AMC for Grid stations
2021_PDD_121869_1
TLMD-IV/e-NIT/03 OF 2021-22
Open Tender
Electrical and Maintenance Works
Item Wise
360 days
Pampore/ zainakote
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,100
Executive Engineer TLMD-IV, Pampore
Exempted
4 May 2021
6 Apr 2021
4 May 2021
7 Apr 2021
3 May 2021
7 Apr 2021
180 days
Amount
Power Transformer :-
Checking of Auto starting of fans, External cleaning of radiators, Cleaning of marshalling boxes of transformer/reactor and OLTC, (ii) Tightening of terminations, Checking of OLTC driving mechanism, Electrical checking/ testing of pressure relief device, Buchholz relay, OLTC surge relay/ checking of alarm/ trip and checking of alarm/ trip and checking/ replacement of the gaskets of the terminal box, Checking / Tightning of earthing connections, Checking of earth resistance of Neutral, Replacement of Silca Gel of breathers and oil toping of transformers 20MVA to 50MVA, including tandelta testing of bushing/ winding & DGA/ BDV testing of transformer oil.
Draning/ De-sludging of transformer oil of transformers
Filling of oil, filitration and dehydration of transformer including installation of vacume pump
Reparing of cooloing fans of transformers including replacement of damaged winding, bearing etc.
Lifting of top lid of power transformer for complete physical inspection & replacement of gaskets.
Replacement of damaged core bolts/Earthning strip etc.
Overhualling of Circuit Breaker :- Checking of oil pressure drop during duty cycle operation check, Checking of auto-starting / stopping of oil pump,pressure switch setting,etc, Checking of healthiness of accumulator by checking the pre-charging pressure when building up pressure from zero, Checking of operation of safety valve, Cleaning of breaker units, checking of protection equipmentsand replacement of defective ones, i.e., complete inspection and testing of SF6 type circuit breakers inclusive of operating mechanism. Maintaning gas levels, venting of circuit breakers, replacement of o-rings , gas kits including circuit breaker anylises by CBA etc.
220KV SF6 Breaker
132KV SF6 Breaker
33KV VCB
Current Transformers :- Checking of bellow expansion, Checking of oil leakage in terminal box, Checking of primary connection strips, Checking of healthiness of gaskets,Checking the tightness of all connections including earthing of PF terminal, Cleaning of marshalling box and junction box, Checking cleanliness / tightness of all electrical connections including earthing of all marshalling boxes, CT secondary terminal, space heater and illumination, healthiness of secondary terminal bushing, checking of oil level, measurement of IR value tightening of jumpers, CT anylises with the help of CTA etc.
CVT's / PT's :- Visual checking of earthing HF point (in case it is not being used for PLCC,Checking of any breakage or cracks in cementing joint, Cleaning of CVT capacitor stacks and tightness of terminal connections, Checking of space heater and illumination,Checking and tightness of all connections including earth connections Cleaning of marshalling box and junction box, Checking of healthiness of gaskets, Checking of neutral earthing in CVT, healthiness of all gaskets and oil level. Measurement of IR value and tightening of all connections and droppers.
Surge Arrestors :- Checking of leakage current(third harmonic resistive current), Testing of counters and leakage current meters, Cleaning of insulators, Checking of earth connections between surge arrester,surge monitor and earth, Checking of leakage current after cleaning of porcelain surface, cleaning of LA insulators. Measurement of IR value and tightening of droppers and testing of counter and leakage of current meters, Cleaning of insulators, Checking of earth cennections between surge arrester, Surge moniter and Earth.
Isolators :- Maintenance of linkages including transmission gears, stopper bolts. Cleaning of auxiliary switch contacts and greasing with silca grease, cleaning of support insulators, termination contacts, checking of elecctrical / mechanical interlocks with E/S and CB, mounting bolts, alignment, nuts, pins, space heater, illumination, healthiness of gaskets, auxiliary contacts, alignment of earthing blades, operation of earth switch, almunium / copper flexible conductor, earth connections of structures and MB. lubrication of operating mechanism, hinges lock joints, levers, bearings, main contacts, cleaning of post insulators, tightening of clamps.
Post Insulators :- Checking of insulators for cracks and cleaning of insulators.
Gantry Columns and Beams :- Tightening of all nuts / bolts and providing of missing nuts / bolts and damaged members
Reparing of Three phase motors of isolators including replacement of damaged winding and bearing.
:Replacment of damage 220kV/132kV CT/PT/LA including dismentiling.
DROPERS/JUMPERS/Clamps :- Replacement of damaged / burnt droppers or jumpers or Clamps of isolators/ breakers/transformers /CT/PT etc. 220/132/33kV Yard
Illumination System :- Checking of healthiness of fittings in station buildings, outdoor switch yard, repairing and replacement if required, lighting of panels. Tightening of terminals etc.
Battery Bank: Checking and cleaning of battery cell terminals, application of patrolum gelly, if required, conduction of battery impendence test and discharge test checking voltage temperature, current, sp. Gravity of individual cells as well as terminals voltage, battery dischrge testing etc.
Battery Charger :- Checking of control cards, measurement of test point voltage values, testing of DC earthfault and U/V relays, IR measurement of charger transformer, checking of earthing etc. Checking of charger panel / DCDB for electrical connections, cleanliness etc.
Protection System :- Checking of relays and application of CCl4 for cleaning, replacement of worn out / defunct relays, checking and replacement of control wiring, if required, primery & secondery injection testing etc.
cleaning of cable trenches, trays, racks etc
L.T. Transformer :- Testing of oil BDV, IR measurement, Testing /checking of OTI,WTI and Buchholz (if provided, Checking of healthiness of Pressure relief diaphragm, Checking healthiness of Buchholz relay, Checking tightness of earthing connections L.T Pannel: Cleaning of panels,bus bar insulators etc. Relays Testing, Tightning of all electrical connections,Checking of indicating meters ,Check for change-over facility, if provided,Check operation /indications in OFF Load condition of MCCB,
Earthing Mat :- Measurment of earth resistivity, checking of electrical continuity of equipment earthings, tightening of earthing connectors, removal of rust from bolted earth connectors and tightening. 220/132kV
DC Distribution Board :- Checking of connections, wiring, replacement of wiring if needed and checking of healthiness of all D/C lights.
Fire Protection System:- Refilling of fire fighting CO2 and dry chemical powder gas cylinders, providing of Nosels etc.
Deweeding of switch yard
General inspection, cleaning, tightening of electrical connections of C &R pannels, D C /AC Diatrbution pannels etc
Painting of outdoor equipments (Transformers, MK's, CT/PT/CVT, Protection wall, Circuit breaker, isolatores, poles etc.
Fixing of anti clambing device/Bird Guard over D/C tower
Fixing of phase plates/No. plates/danger plates over D/C tower
Fitting of repair slevees comperssion type for over ACSR conductor
Store handling:
Unloading / Loading of C&R Panels, in divisional store Pampore Including manual Carriage within store yard).
Unloading / Loading of ,angle iron, Tor steel , tower material in divisional store Pampore Including manual Carriage within store yard).
Unloading / Loading of CT/CVT/PT/CB etc in divisional store Pampore Including manual Carriage within store yard).
PG Clamps suitable for 0.4 ACSR Conductor
Isolator pad clamps 0.4
Isolator pad clamps 0.5
Isolator pad clamps 0.75
CT Twin clamps suitable for 0.4 conductor
LA Clamps 0.75 x 0.4
LA Clamps 0.5 x 0.5
PG Clamps 0.4
PG Clamps 0.7
PG Clamps 0.5
Paid clamps 0.4 x0.4
T- Clamps 0.7x0.7
T- Clamps 0.4x0.2
T- Clamps 0.4 x 0.7
T- Clamps 0.7 x 0.4
PG Clamps for 100 mm² ACSR Conductor
Aeroshell fluid F-41 (shell make)
SF6 gas
Double tension fittings 0.4 ACSR
Single tension fittings 0.4 ACSR
Single tension fittings 0.2 ACSR
Vibration Dumper 0.2 ACSR
Single Suspension Fittings ACSR 0.4
M/S IRFAN AHMAD DAR
M/s B. L. TRADERS
stage.html
html • 0.02 MB
finance_235199.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .