star rating, inverter type technology, 230 V, 50 Hz, refrigerant -R32, single phase, indoor/ outdoor unit complete with cordless remote control unit and compressor- inverter rotary type, condenser-100% Copper type, noise level outdoor-60 dB and high cooling performance and desirable cooling mode for different types of climate. Make- Blue star/Voltas/LG
Supply and fixing of voltage stabilizer for automatic operation single phase naturally air cooled indoor type and designed for input variation between 170volt to 250volt with output voltage stabilised at 230Volt with accuracy of ± 2.5% and of capacity of 4.0 KVA.
Supply & fix MCCB 4 pole 125 amp, breaking Capacity Icu at 415V AC 50Hz -18 KA complete all as specified and directed.
Chemical Earthing complete with copper earth plate electrode 900mm x600 mm x 5 mm buried directly in ground vertically to a depth not less then 2.25 meter below normal ground level with top edge of the plate not less then 1.50 meter below normal ground level connected to copper earth strip 32x6 mm by means of bolts, nuts, check nuts and washers complete up to and including test point made out of 40 x 6mm alum flat including earthing pit, charcoal-250 kg ,common salt- 250kg, magnesium sulphate-100kg, earth strip 32x6 mm up to 7.5m through 40 mm GI pipe, 20mm dia medium grade GI watering pipe , PPC pit in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate ,PCC pit cover including earth work complete all as shown in electrical plate No-5 of SSR-2014 (part-I). (For Split AC - 04 Nos, DG set -10 Nos, Cable network for specialized items 12, Ext EE 22, Anti Static Flooring-28 , Esd Discharge plate -4)
EXTERNAL ELECTRIFICATION
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure
Supply, install, testing and commissioning of Distribution transformer ( Level 3) mounted on masonry platform stepdown, 11KV/0.433KV, Three Phase complying with IS: 1180/IEC-76(Part-1) 2014 with latest amendments, indoor type double copper wound suitable for 50 Hz system of capacity 1000 KVA, oil immersed naturally cooled delta connected on HT side and Star connected on LT side, Vector Group Dyn11, provided with OFF load tap changer to vary secondary voltage from -7.5% to + 7.5 % in step of 2.5 %. Losses should be confined to the limits specified as follows: maximum allowable losses at full load (100 % ) & Half Load ( 50 % )shall not be exceeded 0.98 % & 0.70 % Respectively as per GRlHA RATING, Percentage Impedance: 5%. Losses and Impedance are subjected to tolerance as specified in IS 1180. The transformers should be supplied with first filling of oil confirming to IS 335 .The transformer should have both side cable end box with neutral brought out complete all as directed by Engineer - in -Charge, and installation of transformer shall be carried out as per IS-10028 and comprising with the following standard fittings/Technical specifications : -(For DRF ), Make of transformer - Voltamps/Schneider/ Siemens/Pactil/ITL/Kirloskar
(a) Lifting lug for transformer and tank. (b) Earthing terminal rating and diagram plate. (c ) Air release device. (d) Oil filling inlet pipe with plug. (e) Drain outlet pipe with brass gate valve. (f) Conservator tank with oil level indicator (g) Silica jel breather
(h) First fill of oil upto level including conservator tank with fresh new oil conforming to IS335. (j) Type of connection Delta/Star (k) Type of cooling: Oil and Natural Air. (l) Vector group:DYN 11. (m) Temperature rise over an ambient of 50 °C maximum. (n) Cable end box on both side for HT/LT cables of suitable size. (o) Provision of thermometer with pocket. (p) Provision of oil and winding temperature gauge. (q) Buchhoz Relay
Supply, install, testing and commissioning of Distribution transformer ( Level 3) mounted on masonry platform stepdown, 11KV/0.433KV, Three Phase complying with IS: 1180/IEC-76(Part-1) 2014 with latest amendments, indoor type double copper wound suitable for 50 Hz system of capacity 750 KVA, oil immersed naturally cooled delta connected on HT side and Star connected on LT side ,Vector Group Dyn11, provided with OFF load tap changer to vary secondary voltage from -7.5% to + 7.5 % in step of 2.5 %. Losses should be confined to the limits specified as follows: :maximum allowable losses at full load (100 % ) & Half Load ( 50 % )shall not be exceeded 0.98 % & 0.70 %, Percentage Impedance: 5%. Losses and Impedance are subjected to tolerance as specified in IS 1180. The transformers should be supplied with first filling of oil confirming to IS 335 .The transformer should have both side cable end box with neutral brought out complete all as directed by Engineer - in -Charge, and installation of transformer shall be carried out as per IS-10028 and comprising with the following standard fittings/Technical specifications : -( Ejection seat complex) Make- Voltamps/Schneider/ Siemens/Pactil/ITL/Kirloskar
(a) Lifting lug for transformer and tank. (b) Earthing terminal rating and diagram plate. (c ) Air release device. (d) Oil filling inlet pipe with plug. (e) Drain outlet pipe with brass gate valve. (f) Conservator tank with oil level indicator (g) Silica jel breather
(h) First fill of oil upto level including conservator tank with fresh new oil conforming to IS335. (i) Type of connection Delta/Star (j) Type of cooling: Oil and Natural Air. (k) Vector group:DYN 11. (l) Temperature rise over an ambient of 50 °C maximum. (m) Cable end box on both side for HT/LT cables of suitable size. (n) Provision of thermometer with pocket. (o) Provision of oil and winding temperature gauge. (q) Buchhloz relay
Supply, install, testing and commissioning SF6 insulated compact Outdoor type R.M.U. rated voltage 11 KV,rated current 630 A, short circuit breaking current 16 KA and making capacity 40 KA ,fully arc proof metal enclosed, free standing, floor mounting, flush fronted type consists of manually operated non draw out type SF6 module-1 Nos load break switches (Incomers) and 2 No. Vacuum circuit breaker (outgoing) with integrated relays and related CTs as specified below, cable switch module and an interlocking mechanism with the earthing switch all as specified and directed. Degree of protection shall be per manufacturer specifications. Make of LT panel board - L&T / ABB / Schneider/Siemens or by their authorized channel partners duly authenticated by the company
(a) Fixed type voltage indicators and electronic short circuit indicators for simple fault indication b) Resin cast CT with ratio 75/1-1 with 15VA burden class1 for metering and class 5 P10 for protection-Set of three c) Resin cast potential transformers with ratio 11KV/1.732, 110V/1.732, 200 VA class1 with HT fuses mounted on with drawable rack d)Self powered microprocessor controlled numeric relay comprising of three over current , one earth fault protection relay with high set for both phase & earth and with fault memory, universal auxiliary supply Model No.IRI1- WD of C&S make / Model No MC-61A of L&T make e) Trip circuit supervision relay Model No. MRA1 of C&S make or equivalent in L&T f) Master trip relay Model No. CLR of C&S make or equivalent in L&T
n) Copper bus bar common for outgoing feeders o) Manual charging/ operating arrangement p) Fuses for metering and protection system q) Push buttons for accepting faults and reset r) Rear bottom entry of HT cables s) LED indicating lamps i) Auto trip ii)Spring charge iii)Fault alarm iv)Trip circuit healthy v)Trip circuit unhealthy vi)Breaker ON vii) Breaker OFF t) Complete control panel wiring with copper wire of size not less than 1.5 sqmm u) Civil works required for foundation as per manual of manufacturer
Supply, Installation, test and Commissioning, factory fabricated LT panel board, type tested by CPRI /Authorised Govt. Agencies , confirming to IEC 60349-1 & 2,up to 400 Amps incomer OR confirming to IEC 61349-1 & 2, above 400 Amps incomer, LT panel board made out of 2 mm thick GI Sheet multifold design, chemically treated surface with multi tank process powder coating, indoor modular type, dust free ,Vermin Proof , totally enclosed with Confirming to IP 43 for indoor panel & Confirming to IP 54 for outdoor panel ,single door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Galvanised iron Angle Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Testing after Installation including complete all as specified and comprising of the following :– Make of panel board - L&T / ABB / Schneider/Siemens or by their authorised channel partners duly authenticated by the company.(For Main Panel DRF Building)
Supply, Installation, test and Commissioning, factory fabricated LT panel board, type tested by CPRI /Authorised Govt. Agencies , confirming to IEC 60349-1 & 2,up to 400 Amps incomer OR confirming to IEC 61349-1 & 2, above 400 Amps incomer, LT panel board made out of 2 mm thick GI Sheet multifold design, chemically treated surface with multi tank process powder coating, indoor modular type, dust free ,Vermin Proof , totally enclosed with Confirming to IP 43 for indoor panel & Confirming to IP 54 for outdoor panel ,single door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Galvanised iron Angle Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Testing after Installation including complete all as specified and comprising of the following :– Make of panel board - L&T / ABB / Schneider/Siemens or by their authorised channel partners duly authenticated by the company. (For Main Panel Ejection seat complex)
Electric rubber hand gloves 11 KV
Supply, installation, commissioning and testing the following Vacuum Circuit breaker 11 KV, 3 phase 50 cycle ( 50 HZ) totally enclosed metal clad switch gear panel factory made, powder coated board with indoor vacuum circuit breaker floor mounted composite panel with common copper tinned bus bar complete, dust and vermin proof free standing consisting total 3 nos 11 KVA VCB panels as per following description & including 1 no Inbuilt Power pack 30 v dc to be provided with panel at least for 30 minute Back Up. - (1 incomer+02 Nos as outgoing = 03 Nos VCBs ( Location DRF Sub station ) (A) INCOMING VCB PANEL EACH CONSISTING OF THE FOLLOWING EQUIPMENT :-(Main DRF building) (a) One No 630 Amps capacity triple pole metal clad HT control panel totally enclosed extendable pattern air insulated metal clad housing, floor mounting vertically isolated, vermin proof, fully interlocked horizontal draw out type having double isolation features & control device with grounded neutral system and equipped with the following equipment. (i) One set of 3 phase 800 Amps air insulated, tinned copper bus bar with insulated colour coating. (ii) One set of side frame for housing for circuit breaker carriage. (iii) 6 Nos 630 amps isolators plugs. (iv) One set of mechanical interlock and automatic shutter system, (v) One 630 Amps triple pole 350 MVA rupturing capacity VCB with automatic drop out and manually charged and motor operated spring closed mechanism complete with auxiliary switches, truck mounted draw out, vacuumed circuit breaker, incorporating mechanical as well as electrical ON/OFF indication, mechanical indication "ON" push button for emergency trip & 30 Volts DC trip coil. (vi) One cable box suitable for reception for 120/185 sqmm HT XLPE 3 core under ground cable 11000 volts pressure.
(xiv) One No volt coil to trip the VCB on failure of electric supply. (xv) One set of mechanical interlock and automatic shutter gear. (xvi) 230 volts AC single phase 80 watt rated strip heater with switch and thermostat space heating. (xvii) Provision of 30 volts DC tripping system with suitable power pack including, siren/ horn alarm and accept switch and over voltage protecting relay. (xviii) Provision of motor charging with AC motor. (B) OUT GOING VCB PANEL 630 AMPS COMPRISING THE FOLLOWING :-(for outgoing - 2 nos ) (a) One No 630 Amps capacity triple pole metal clad HT control panel totally enclosed extendable pattern air insulated metal clad housing, floor mounting vertically isolated, vermin proof, fully interlocked horizontal draw out type having double isolation features & control device with grounded neutral system and equipped with the following equipment. (i) One set of 3 phase 630 amps air insulated tinned copper bus bar with colour coating. (ii) One set of side frame housing with circuit breaker carriage.
(iii) 06 Nos 630 amps isolating plugs. (iv) One set of mechanical interlock and automatic safety shutter gear. (v) One 630 Amp triple pole 350 MVA rupturing capacity VCB with automatic drop out and manually charged and motor operated spring closed mechanism complete with auxiliary switches, truck mounted draw out, vacuum circuit breaker, incorporating mechanical as well as electrical ON/OFF indication, mechanical indication "ON" push button for emergency trip & 30 Volts DC trip coil. (vi) One rear cable box for reception of one 120/185 sqmm HT XLPE 3 core cable 11 KV pressure. (vii) Three nos primary wound current transformer ratio 50/25/ 5-5 amps for the protection and metering having adequate VA burden and averaging. (viii) One set of 4 Nos LED lamps for indicates on/off/trip charging (ix) 144 mm square Type CT operated digital amp meter with 3 way rotary switch. (x) One No microprocessor relay 3 phase over current earth fault relay MC 61-CNX make : L&T (xi) Provision of DC 30 volts tripping system connected to common siren / horn alarm but with separated reception switch ( accept switch). (xii) Provn of motor charging with AC motor.
Supply, installation, commissioning and testing the following Vacuum Circuit breaker 11 KV, 3 phase 50 cycle ( 50 HZ) totally enclosed metal clad switch gear panel factory made, powder coated board with indoor vacuum circuit breaker floor mounted with common copper tinned bus bar complete all as specified
VCB PANEL EACH CONSISTING OF THE FOLLOWING EQUIPMENT :-(Ejection seat complex) (a) One No 630 Amps capacity triple pole metal clad HT control panel totally enclosed extendable pattern air insulated metal clad housing, floor mounting vertically isolated, vermin proof, fully interlocked horizontal draw out type having double isolation features & control device with grounded neutral system and equipped with the following equipment. (i) One set of 3 phase 630 Amps air insulated, tinned copper bus bar with insulated colour coating. (ii) One set of side frame for housing for circuit breaker carriage. (iii) 6 Nos 630 amps isolators plugs.
(iv) One set of mechanical interlock and automatic shutter system, (v) One 630 Amp triple pole 350 MVA rupturing capacity VCB with automatic drop out and manually charged and motor operated spring closed mechanism complete with auxiliary switches, truck mounted draw out, vacuum circuit breaker, incorporating mechanical as well as electrical ON/OFF indication, mechanical indication "ON" push button for emergency trip & 30 Volts DC trip coil. (vi) One cable box suitable for reception for 120/185 sqmm HT XLPE 3 core under ground cable 11000 volts pressure. (vii) 03 Nos double wound current transformer dual ratio 150/100/ 5-5 amps for protection and metering having adequate VA burden and accuracy. (viii) One set of 4 Nos LED lamp for indicate ON/OFF/Trip/charging. (ix) One 3 phase horizontal draw out type voltage transformer 100 VA burden and accuracy mounted on the draw able housing for 11000 volts/ 110 volts with protection fuse.
Supply, Installation, test and Commissioning, factory fabricated, as per IS/ IEC 61349-1 & 2, indoor type, APFC capacitor bank Panel Board of size as recommended by manufacturer 200 KVAR with 8 steps ( 50 + 25 + 25 + 25 +25+25+12.5+12.5) WITH MD-XL CAPACITOR AND MCCB AS INCOMER Automatic Power Factor Correction panel , made out of 2 mm thick CRCA Sheet Dust and Vermin Proof, single door with both side opening including Neoprene Rubber Gasket, conforming to IEC 61439 1 & 2and IEC 61641, suitable for 440 Volt 3 Phase 4 Wire System, The enclosure shall be pre-treated as per 11 tanks process and finished with powder coating of shade RAL 7032. , including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers etc. and embedded with 50X50X6mm Mild Steel Angle Iron Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20mm Graded Stone Aggregate) and Testing after Installation complete all as specified .The panel shall be factory fabricated comprising of following. A) INCOMER MCCB 630 A 35 KA,4 POLE ,thermal magnetic release, Ics=100% Icu & L&T cat no- CM94104OOT1OG /Legrand cat no-025540/Schneider cat no-LV540310- 1 no, (Thermal Magnetic Release) ROM+SPDR - 1 no, Auxiliary 1 c/o +TAC 1 c/o- 1 no B) OUTGOING CAPACITOR FEEDERS : - I) 50KVAr Capacitor feeder comprising of:- ( 1No. ) 160A, BUSSMANN FUSE type 160EET - 3 nos Thyristor switching module 50kVAR, 440V,TSM,LTTSM- 1 7% Detuned Aluminium Reactor 50KVAr 440V,LTAL,CAT NO-0750B2 -1 Ultra heavy duty capacitor LTXL , BOX type oil Filled Capacitor bank 30 kVAr,suitable for 480V ,LTXL - 2 nos Make of APFC panel board - L&T / ABB / Schneider/Siemens or by their authorised channel partners duly authenticated by the company.
Push Button ON/OFF -2 nos, Indicating lamps 2 nos Auxiliary Contactor {2NO+2NC} 24V DC Coil Voltage, MX-0 type -1 6A DP MCB ,C-CURVE-1 II) 25 KVAr Capacitor feeder comprising of:- ( 5 Nos. ) 80A, BUSSMANN FUSE 80ET,-15 nos Thyristor switching module 25kVAR, 440V , TSM,LTTSM-5 nos 7% Detuned Aluminium Reactor 25KVAr 440V Ultra heavy duty capacitor LTXL , BOX type oil Filled Capacitor bank 30 kVAr,sutable for 480V , LTXL - 5 NOS Push Button ON/OFF -10nos, Indicating lamps 10 NOS, Auxiliary Contactor {2NO+2NC} 24V DC Coil Voltage MXO- 5 6A DP MCB , C CURVE 5 NOS
III) 12.5 KVAr Capacitor feeder comprising of:- ( 2 Nos. ) 40A, BUSSMANN FUSE- 6 NOS Thyristor switching module 25kVAR, 440V,TSM,LTTSM - 2 NOS 7% Detuned Aluminium Reactor 12.5KVAr 440V LTAL,CAT NO-0712B2- 2 NOS Ultra heavy duty capacitor LTXL , BOX type oil Filled Capacitor bank 15 kVAr,sutable for 480V Push Button ON/OFF -4nos, Indicating lamps 4 NOS, Auxiliary Contactor {2NO+2NC} 24V DC Coil Voltage MXO- 2 6A DP MCB , C CURVE 2 Nos.
Supply, Installation, test and Commissioning, factory fabricated, as per IS/ IEC 61349-1 & 2 indoor type, APFC capacitor bank Panel Board of size as recommended by manufacturer 180 KVAR with 8 steps ( 50 + 25 + 25 + 25 +25+12.5 + 12.5 + 5) WITH MD-XL CAPACITOR AND MCCB AS INCOMER Automatic Power Factor Correction panel , made out of 2 mm thick CRCA Sheet Dust and Vermin Proof, single door with both side opening including Neoprene Rubber Gasket, conforming to IEC 61439 1 & 2and IEC 61641, suitable for 440 Volt 3 Phase 4 Wire System, The enclosure shall be pre-treated as per 11 tanks process and finished with powder coating of shade RAL 7032. , including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers etc. and embedded with 50X50X6mm Mild Steel Angle Iron Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20mm Graded Stone Aggregate) and Testing after Installation complete all as specified .The panel shall be factory fabricated comprising of following. INCOMER MCCB 630 A 35 KA,4 POLE ,thermal magnetic release, Ics=100% Icu & L&T cat no- CM94104OOT1OG /Legrand cat no-025540/Schneider cat no-LV540310- 1 no (Thermal Magnetic Release) ROM+SPDR - 1 no, Auxiliary 1 c/o +TAC 1 c/o- 1 no OUTGOING CAPACITOR FEEDERS : - I) 50KVAr Capacitor feeder comprising of:- ( 1No. ) 160A, BUSSMANN FUSE type 160EET - 3 nos Thyristor switching module 50kVAR, 440V,TSM,LTTSM- 1 7% Detuned Aluminium Reactor 50KVAr 440V,LTAL,CAT NO-0750B2 -1 Ultra heavy duty capacitor LTXL , BOX type oil Filled Capacitor bank 30 kVAr,sutable for 480V ,LTXL - 2 nos Make of APFC panel- L&T / ABB / Schneider/Siemens or by their authorised channel partners duly authenticated by the company.
Make of APFC panel board - L&T / ABB / Schneider/Siemens or by their authorised channel partners duly authenticated by the company. Push Button ON/OFF -2 nos, Indicating lamps 2 nos Auxiliary Contactor {2NO+2NC} 24V DC Coil Voltage, MX-0 type -1 6A DP MCB ,C-CURVE-1 II) 25 KVAr Capacitor feeder comprising of:- ( 4 Nos. ) 80A, BUSSMANN FUSE 80ET,-12 nos Thyristor switching module 25kVAR, 440V , TSM,LTTSM-4 nos, 7% Detuned Aluminium Reactor 25KVAr 440V-4nos Ultra heavy duty capacitor LTXL , BOX type oil Filled Capacitor bank 30 kVAr,sutable for 480V , LTXL - 4 NOS Push Button ON/OFF -8nos, Indicating lamps 8 NOS, Auxiliary Contactor {2NO+2NC} 24V DC Coil Voltage MXO- 4, 6A DP MCB , C CURVE -4 NOS
III) 12.5 KVAr Capacitor feeder comprising of:- ( 2 Nos. ) 40A, BUSSMANN FUSE- 6 NOS Thyristor switching module 25kVAR, 440V,TSM,LTTSM - 2 NOS 7% Detuned Aluminium Reactor 12.5KVAr 440V LTAL,CAT NO-0712B2- 2 NOS Ultra heavy duty capacitor LTXL , BOX type oil Filled Capacitor bank 15 kVAr,sutable for 480V Push Button ON/OFF -4nos, Indicating lamps 4 NOS, Auxiliary Contactor {2NO+2NC} 24V DC Coil Voltage MXO- 2 6A DP MCB , C CURVE 2 NOS at least for 30 minute Back Up. IV) 5 KVAr Capacitor feeder comprising of:- (1 Nos. ) 16A, BUSSMANN FUSE 3 nos Thyristor switching module 10kVAR, 440V,TSM,LTTSM -1 7% Detuned Aluminium Reactor 5 KVAr 440V,LTAL,CAT NO-0712B2-1 no Ultra heavy duty capacitor LTXL , BOX type oil Filled Capacitor bank 7.5 kVAr,sutable for 480V ,LTXL- 1nos Push Button ON/OFF -2nos, Indicating lamps 1NOS, Auxiliary Contactor {2NO+2NC} 24V DC Coil Voltage MXO- 1, 6A DP MCB , C CURVE 3 NOS,
Supply and fix LT bus duct air insulated type made out of 3mm thick CRCA sheet flanged type of suitable cross section with copper bus bars three phase and half neutral of 2000A capacity duly supported on DMC /FRP insulators including provision of suitable supports from ground for outdoor portion of bus duct with canopy &from roof for indoor portion of bus duct, painting the bus duct with two coats of synthetic enamelled paint over a coat of red oxide primer and connection with flexible laminated copper strips of same capacity at both transformer and LT panel complete all as directed and specified. Makes : L&T/Schneider/ABB
Supply and fix LT bus duct air insulated type made out of 3mm thick CRCA sheet flanged type of suitable cross section with copper bus bars three phase and half neutral of 1600A capacity duly supported on DMC /FRP insulators including provision of suitable supports from ground for outdoor portion of bus duct with canopy &from roof for indoor portion of bus duct, painting the bus duct with two coats of synthetic enamelled paint over a coat of red oxide primer and connection with flexible laminated copper strips of same capacity at both transformer and LT panel complete all as directed and specified. Makes : L&T/Schneider/ABB
Supply and Fix Drop out Fuse (Expulsion Fuse Single Pole) unit insulated with barrel suitable for HT 11 Kv out door installation mounted on steel frame rating upto 100Apms all as directed and as specified.
STAND BY POWER SUPPLY
Supplying, installing, testing and commissioning, factory assembled silent Diesel Engine driven generator set, fully wired alternator AC to give an out put of 750 KVA continuously rating at a power factor 0.8 lagging, 3 phase 4 wire, 415 volts 50 Hz supply, 1500RPM, directly coupled with diesel engine liquid cooled mounted on common base frame complete with floor mounting fuel tank (service tank) of adequate capacity with fuel line & accessories, PCC foundation work as per manufacturer's instructions, vibration damper pads, control panel & other accessories etc. and comprising of following. (a) Diesel Engine: Liquid cooled turbo charged with after cooler to deliver suitable BHP at 1500RPM under NTP conditions of BS 5514 and conforming to IS 10001/ 10002, DIN 6271 & ISO 3046 with an overload capacity of 10% for one hour in any 12 hours continuous operation with the following accessories:. Diesel engine of rated speed at full load electric start developing with system with radiator and including electronic governor control of class A1, engine control panel, lub oil pump, water pump, fuel tank, exhaust pipe with silencer and suitable for electric start with batteries of adequate capacity and suitable for alternator of specified capacity complete with fly wheel direct/ flexible coupling and coupling guard complete. Make of engine: KEOL / Kirloskar Electric / Ashok Leyland / Cummins / Greaves Make of Alternator: KOEL GREEN / Kirloskar /Stampford / Crompton / Jyoti
(a) Radiator with blower fan or heat exchanger with guard. (b) Pipe coupling for engine cooling system piping. (c ) Corrosion inhibitor coolant (d) Paper element filters (i) Fuel filter (ii) Lube oil filter (iii) By pass (e) Fly wheel housing and fly wheel to suit alternator. (f) Engine bearing mechanism in fly wheel housing.
(g) Shut off coil with safeties for LLOP/HWT/over speed. (h) Dry type air cleaners and vacuum indicators. (j) Residential silencers. (k) Stainless steel exhaust flexible bellows. (l) Motor driven priming pump. (m) Battery charging alternator.
(n) Exhaust piping made out of STIC C class, MS pipe inclusive of all accessories and hardware, necessary supports scaffolding as per manufacturer's recommendations to sustain back pressure with rain cap. (o) Mineral wool insulation 2 inch thick suitable for 400 degree Celsius temperature cladded with aluminium sheet o 30 gauge for the entire length of exhaust pipe. (p) First fill of oil, coolant and diesel during commissioning and 12 hours testing. (q) Interconnecting copper cabling of adequate capacity batteries control. (r ) Fuel pipe class STIC 1"" /1.5"" /2"" dia - 01 lot (s) Self starter 12 volts DC. (t) Electric operated electronic governor. (u) Fuel injection pump. (v) No of cylinders - 12 No VEE
(w) Electronic instrument panel, complete with all accessories as per manufacturer's specifications displaying the following:- (i) 24V Battery. (ii) Water temperature. (iii) lubricating oil pressure. (iv) Engine speed -1500Rpm (v) Engine hours (vi) Frequency. (vii) Voltage. (w) Safety control (Trip and indication). (i) High water temperature (ii) Low lube oil temperature (iii) Over speed stop (x) Base frame: Sturdy, fabricated welded construction, channel iron base frame (duly painted) for mounting engine and alternator as per manufacturer's design alonwith AVM pads.
(y) Battery:-12 volts(1x12v Battery) DC, 180AH, maintenance free battery conforming to IS:14257 with leads & terminals (Make- Exide/ Amaron). (z) Fuel tank: 10 hrs. full load diesel storage capacity fuel tank with mounting brackets factory made of 5mm thick HR/MS sheet with level indicator fuel inlet, fuel outlet, air vent, drain plug, in let arrangement for diesel filling fro exterior canopy (without opening its panel) etc. complete all as specified and directed. (aa) Isolator panel with 1250 amp MCCB (ab) Auto logic panel for automatic stat" (c) Acoustic Enclosure:- M & L for acoustic enclosure for the above 750 KVA DG set to reduce noise level to 75 dB measured at 1.0 meter distance for audible frequencies as per guide of Central Pollution Control Board and size 6800x2300x2713 mm and manufacturer's specification and comprising of following from authorised GOEMs of Gen Set manufacturer's specified :- (i) Sound insulation : 100mm thick Rock wool (Density 64 Kg/Cum). (ii) Outer body : 1.6mm thick CRCA (iii) Door : 1.6mm thick CRCA (iv) Base frame : ISMC 300 (v) Inside illumination : 1 No.- 1 x 18 watt FTL fitting of make Phillips/ Bajaj/ Crompton.
(d) AMF Control panel:- Factory fabricated cubicle type, free standing, floor mounted, indoor type, IP-52, AMF control panel, provided with removable rear panels & hinged front panel for easy accessibility, fabricated out of not less than 2.0mm thick CRCA sheet including two coats of powder coated paint over a coat of red oxide primer etc. and comprising of following: (e) AMF control circuit with 4 pole MCCB 1250Amps - 2 nos, with ultimate breaking capacity Icu-36 KA at 415 volts and microprocessor release conforming to IEC 60947 Part-I with breaking capacity Ics=Icu at 415 volts , thermal overload setting 70% to 100%, short circuit setting 5 to 10 times-02 Nos. for main supply & DG set supply with HRC back up fuse complete with all DC control relays/ Line voltage monitor (LVM) as per OEM specifications incorporating motorised stored energy operating Engine start, stop, three attempt starting facility and failure to start etc. (f) Digital load manager : Three phase 4 wire indicating V,I,PF, KVA, KW, F of Enercon make with serial communication port model No.EM6400 with class 1.0 accuracy meter or equivalent make suitable rating of CT per phase- one No. (i) Indication lamp R, Y, B with 3 Nos. of 2A HRC fuses-10 sets. (ii) Bottom gland plate for incoming and outgoing cables. (iii) Circuit diagram plate. Note :- (i)DG set should be suitable as per latest norm of National Clean Air programme (NACP) Act 1981. DG set should mandatorily include the emission control device to make it compliance with emission limits as brought out in the gsr issued by min of environment regarding emission limits of Nox , HC , CO, PM (ii) Make of MCCB - L&T / Schneider/ ABB/ Legrand
Supply, Installation, test and Commissioning, factory fabricated LT panel board, type tested by CPRI /Authorised Govt. Agencies , confirming to IEC 60349-1 & 2,up to 400 Amps incomer OR confirming to IEC 61349-1 & 2, above 400 Amps incomer, LT panel board made out of 2 mm thick GI Sheet multifold design, chemically treated surface with multi tank process powder coating, indoor modular type, dust free ,Vermin Proof , totally enclosed with Confirming to IP 43 for indoor panel & Confirming to IP 54 for outdoor panel ,single door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Galvanised iron Angle Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Testing after Installation including complete all as specified and comprising of the following :– Make of panel board - L&T / ABB / Schneider/Siemens or by their authorised channel partners duly authenticated by the company.(For DG Panel DRF bldg)
Supply, Installation, test and Commissioning, factory fabricated LT panel board, type tested by CPRI /Authorised Govt. Agencies , confirming to IEC 60349-1 & 2,up to 400 Amps incomer OR confirming to IEC 61349-1 & 2, above 400 Amps incomer, LT panel board made out of 2 mm thick GI Sheet multifold design, chemically treated surface with multi tank process powder coating, indoor modular type, dust free ,Vermin Proof , totally enclosed with Confirming to IP 43 for indoor panel & Confirming to IP 54 for outdoor panel ,single door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Galvanised iron Angle Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Testing after Installation including complete all as specified and comprising of the following :– Make of panel board - L&T / ABB / Schneider/Siemens or by their authorised channel partners duly authenticated by the company.(For DG Panel Ejection seat complex)
Supply and fix cable route indicator made of round CI disc embossed LT Cable, of size 16cm dia 6mm thick duly riveted with angle of size 50x50x4mm and 60cm long including PCC 1:2:4 B1 using 20mm aggregate 15cm x 15cm x 15cm for grouting the same complete all as specified.
Supply and fix cable route indicator made of round CI disc embossed HT Cable, of size 16cm dia 6mm thick duly riveted with angle of size 50x50x4mm and 60cm long including PCC 1:2:4 B1 using 20mm aggregate 15cm x 15cm x 15cm for grouting the same complete all as specified.
EXTERNAL WATER SUPPLY
Supply and laying Ductile iron pipes with spigot and socket ends centrifugally cast, Class K-9, in any length laid in trenches of size 80 mm dia including rubber Tytan joint
Supply and fixing foot valve conforming to IS 4038, 50 mm (3") dia
Supply install test and commissioning of centrifugal pump set, electric driven complete with all accessories suitable for pumping water 422 LPM discharge at 30 m head coupled with suitable size of electric motor AC 3 phase ,50Hz including supply and fixing the items, such as, necessary connection from starter to motor terminal using proper size of copper cable including ,connection of suction pipe from pump to foot valve, delivery pipe connected to the raising mains of the over head reservoir by means of suitable joints painting the suction and delivery pipe with super enamel paint over a coat of primer as per standard code of colour including MS base plate complete complete all as specified and directed. Note : Suction and delivery pipes shall be measured and paid under appropriate items ( main water supply pump for building)
Supply install test and commissioning of open well submersible pump set, electric driven complete with all accessories suitable for pumping water 60 LPM discharge at 30 m head coupled with suitable size of electric motor AC 3 phase ,50Hz including supply and fixing the items, such as, necessary connection from starter to motor terminal using proper size of copper cable including ,connection of suction pipe from pump to foot valve, delivery pipe connected to the raising mains of the over head reservoir by means of suitable joints painting the suction and delivery pipe with super enamel paint over a coat of primer as per standard code of colour including MS base plate complete complete all as specified and directed. Note : Suction and delivery pipes shall be measured and paid under appropriate items ( main water supply pump for building)
Note- Energy Efficient Motors-Motors shall comply with following a. All permanently wired poly phase motors of 0.375kW or more serving the building and expected to operate more than 1500 hours per year and all permanently wired poly phase motors of 50kW or more serving the building and expected to operate more than 500 hours per year shall have a minimum acceptable nominal full load motor efficiency not less than IS 12615 for energy efficient motors b. Motors of horsepower differing from those listed in the table shall have efficiency greater than that of the next listed kW motor 0.64% c. Motor horse power rating shall not exceed 20% of the calculated maximum load being served. Motor nameplate shall list the nominal full- load motor efficiencies and the full load power factor e. Motor users should insist on proper rewinding practices for any rewound motors. If the proper rewinding practice can not be assured, the damaged motor should be replaced with a new, efficient one rather than suffer the significant efficiency penalty associated with typical rewind practices f. Certificates shall be obtained and kept on record indicating the motor efficiency. Whenever a motor is rewound, Appropriate measures shall be taken so that the core characteristics of the motor is not lost due to thermal and mechanical stress during removal of damaged parts after rewinding a new efficiency test shall be performed and a similar record shall be maintained
Construction of brick masonry valve chamber of size 900x900x900 mm (internal dia) suitable for 150 mm dia sluice valve with necessary earth work excavation plain cement concrete 1:4:8 using 40 mm graded stone aggregate 75 mm thick in cement mortar 1:6 15 mm thick plastering 1:6 internally including flooring and externally up to 15 mm below ground level plain cement concrete 1:4:8 type B1 using 20 mm graded stone aggregate in coping MS sheet cover made out of 3 mm thick MS sheet flat iron frame and bracing with locking arrangement applying two coat of synthetic enamel paint including dismantling removing the existing damage chamber completely removal of debris to a distance not exceeding 50 mtr distance depositing where as directed by Eng. - in- charge.
Earthing complete with galvanized steel earth plate electrode 600mm x600 mm x 6mm buried directly in ground vertically to a depth not less then 2.25 meter below normal ground level with top edge of the plate not less then 1.50 meter below normal ground level connected to galvanized earth wire 4 mm dia by means of bolts ,nuts ,check nuts and washers complete up to and including test point made out of 40 x 6mm alum flat including earthing pit , charcoal common salt ,earth wire 4 mm dia up to 7.5m, 20mm dia medium grade GI watering pipe ,G.I. protection pipe 15 mm dia up to 7.5m long,,PPC pit in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate ,PCC pit cover including earth work complete all as shown in electrical plate No-5 of SSR-2014 (part-I). Ext Water Supply 04, Fire fighting: 04, Int Electrification: 04, AC: 06
FIRE FIGHTING
Supply and laying DI pipes K-9 size of 250 mm dia with double flanged screwed ends, in any length laid in trenches
Supply and laying DI pipes K-9 size of 150 mm dia with double flanged screwed ends, in any length laid in trenches
Supply and fix for 250mm dia PN-16, reducer, all Flange,Tee,Bend,Elbow,Gaskit Nut bolts etc., (single and double branch) any type and angle /radius and straight connecting pieces complete all as specified and directed.
Supply and fix for 150mm dia PN-16, reducer, all Flange,Tee,Bend,Elbow,Gaskit Nut bolts etc., (single and double branch) any type and angle /radius and straight connecting pieces complete all as specified and directed.
Supply and fix CI sluice 250 mm dia, valve both ends flanged and drilled, bonnet wedge stuffing box. Gland trust plate, hand wheel made out of grey CI, complete valve confirming to IS 14846/2000 and its fittings suitable for hydraulic test pressure of 15 Kg/sqcm PN 1.6 ISI marked complete all as specified and directed. MAKE : Kirloskar/ Upadhyay/ L&T
Supply and fix brass double end flanged and drilled non return valve of size 250mm dia , Pn 1.6 ISI Marked Make: Kirloskar/ Upadhyay/ L&T
Supply and fix fire alarm control repeater panel complying with BS EN 54 2 loop panel of capacity from 99 detectors & 99 modules upto 200 detectors and modules.(Panel shall be integrated with AHU Panel & Ac Plant Panel)
M & L for Low smoke Zero halogen flame retardant fire alarm cable 2 core, 1.5 mm² copper conductor confirming to BS7629-I , BS6387 & rated for 500 v grade having plain stranded copper conductor with priming insulation of glass mica fire resistance tape & secondary insulation of high performance silicon rubber with electrostatic screen of aluminium fire barrier Type LT53 outer sheath confirming to BS 7655, red in colour drawn through & concealed steel conduit ( Conduit will be measured & paid separately under relevant item including laying, fixing, connecting complete all as specified and directed).
Supply and fix suitable for Air released valve of 250 mm dia, PN 1.6 including necessary support and painting with two coats of enamel paint over a coat of primer etc., complete for wet riser termination.
BLANK
FLAME PROOF LIGHTING
S&F Flame Proof Exhaust fan of size 600 mm sweep motor -0.75 Hp, Metal body complete with and louvers connecting up including provision of three core flexible copper wire of size 23/0.0076 including ERW conduit from Jn box to exhaust fan. Make- Sudhir/Crompton Greaves/Bajaj
Supply & fixing Flame Proof Wall mounting fan 610 mm sweep high speed, thermally protected motor, heavy duty gear box, 90 degree oscillation for wide coverage conforming to IS-2997-1964 all as specified and directed by Engineer-in-Charge. , Make-Sudhir /Havells/Crompton Greaves/Bajaj/Orient
BOREWELL
Geographical survey of ground water from any approved hydrologist agency to explore the ground water potential of the area & submitting the technical report to department giving recommendation on feasibility of tube well at particular location complete all as specified and directed.
Drilling of trial bore well 200mm dia. In any type of soil/rock by rotary fast rig method or any other approved method of depth not exceeding 60 m at allocation approved by GE based on soil investigation report and disposal of waste material all as specified & directed.
Drilling of trial bore well 200mm dia. In any type of soil/rock by rotary fast rig method or any other approved method of depth exceeding 60m but not exceeding 120 m at allocation approved by GE based on soil investigation report and disposal of waste material incl. following job complete all as specified & directed.
Collection of soil sample of bore at every 1m depth & submission to department with strata chart
Collection of water sample from bore well & getting them tested from chemical & bacteriological analysis from recognised institution approved by govt.
Test on quality of water for drinking purpose
Supply and lowering plain MS casing pipe of outer dia 200mm , wall thickness not less than 5.4 mm conforming to IS specification complete all as specified and directed.
Supply and lowering plain MS ribbed screen pipe of outer dia 200mm , wall thickness not less than 5.4 mm conforming to IS specification complete all as specified and directed.
S & F Fixing cost for MS reducer, bail plug, well cap, MS strip for centring, MS iron clamps, electric logging and sample strata box
M & L development of tube well with compressed air and after with 25% extra capacity pump by pumping muddy water. (72 Hrs)
M & L yield test for the bore well by continuously pumping for 16 hours to determine safe pumping yield.
Supply, install, test and commissioning, submersible pump set, 3 phase 415 AC,2900 RPM ,head 150 m ,discharge 120 LPM suitable for 200 mm dia bore well (Casing pipe size 200/ 250 mm) supplied and installed complete Make KSB / JYOYI/KIRLOSKAR
Supply and lay/lower submersible cable in to bore hole along with submersible pump set flat PVC insulated and sheathed water proof flexible copper conductor 1100 volts grade of size flat 3 core 10 sq mm including all necessary jointing materials/kit and connecting up motor and starter terminals and testing complete all as specified & directed.
Supply, Installation, test and Commissioning, factory fabricated LT panel board, type tested by CPRI /Authorised Govt. Agencies , confirming to IEC 60349-1 & 2,up to 400 Amps incomer OR confirming to IEC 61349-1 & 2, above 400 Amps incomer, LT panel board made out of 3.15 mm thick GI Sheet multifold design, chemically treated surface with multi tank process powder coating, indoor modular type, dust free ,Vermin Proof , totally enclosed with Confirming to IP 43 for indoor panel & Confirming to IP 54 for outdoor panel, double door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Galvanised iron Angle Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Testing after Installation including complete all as specified and comprising of the following :– Make of panel board - L&T / ABB / Schneider/Siemens or by their authorised channel partners duly authenticated by the company.
M & L for Heavy duty galvanized steel socket (couplings) 100 mm long for joining GI pipe in bore holes suitable for 80 mm GI pipe complete all as specified & directed.
M & L for Pea gravel of size 5mm to 8mm size of approved quality packed around the pipe complete.
S & F MS clamp made out of 50 X 6mm MS flat of size for holding 80mm dia GI tubing including nut , bolt & washer complete all as specified and directed.
M & L for platform around bore well with PCC 1:3:6 type C2 40mm graded stone aggregate of size 1.2 X 1.2 X 0.3 m , with 2 nos GI pipe 80mm dia 60 cm long embedded in concrete
Supply and fix MS pipe End cap screwed for 200 mm PVC pipe complete all as specified and directed.
Earthing complete with galvanized steel earth plate electrode 600mm x600 mm x 6mm buried directly in ground vertically to a depth not less then 2.25 meter below normal ground level with top edge of the plate not less then 1.50 meter below normal ground level connected to galvanized earth 32 x 6mm GI strip by means of bolts ,nuts ,check nuts and washers complete up to and including test point made out of 40 x 6mm alum flat including earthing pit , charcoal common salt,Earthing lead 32x6 up to 7.5m, 20mm dia medium grade GI watering pipe, PPC pit in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate, PCC pit cover including earth work complete all as shown in electrical plate No-5 of SSR-2014 (part-I) NOTE-: GI earth strip shell be measured and paid for separately under relevant item of schedule . Bore well: 02, LP: 24
AIR COMPRESSOR
Supply and install high pressure air cooled reciprocating piston compressor with belts, belt Guard and motor pulley , pressure switch, pressure gauge ,safety valve & Drain valve ,TEFC Motor , DOL starter 5.0 HP motor discharge 14 CFM with class F insulation, 175 PSig complete with motor, starter. Pulley and belts mounted on wheels and trolley coupled with Air. Make of AIR-COMPRESSOR - ELGI / EVEREST / A-1 / KHOSLA
REFRIGERATOR & WATER COOLERS
Supply and install refrigerators, electric driven (single phase), AC 230 V, capacity 190 Ltrs having smart inverter compressor , 5 star rated, single door, direct cool complete all as specified & directed. Make:LG, Samsung, Blue star
Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 2.0 KVA
AVIATION OBSTRUCTION LIGHTS
Supply and fix aviation obstruction light of 10W LED type twin with doom and other fixing accessories.
Supply and fix SPN MCB 16A, 10 KA all as specified & directed. Make - L&T/ Bajaj/ Havell
CONDUITS FOR TELEPHONE & TV
M & L for TV socket module metal flushed including flushed Box cover plate Box for 2 way module complete all as specified.
M & L for telephone jack with module metal flushed including flushed Box cover plate Box for 2 way module complete all as specified.
LIFTS
Design, supply, install, testing& commissioning goods lift ,speed 0.5 metre/sec with single speed motor, 415 volts, 3 phase AC 50 Hz supply, conforming to IS-14665 and as amended suitable to serve up to 2 Floors (G+1) upper floors with AC Variable Voltage & VariableFrequency Drive (VVVF drive) complete suitable to carry 1000 Kg load with all standard accessories, simplex automatic& manual dual controlled operation with/without attendant, centre opening doors with door drive (electric motor driven mechanism), sliding stainless steel doors, automatic rescue device (ARD) system, 3D infra red sensor in full height of door & built in announcing system without hand set (03Nos, one each in car, Machine room & near Ground floor landing door) complete all as specified . (DRF Building 01, Ejection seat complex bldg- 01 Nos) Make: OTIS, Schindler, Kone, Mitsubishi
The lift shall conform to the following technical specification. [i] Type of Lift: Goods Lift [ii] Load Capacity: 1000 kg [iii] Speed: 0.5 m/s with single speed motor [iv] Power Supply: 3- Phase, 4 Wire, 415 V, 50 Hz AC [v] Type of Drive: AC Variable Voltage & Variable Frequency [vi] Type of Machine: Gearless
[vii] Car Size: Not less than 2.52 m² [vii] Car and Landing Door at all floors: Automatic center opening with VVVF door drive, opening size not less than 1200 mm X 2000 mm, sliding type, fabricated by stainless steel sheet not less than 16 gauge having hairline finish (N-304) [viii] Car Enclosure: Manufactured with stainless steel frame not less than 16 gauge with hairline finish (N-304) having stainless false ceiling with hairline finish, internal lighting arrangement with LED light fittings operated on commercial supply and one LED light fitting operated on battery with invertor as emergency light complete internal ventilation system provided with concealed arial/cross flow fan with auto cut-off system and stainless steel grill/wire mesh for protection [ix] Provision of standard thickness stainless steel hand-rail 40 mm diameter all around inside the car cabin [x] Terminal Buffers: Metal special spring/PU/Oil buffers as per manufacturer specifications. The buffing stroke should not be less than 200 mm. [xi] Door Opening (Inside): Protected by centre opening stainless steel doors with hairline finish doors with clear opening of 1200 mm X 2000 mm
[xii] Car & Counter Weight Guide: Guide rails of MS 'T' section as per OEM design; counter weight shall be as recommended by OEM [xiii] Flooring: 5 mm thick Aluminium chequered plate / as per OEM design [xiv] Signals: [a] Combined luminous hall buttons with LED/LCD/VFD hall position indicators at all floors [b] LED/LCD/VFD for car position indicator of stainless steel [c] One No. of car opening panel with luminous buttons in car (stainless steel) [d] Car direction indicator in car & landing [e] Battery operated alarm bell & emergency light (rechargeable) along with suitable maintenance free battery (This system should be separate from ARD batteries.)
[f] Overload warning feature in car cabin (display and announcing type both) [g] One fireman's switch to be installed at ground floor near landing door [h] All signal fixture & car operating panel on hairline stainless steel face plate with hairline finish. [i] Infrared door sensor safety edge of door for entire height. [j] Built in announcing system without handset 2 Nos., one for lift car & ground floor landing door and one announcing system with handset in machine room. [k] The interior of the car should be provided with a device that audibly announce the floor position of lift car has reached and announce that car entrance/exit door is open or closed.
[xv] Stops & Opening : 2-2 All opening on same side. [xvi] Satiety Device: [a] Automatic rescue device (ARD)/automatic landing device operating with maintenance-free batteries having suitable capacity. The batteries must have auto charging facilities. The charger input be connected with converter of regenerative drive. [b] The ARD actuation time should be less than one second after failure of power supply and when ARD is operative the car should stop at the nearest floor and then open. [xvii] Operation: Simplex, full collective automatic operation with and without attendant. [xviii] Machine room: Located above the hoist way. Details as per building drawing.
[xix] Hoist way construction details as per building drawing [xx] Civil work: Necessary Civil work viz. making good disturbed surfaces, modification to landing space to suit to car size, necessary foundation to machine etc. [xxi] One number of wall mounted type telephone instrument of make installed inside of car cabin along with fixing arrangement and telephone cable of suitable size from car cabin to machine room run along with travelling cable. The telephone instrument shall be connected in the telephone DB installed in the machine room. [xxii] Mirror of suitable size to be provided on the wall opposite to main door above SS railing.
Material & labour of Earthing complete with copper plate electrode 60×60cm ×3.15mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to copper strip 20x3 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel, GI pipe medium grade of dia 40mm for protection of copper earth strip & 20mm dia medium grade GI watering pipe, PPC pit in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate, PCC pit cover including earth work all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including testing on completion and all as direction of Eng.-in-Charge. Lift: 04, Ext WS: 04, Fire fighting 08, Air Compressor 04, AC 12
CRANE
Design, supply, install, testing and commissioning of indoor type EOT (electrically operated travelling) double girder over head crane of 2 Ton capacity, class III, M7 as per IS:3177 of 2020 and IS : 807 of 2006 and other relevant Indian standards of latest versions having straight travel path, operating on 415 volts, 3 phase, 50Hz, AC and with control voltage not exceeding 110 volts, AC through low voltage transformer with independent movable pendent supported by chain/SS rope, double girder type , floor operated movable pendent control by means of push buttons independent of crab trolley position with protective panel with down shop lead, trailing cable complete with minimum IP-55 protection for cables, motors panels incl separate canopy for for motors along with all accessories/equipment's duly epoxy painted complete all as stipulated in Annexure-'A' here in after , as shown on drawings and as directed. The span length, cross travel length & hook height mentioned is tentative exact span length, cross travel length & hook height shall be measured at site before fabrication. EOT crane shall be provided with the following specifications and capable for electrically controlled movements: (i) Capacity of Crane : 2 Ton double box girder (ii) Clear span : 7.5 m (approx.) (iii) Bay length : 13.5 m approx. (iv) Hook height : 6 m approx. (v) Hoisting speed : 3.0 mtr / min with creep control (vi) CT speed : 5.0 mtr/ min with creep control (vii) LT speed : 10.0 mtr/min with creep control (viii) Control; Pendent control,
NOTE: 1 a) The crane is to be operated in indoor as well as outdoor fully exposed to weather elements. Adequate IP protective covering over the electrical and mechanical components shall be provided b) The crane shall be provided with additional storm brakes for anchoring it to cater to storm conditions c) Automatic electrohydraulic or electromagnetic brakes shall be provided if the service brakes are not electromechanical type. d) Unit rate quoted shall be deemed to include provision of electrical wiring of suitable size in rigid metallic conduits fixed on surfaces from main switch upto electrical control panels. All cables shall be armoured copper cables. Provision of ISMC channel welded along with ISMB (gantry girder) and longitudinal travelling rail welded along with ISMC inclusive all supports, MS insulators & other fittings & fixture as reqd.
e) Clear span and bay length specified and shown on drgs are only indicative. The tenderer shall visit the site and ascertain exact span and bay length before designing / execution. f) Long travel main gantry girder will be provided by Building Contractor g) Dimensions, capacities/sizes of equipment's/ accessories mentioned on drawing are minimum to be provided. Prior approval of Accepting Officer shall be obtained for the detailed construction drg and electrical wiring diagram of EOT crane and contractor shall incorporate changes wherever required and the rates quoted above shall deemed to inclusive of such provisions and its accessories before designing / execution. h) Longitudinal / cross travel shall be limited to 1.0 m away from the wall on both ends as far as possible. j) The lowest bidder shall prepare Constructional drawing including specification as per the design of approved OEM. In case the lowest bidder is not OEM himself then lowest bidder shall submit an MOU with departmentally approved OEM for construction and executing of the crane work. Drawings and specifications in both the cases will be subject to approval of accepting officer as per Para (g) above.
WATER PURIFIER
Supply and fix Reverse Osmosis plant of output capacity of 25 litters per hour. (For water cooler)
ARBORICULTURE
M & L for supplying and staking of good soil well sieved 90% to pass through IS sieve of 10mm size free from stones rubbish like lumps, stones, roots and other foreign materials suitable for gardening. The soil should be fresh from quarry. The colour of the soil generally red including cost of all royalty and carriage, all tools, plants, taxes, octroi etc., all complete.
Supply only at site dump manure well decayed, well dried, well powdered, without clodes and free from stones, dried grass and other rubbish material. The colour of manure shall be black. The manure screened through sieve at 1:5 designation 4.75 micron including carriage at site.
Planting large Feature Trees :- Supply and planting of best quality healthy plants at site in 0.60 m x0 .60 m x0 .60m pit . Filling the pit with fresh garden soil/silt, sand & manure in ratio of 2:1 by volume (2 part of stacked volume of manure after reduction by 8%). Mixing soil/silt, sand and manure thoroughly well, levelling as directed, watering previous night, planting one or two year old healthy and 1.20 m tall specific feature trees sapling as per specifications. Watering, weeding, stirring of soil replacing of causalities etc., complete. (a) Giger - 10 Nos (b) Orchid - 10 (c) Gulmohar - 06 Nos (d) Casia Alata - 06 (e) Erythnina crystagalli - 10 Nos (f) Tulip - 08
M&L for development lawn area and planting of carpet grass or any other grass as approved by GE ,including supply and laying black cotton or other fertile earth, manuring , watering to grow upto sufficient height , maintained upto three months and cutting with grass cutting machine evenly complete.
FIRE RESISTANCE ALUMINIUM PARTITION IN MECHANICAL SIZE
S&F anodised aluminium frame powder coated for doors , windows, ventilators with one or more rebates including jointing cleats for fixing etc. complete all as specified. Thickness of powder coating will be 50 micron.
S&F sheet glass 6mm thick with 2 hrs Fire rating and and glazing secured with snap beads with rubber gasket exc. 0.5 Sqm. Make- Saint/ Gobin
S & F fire retardant plywood 12mm thick including 1mm thick laminate fixed with fire proof adhesive Archid Plywood, century Plywood or equivalent fire Retardant Plywood 12mm thick, laminated with fire proof retardant of class I fire
COMPREHENSIVE MAINTENANCE OF LIFTS
Comprehensive maintenance and repairs of fully automatic electrically operated Goods Lift - 2 nos, speed 0.5 metre/sec with single speed motor, 415 volts, 3 phase AC 50 Hz supply, conforming to IS-14665 and as amended suitable to serve up to 2 Floors (G+1) upper floors with AC Variable Voltage & Variable Frequency Drive (VVVF drive) complete suitable to carry 1000 Kg load with all standard accessories, simplex automatic& manual dual controlled operation with/without attendant, centre opening doors with door drive (electric motor driven mechanism), sliding stainless steel doors, automatic rescue device (ARD) system, 3D infra red sensor in full height of door & built in announcing system without hand set (03Nos, one each in car, Machine room & near Ground floor landing door) complete all as specified . (DRF - 1 Nos , and Ejection Seat Complex- 01 Nos) comprising of all devices and accessories through 36 months for all days including holidays etc. after expiry of defects liability period as shown below and all as specified and directed to Eng.-in-Charge Note : Contractor shall carryout comprehensive maintenance (routine, daily, weekly, monthly, quarterly, half yearly, yearly) as per attached Performa and maintain all the lifts in serviceable condition 24 hrs x 365 days with out any extra cost.
(a) 1 year after expiry of defects liability period
(b) 1 year after completion of BOQ item No. 42.02 here-in-before
(c) 1 year after completion of BOQ item No. 42.03 here-in-before
Note :- Notes :- (i) Rates quoted under Sch A shall be for both materials and labour complete unless mentioned otherwise. (ii) After expiry of the defects liability period of 24 months from the certified date of completion of work, Government reserves the right to order the contractor to carryout comprehensive maintenance services of the lift (provided by him under Sch A in accordance with terms and conditions detailed in Sch A and specifications enclosed thereof in the event of Govt. exercising the above right, the terms of comprehensive maintenance service contract shall be for a period of three years. Total period of comprehensive maintenance service contract of the lift shall be three years from the expiry date of the details liability period. (iii) The contractor shall enter in to a MOU with the OEMs for the provision of the lift and further maintenance. The MOU for the post warranty/post defect liability period between the contractor the contractor and OEM shall be submitted at least six months prior to the issue of completion certificate of the main contract.
(iv) The rate quoted under this Sch A shall be deemed to include for materials and labour required for comprehensive maintenance including repairs. (v) The work covered under Sch A will be ordered on the contractor by the respective Garrison Engineer on every year through a separate works order for the lifts installed in their area at the rate quoted by the contractor till completion of three years comprehensive maintenance.
(vi) This contract shall be operative for the period of three years after expiry of defect liability period only for the purpose of comprehensive maintenance. (vii) In case of non function of Lift recovery shall be effected after the defect is noticed or notified either in writing or through a social media message by GE or his rep in terms of PS clauses mentioned in the tender.
COMPREHENSIVE MAINTENANCE OF AIR CONDITOINING
Comprehensive maintenance comprising of routine, preventive & breakdown maintenance of chilled water type central air conditioning plant of capacity 110 TR installed, comprising of all devices and accessories through out 12 months on all days including sundays & holidays for a period of 03 years after expiry of defects liability period (i.e. 24 months after completion of all Phase II tests) all as specified and directed and as shown below:-
(a) 1 year after expiry of defects liability period
(b) 1 year after completion of BOQ item No.43.02 here-in-before
(c) 1 year after completion of BOQ item No.43.03 here-in-before
MANING AND OPERATION OF CENTRAL AC PLANTS
Outsourcing of services round the clock ( consisting of three shifts) including Sundays and holidays and operation of Central type air conditioning plant of capacity 3 x 55 TR ( Two plants each to be run at a time and one will be kept as stand by) including all connected electrical items such as main switch, starter,change over switch, MCCB, voltmeter, ammeter, panel board etc, cooling tower,condenser or water pump ,valve system,controling system, condenser,refrigerant line,adjusting valve, refrigrant valve, bypass valve, daily checcking, leakage, checking noise, controlling temp. of plant,cleaning of plant and it's surrounding area etc, by one Ref Mech (Skilled) per shift for 03 shifts in a day all as per manufacturers instructions and as specified and directed by Engr-in-charge.
(a) 11 months after completion of work
(b) 11 months after completion of BOQ item No. 44.02 here-in-before
(c) 11 months after completion of BOQ item No. 44.03 here-in-before
(d) 11 months after completion of BOQ item No. 44.04 here-in-before
(e) 11 months after completion of BOQ item No. 44.05 here-in-before
(f) 05 months after completion of BOQ item No. 44.06 here-in-before
NOTE:- (a) The contractor shall be responsible for periodical maintenance, as per maintenance schedule attached and specified including renewal / replacement of parts, fittings / fixtures filling of refrigerant gas etc required for smooth functioning of the plant as per manufacturers instructions. (b) The Contractor shall Employ Refrigeration mechanichaving minimum ITI qualification from Govt Recognised institute with adequate knowledge & minimum 2 years experience in maint/operation of AC plants. The operator must competent to carry out the minor maint all as directed. (TOTAL number of operators required per day are 03 nos.)
(c) Contractor shall pay the wages to the employees through e-payment i.e Adhaar linked bank accounts (credit to their bank account). Engineer-in-charge shall ensure that e-payment made to employees and their wages shall not be less than minimum wages fixed by state Govt or Central Govt whichever is more. Monthly e-banking statement shall be furnished by the contractor to the Engr-in-charge and the same shall be kept in record duly verified.
(e) The contractor shall maintain all the registers under various labour law rules, 2017 and shall be produced to the Engineer-in-Charge as well as officers detailed by central labour department. (f) Each shift duration shall be 8 hours & duty timing will be decided by Engr-in-Charge.
(g) The unit rate quoted shall deemed to be included for cost of labour for daily routine maintenance for trouble free functioning of installation. (h) In case of any abnormal noise/ complaint the plant should be put off and same should be brought to the notice of Engr-in-charge. (j) The operator employed by the contractor shall be capable of carrying out minor repair/ maintenance & should have well experience in AC plants as applicable.
(r) The contractor shall provide board at proper location near each installations duly writting the name of operators and Mobile Numbers shiftwise. (s) In case of non function of AC Plant panel recovery @ 3000 per day shall be effected 24 hrs after the defect is noticed or notified (t) Any defect in to a motor , Pumps, compressure ,Control Panel ,AHU, Refrigarent Gas , Cooling Tower shall be considered as outstanding defect & Panel charge will be applicable as above in Note (r )
S.N. Constructions
vijay infraprojects pvt ltd
SOOD ASSOCIATES PVT LTD
Bidder Name
S.N. Constructions
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid