| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.6 LAccepted-AOC NO 51 TOWN HALL 3RD STREET ARAKKONAM TAMIL NADU 631 001 | ARAKKONAM | RANIPET | TAMIL NADU | 631001 | L1 | Accepted-AOC L1 | |
| 2 | L2₹32.0 L+₹7.1 L (28.2%)Rejected-AOC 2 RC ENTERPRISES NEAR AGRASEN BHAWAN BHATAPARA CHHATTISGARH LINK ROAD BALODA BAZAR RAIPUR CHHATTISGARH 493118 | BALODA BAZAR | CHHATTISGARH | 493118 | L2 | Rejected-AOC L1 being accept |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
28 May 2024, 6:00 pmClosed
CWE NAVY CHENNAI
Commander Works Engineers Navy Military Engineer Services Fort St George Rajaji Salai Chennai600 009
87962 REPAIRS MAINTENANCE TO PACKAGE AND DUCTABLE TYPE AIR CONDITION PLANT OF VARIOUS CAPACITY UNDER GE(M) ARAKKONAM
2024_MES_650140_1
CWE/NAVY/ARK/87692/E8 OF 2023-24
Open Tender
Miscellaneous Works
Item Rate
180 days
Arakkonam
As per NIT
8 documents required · 8 mandatory
₹500
GE Maint Arakkonam
₹60,000
Yes
27 Jun 2024
26 Apr 2024
30 May 2024
26 Apr 2024
28 May 2024
10 May 2024
26 Apr 2024 - 3 May 2024
Amount
SCHEDULE 'A' PART-I [ AC PLANT WORKS]
Material and labour for servicing and cleaning of condenser coil unit and cooling Coil unit of Package type AC Plant by cleaninhg chemical and flushing with plain water by pressure pump for removing complete trace of soda from the coil and fix in original position including testing all as specified and directed for the following capacity Package type AC plants. (Note: Servicing and cleaning shall be done once in 6 month)
(a) 5.5 TR Capacity
(b) 8.5 TR Capacity
(c) 11TR Capacity
(d) 17 TR Capacity
(e) 22 TR Capacity
Material and labour for servicing and cleaning of AHU and Duct unit (supply air and return air) ,removing, any obstruction for AIR flow by air blower etc, and taking out all un wanted materials including cleaning Micro filter all as specified and directed by Engineer-in-Charge for the following capacity Package type AC plants. (Note: Servicing and cleaning shall be done once in 6 month)
(a) 5.5 TR Capacity
(b) 8.5 TR Capacity
(c) 11TR Capacity
(d) 17 TR Capacity
(e) 22 TR Capacity
Supply & Fixing of washable Air filter of 5 Microns for the following size suitable for ductable package type AC plants all as specified & directed by Engineer-in-charge
(a) Air filter of size 1.8" x 1.8"
(b) Air filter of size 1.6" x 1.10"
(c) Air filter of size 2.5" x 1.6"
(d) Air filter of size 2' x 2'
(e) Air filter of size 1.'6" x 7'
(f) Air filter of size 1' x 4'
S&F for renewal of damaged insulation of refrigeration system of various unit with 6mm thick nitrile foam as specified and directed by Engr-in-charge.
Material & Labour for dismantling unserviceable / worntout "V" belts any type / model , supply and fix new "V" Belt of following specification and testing. Make :- FENNER / DUNLOP / V GRIP
(a) V- Belt of size A- 22
(b) V- Belt of size A-26
(c) V- Belt of size A- 30
(d) V- Belt of size A-32
(e) V- Belt of size A-36
S&F Filter Drier/Strainer suitable for Package type AC Plant for the following size liquid line including taking down old unserviceable one all as directed. Make; DANFOSS/EMERALD/RAPID COOL/SPARLAN
Liquid line of size 3/8 "
Liquid line of size 1/2 "
Liquid line of size 5/8 "
S&F Expansion Valve suitable for the following capacity Package type AC unit including taking down old unserviceable one all as directed. Make; Donfos/Rotex/Sporlon
5.5 TR Package type AC
8.5 TR Package type AC
11 TR Package type AC
17 TR Package type AC
22 TR Package type AC
S&F Ammeter digital type (Three digit)with suitable CTs 5A Class I as per L&T / Siemens /ABB /AE /Meco
S&F Aluminium Lugs suitable for wire of following below size:-
(a) Lugs suitable for wire upto 16 Sqmm
(b) Lugs suitable for wire 25 Sq mm
(c) Lugs suitable for wire 35 Sq mm
(d) Lugs suitable for wire 50 Sq mm
(e) Lugs suitable for wire 70 Sq mm
(f) Lugs suitable for wire 95 Sq mm
S&F Copper Lugs suitable for wire of following below size
(a) Single core 16 sq mm
(b) Single core 10 sq mm
(c) Single core 6 sq mm
(d) Single core 4 sq mm
S&F Single core PVC insulated (unsheathed) multi strand flexible Copper conductor FRLS cable of following below size 1100Volts grade Make: Polycab/ Finolex/Plaza
(a) Single core 16 sq mm
(b) Single core 10 sq mm
(c) Single core 6 sq mm
(d) Single core 4 sq mm
S&F in replacement Power Contactor of following capacity Make : L&T /Siemens /Schneider.
(a) Power contactor 40A 3 Pole 415 Volt
(b) Power contactor 32A 3 Pole 415 Volt
(d) Power contactor 25A 3 Pole 415 Volt
(e) Power contactor 18A 3 Pole 415 Volt
S&F in replacement Power Contactor with NC & NO along with overload relay and timer of following capacity Make : L&T /Siemens /Schneider.
(a) Power contactor 40A 3 Pole 415 Volt
(b) Power contactor 32A 3 Pole 415 Volt
(c) Power contactor 25A 3 Pole 415 Volt
(d) Power contactor 18A 3 Pole 415 Volt
S&F Condenser Fan Blade with complete asembly suitable for the following capacity plants all as specified & directed by Engineer-in-charge.
(a) 5.5 TR Package type AC
(b) 8.5 TR Package type AC
(c) 11 TR Package type AC
(d) 17 TR Package type AC
(e) 22 TR Package type AC
Material and Labour for taking down Condenser fan motor of following capacity from outdoor unit from original location for overhauling serive (ie greasing, oiling and varnishing to the startor winding and replace the worn out bearing, painting with two coats of systhetic enamel paint) and refixing to the original locaction including testing complete all as specified and directed.
(a) 370 W, 940 RPM, Three Phase, 440 V, 50 Hz
(b) 370 W, 930 RPM, Three phase 440 V, 50 Hz
(c) 370 W, 910 RPM, Single phase 230 V, 50 Hz
(d) 250 W, 900 RPM, Single phase 230 V, 50 Hz
(e) 190 W, 920 RPM, Single phase 230 V, 50 Hz
Material and Labour for taking down the unserviceable Condenser fan motor and dismantling including taking out damaged/burnt out winding from motor, cleaning the slots with CTC and rewinding the same with new super enamelled copper winding wire of existing gauge and turns, oiling and greasing, assembling and installing back into position and testing for satisfactory running complete for the following capacities
(a) 370 W, 940 RPM, Three Phase, 440 V, 50 Hz
(b) 370 W, 930 RPM, Three phase 440 V, 50 Hz
(c) 370 W, 910 RPM, Single phase 230 V, 50 Hz
(d) 250 W, 900 RPM, Single phase 230 V, 50 Hz
(e) 190 W, 920 RPM, Single phase 230 V, 50 Hz
Taking out existing old defected condenser fan motor, supply and fixing new Condenser fan motor of the following capacity from outdoor unit from original location including testing complete all as specified and as directed.
(a) 370 W, 940 RPM, Three Phase, 440 V, 50 Hz
(b) 370 W, 930 RPM, Three phase 440 V, 50 Hz
(c) 370 W, 910 RPM, Single phase 230 V, 50 Hz
(d) 250 W, 900 RPM, Single phase 230 V, 50 Hz
(e) 190 W, 920 RPM, Single phase 230 V, 50 Hz
Material and labour to carry out the leak test on complete refrigeration system (indoor & Out door unit) by charging the dry nitrogen gas & hold up to 24 hrs and rectifying the leakage by bracing / welding / replacing the worn out parts of refrigerant line etc including vacuumising complete system of Package Type ductable Air-conditioning plant with double stage vaccum pump of upto 29 inches of mercury pressure after repairs / replacement of compressor or Repair in Refrigeration System, including labour cost for charging the refrigerant Gas for following plants complete all as specified & directed.
(a) 5.5 TR Package type AC
(b) 8.5 TR Package type AC
(c) 11 TR Package type AC
(d) 17 TR Package type AC
(e) 22 TR Package type AC
Note for Item No.20 :- (i) New Refrigerant gas shall be measured and paid separately as supply only under relavant items. However the T&P and labour charge deemed to include the unit rate quoted above. (ii) Once the Gas charged in it, it should hold in the system minimum six months if any gas leaked from the system the contractor has to charge the gas upto required level on free of cost and No extra cost on this account shall be claimed. (iii) Leakage test on each complete unit shall be measured separately.
Material and labour for taking down the burnout / defective scroll type compressor from the unit and supply and fixing factory made new Scroll type Compressor including necessary welding/brazing, testing and commissioning complete all as specified and directed for the following capacity AC plants. Make : Danfoss/Kirloskar/Blue star/Voltas/Carrier/copeland/as per existing make in plant as approved by GE.
(a) 5.5 TR capacity
(b) 8.5 TR capacity
(c) 11 TR capacity
Note for Item No.22 :- Leak test , Vacuuming & Refrigerant gas charging shall be measured and paid under relavant items.
Supply only R-22 Refrigerant Gas
Supply only R-410A Refrigerant Gas
Material and labour for taking down the indoor unit Blower Motor from original location for overhauling including greasing, oiling and varnishing to the startor winding and painting with two coats of systhetic enamel paint and refixing to the original location including testing complete all as directed for the following capacity blower motors:- (Replacement of bearing will be measured and paid separately as supply only) however labour cost for replacement of bearing shall be deemed to be included in the quoted rate.
(a) 5 HP, Three Phase, 440V, 50 Hz, 1440 RPM
(b) 3 HP, Three Phase, 440V, 50 Hz, 1430 RPM
(c) 2 HP, Three Phase, 440V, 50 Hz, 1420 RPM
(d) 3/4 HP, Three Phase, 440V, 50 Hz, 1440 RPM
(e) 450 W, Single Phase 230 V, 50 Hz, 1440 RPM
(f) 450 W, Single Phase 230 V, 50 Hz, 1350 RPM
(g) 1/2 HP, Single Phase, 230 V, 50 Hz, 930 RPM
(h) 1/2 HP, Single Phase ,230 V, 50 Hz, 950 RPM
Taking down the unserviceable burnt out indoor unit Blower Motor of following capacity and dismantling including taking out damaged/burnt out winding from motor, cleaning the slots with CTC and rewinding the same with new super enamelled copper winding wire of existing gauge and turns, oiling and greasing, assembling and installing back into position and testing for satisfactory running complete all as directed.
(a) 5 HP, Three Phase, 440V, 50 Hz, 1440 RPM
(b) 3 HP, Three Phase, 440V, 50 Hz, 1430 RPM
(c) 2 HP, Three Phase, 440V, 50 Hz, 1420 RPM
(d) 3/4 HP, Three Phase, 440V, 50 Hz, 1440 RPM
(e) 450 W, Single Phase 230 V, 50 Hz, 1440 RPM
(f) 450 W, Single Phase 230 V, 50 Hz, 1350 RPM
(g) 1/2 HP, Single Phase, 230 V, 50 Hz, 930 RPM
(h) 1/2 HP, Single Phase ,230 V, 50 Hz, 950 RPM
Taking out existing old defected indoor blower motor, supply and fixing new indoor Blower Motor of the following capacity from indoor unit from original location including testing complete all as specified and as directed.
(a) 5 HP, Three Phase, 440V, 50 Hz, 1440 RPM
(b) 3 HP, Three Phase, 440V, 50 Hz, 1430 RPM
(c) 2 HP, Three Phase, 440V, 50 Hz, 1420 RPM
(d) 3/4 HP, Three Phase, 440V, 50 Hz, 1440 RPM
(e) 450 W, Single Phase 230 V, 50 Hz, 1440 RPM
(f) 450 W, Single Phase 230 V, 50 Hz, 1350 RPM
(g) 1/2 HP, Single Phase, 230 V, 50 Hz, 930 RPM
(h) 1/2 HP, Single Phase ,230 V, 50 Hz, 950 RPM
Supply only Ball Bearing for Blower Motor at Item No. 26 here-in-before as per existing type/size for the package type AC Plant at Make:SKF/NBC/TATA /as per existing make in plant as approved by GE. Note: labour cost deemed to be included in rate quoted in item No. 26 here-in-before
S&F in replace the package type AC Plant Micro processing unit PCB with Remote control set or for the following capacity plants all as specified & directed by Engineer-in-charge.Make Blue star/ Carrier
(a) 5.5 TR Package type AC
(b) 8.5 TR Package type AC
(c) 11 TR Package type AC
(d) 17 TR Package type AC
(f) 22 TR Package type AC
S&F in replacement LP cut out switch all as specified & directed. Make: DAN FOSS/IND FOSS/DWYER
S&F in replacement HP cut out switch all as specified & directed. Make: DAN FOSS/IND FOSS/DWYER
S&F in Replace damaged PVC drain pipe 32 mm dia all as specified & directed by Engineer-in-charge
S&F in replace Single Phase Preventer unit 415 V,3Ph. Make : Minilec, Model : VSP-3 415 Volt AC, 3 Phase, 50 Hz/L&T/Siemens.
S&F in replace PVC connectors 8.5 to 20 Amps heavy duty 25 mm all as specified & directed by Engineer-in-charge
M&L to attend the complaints on the package type AC Plant, control panel, Micro processing unit of the system of any make / capacity as and when required all as directed by Engineer-in-charge Note: Spares if any required shall be measured under relevent items as supply only
Note for item no-36 (i) The complaint should be attended on same day. (ii) Non recitification of complaints if any The contractor shall be leived penalty of Rs 300 per day per complaint till completion.Recovery will be effected from the RAR
S&F MCCB, adjustable type of following capacity/specification ,440V, 50 Hz, with extended terminal & spreader link. Make : Legrand / L&T/ Siemens/ ABB/ Schneider
(a) MCCB 4 pole, 36 KA 125 Amp
(b) MCCB 4 pole, 25 KA 100 Amp
(c) MCCB 4 pole, 25 KA 63 Amp
S&F MCB of following capacity/specification ,440V, 50 Hz. Make : Legrand / L&T/ Siemens/ ABB/ Schneider
(a) MCB 3 pole, 40 Amp, C Type
(b) MCB 3 pole, 32 Amp, C Type
(c) MCB 3 pole, 16 Amp, C Type
S&F in Replace Capacitor of following capacity for condenser fan motor all as specified & directed
(a) Capacitor of capacity 10 mfd
(b) Capacitor of capacity 08 mfd
(c) Capacitor of capacity 05 mfd
S&F in Replace Bi metal Relay with single phase protection for contactor mounting relay of following range all as specified & directed. Make Siemens /L&T/BCH
(a) Bi metal Relay of range 12.5 to 20 Amps
(b) Bi metal Relay of range 25 to 40 Amps
S&F in replacement Copper Capillary tube 0.9 mm diameter for including the brazing work all as specified & directed.
S&F in replacement Air Blower of following size for Package type AC Plant all as specified & directed.
(a) Air Blower of size 15" X 15"
(b) Air Blower of size12" X 12"
Supply only Shaft for Blower any size at Item No. 26 here-in-before as per existing type/size for the package type AC Plant all as specified & directed by Engineer-in-charge Note: labour cost deemed to be included in rate quoted in item No. 26 here-in-before
Supply only Digital Clapm meter with TRMS all as specified & directed by Engineer-in-charge Make: Meco/ Fluke/Sanwa
S&F Scanner 10 Amps, UV cut off 340 V to 360 V all as specified & directed by Engineer-in-charge
rc enterprises
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .