Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹10.0 CrAccepted-AOC FLAT NO 2450 KRISHNA COLONY JIND 126102 | JIND | HARYANA | 126102 | ₹10.0 Cr | 1 | Accepted-AOC Rates are reasonable |
| 2 | 2₹10.4 CrRejected-Finance HSVP PANCHKULA | PANCHKULA | HARYANA | 133301 | ₹10.4 Cr | 2 | Rejected-Finance Rates are on higher side as compare to L1 |
| 3 | 3₹10.7 CrRejected-Finance HSVP PANCHKULA | PANCHKULA | HARYANA | 133301 | ₹10.7 Cr | 3 | Rejected-Finance Rates are on higher side as compare to L1 |
| 4 | 4₹13.3 CrRejected-Finance 858 SECTOR 23 127021 | BHIWANI | HARYANA | 127021 | ₹13.3 Cr | 4 | Rejected-Finance Rates are on higher side as compare to L1 |
| Sl No | Description | Qty | Unit | M/S SHREE BALAJI BUILDERS L4 | Himmat Singh Contractor L3 | ROHTASH KUMAR CONTRACTOR L2 | M/S AAR PEE CONSTRUCTION COMPANY JIND L1 |
|---|---|---|---|---|---|---|---|
| 1.10 | Supply , erection, jointing and commissioning of 10 sqmm ISI marked alluminium cable in trenches under ground for campus lightening including all labour jointing material complete in all respect. (Length = 100 m)
Supply erection testing of reputed make LED light 100 wats with fittings and accessories complete in all repects. (LED= 10 no.)
Provision for suitable size switches borads along with switches including all material and labour complete in all respect. | 1 | Job | 85,000 ₹85,000 | 50,000 ₹50,000 | 55,000 ₹55,000 | 55,000 ₹55,000 |
| 1.20 | HT Metering Panel: Supply Indoor Type 11KV VCB Control Cubical Panel with vertical Isolation Type Breaker as per Relevant IS as amended up to Date and Additional Specifications, having Capacities as Mentioned Below, Single break trip free mechanism, manually charged and Auto/Manually closing breaker suitable for use on 11kv, 3 phase 50hz AC, Supply with short circuit fault level of 500 Amps Capacity, breaker featured with local ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 2NO plus 2NC and equipped with following switchgears and accessories including making suitable structure arrangement for installation, control wiring and connections etc. as reqd. (1 IC plus 2 OG)
a). VCB, 11KV, 630Amp, 50KA.
b). 1ph 11KV/110 Volts PT (indoor type) Class 0.2 Accuracy and 100 VA burden -3 no’s.
c). 33KV indoor dead type dual core dual ratio 3CTs of ratio 200-100/5-5 A of 15 VA burden, PS 5 P10 and accuracy class 0.2.
d). Control panel- Cubicle type control panel suitable for floor mounting made out of 1.63 mm CR sheet duly powder coated and with following relays.
e). Microprocessor based numerical relay for O/L, E/F and SC Protection suitable for above.
f). Master trip relay -2 no’s.
g). Indicator type Annunciator panel with buzzer.
h). Digital Volt Meter- 0-11 KV.
i). Digital Amp Meter- 0-100 Amp.
j). RYB/ Trip/Closing/Spring charged indicator lamp.
k). Fault Annunciator panel for O/L, WTI, OTI and Buchhloz Relay Alarm And Trip Auxiliary relay.
l). TNC Switch for Operation.
m). Multifunction Meter EM6400NG.
n). TCS Relay for Safe
(At Raw Water pumping station) | 1 | Job | 1,85,000 ₹1.9 L | 6,45,000 ₹6.5 L | 6,50,000 ₹6.5 L | 3,40,000 ₹3.4 L |
| 1.30 | NON CLOG SEWAGE PUMP: Supplying, erection, testing and commissioning of Submersible motor pumping set non clog for sewerage having head below mentioned as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked. ` 5100 LPM x 25.00 M Head (For IPS-1) | 1 | Nos. | 4,35,000 ₹4.3 L | 3,70,000 ₹3.7 L | 3,75,000 ₹3.8 L | 3,95,000 ₹4.0 L |
| 1.40 | NON CLOG SEWAGE PUMP: Supplying, erection, testing and commissioning of Submersible motor pumping set non clog for sewerage having head below mentioned as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked. ` 1700 LPM x 25.00 M Head (For IPS-1) | 2 | Nos. | 3,35,000 ₹6.7 L | 1,19,000 ₹2.4 L | 1,20,000 ₹2.4 L | 2,60,000 ₹5.2 L |
| 1.50 | NON CLOG SEWAGE PUMP: Supplying, erection, testing and commissioning of Submersible motor pumping set non clog for sewerage having head below mentioned as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked. `850 LPM x 25.00 M Head (For IPS-1) | 2 | Nos. | 2,35,000 ₹4.7 L | 57,000 ₹1.1 L | 60,000 ₹1.2 L | 1,90,000 ₹3.8 L |
| 1.60 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 5100 LPM 25 Mtr. Head Compatible to work with cable length of 100 meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For IPS-1) | 1 | Nos. | 2,85,000 ₹2.9 L | 2,30,000 ₹2.3 L | 2,33,000 ₹2.3 L | 2,05,000 ₹2.0 L |
| 1.70 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 1700 LPM 25 Mtr. Head Compatible to work with cable length of 100 meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For IPS-1) | 2 | Nos. | 2,35,000 ₹4.7 L | 1,02,000 ₹2.0 L | 1,03,800 ₹2.1 L | 1,45,000 ₹2.9 L |
| 1.80 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 850 LPM 25 Mtr. Head Compatible to work with cable length of 100 meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For IPS-1) | 2 | Nos. | 1,85,000 ₹3.7 L | 97,000 ₹1.9 L | 97,300 ₹1.9 L | 1,15,000 ₹2.3 L |
| 1.90 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. (70 Sqmm size) | 30 | Metre | 1,385 ₹41,550 | 5,200 ₹1.6 L | 5,200 ₹1.6 L | 2,200 ₹66,000 |
| 2.10 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. (25 Sqmm size) | 30 | Metre | 685 ₹20,550 | 1,900 ₹57,000 | 1,900 ₹57,000 | 900 ₹27,000 |
Tender Value
₹12.3 Cr
EMD Value
₹24.5 L
Closing Date
9 Mar 2026, 2:00 pmClosed
ADARSH KUMAR SINGLA
Hisar PHED No. 2
DPR FOR STRENGTHENING OF EXISTING SEWERAGE SCHEME BY PROVIDING IPS and LAYING THE BALANCE SEWER LINES
2026_HRY_502263_1
2026EF91E2C3 B86A 4B5A B412 A710608AFD25565PUH
Open Tender
Civil Works
600 days
Uklana Mandi
As per DNIT
3 documents required · 3 mandatory
₹20,000
₹24.5 L
Yes
19 May 2026
12 Feb 2026
9 Mar 2026
12 Feb 2026
9 Mar 2026
12 Feb 2026
Select, Excess (+), Less (-) Less (-)
Tender Inviting Authority: EE PHED-2 Hisar
DNIT Name : UKLANA TOWN: DPR FOR STRENGTHENING OF EXISTING SEWERAGE SCHEME BY PROVIDING IPS and LAYING THE BALANCE SEWER LINES AT UKLANA TOWN DISTRICT HISAR. “Construction of IPS comprising collecting tank, pump chamber, boundary wall, Rising main lines, D.G set, electric transformer and pumping machinery. Laying the sewer lines and construction of manholes etc. and all other works contingent thereto`.
Contract No: 01662-246249
Name of the Bidder/ Bidding Firm / Company :
Sl. No. Item Description NS Item Item Code / Make Quantity Units Estimated Rate in Rs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder in Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category
1.1 Supply , erection, jointing and commissioning of 10 sqmm ISI marked alluminium cable in trenches under ground for campus lightening including all labour jointing material complete in all respect. (Length = 100 m) Supply erection testing of reputed make LED light 100 wats with fittings and accessories complete in all repects. (LED= 10 no.) Provision for suitable size switches borads along with switches including all material and labour complete in all respect. Job Excess(+) Full Conversion INR
1.2 HT Metering Panel: Supply Indoor Type 11KV VCB Control Cubical Panel with vertical Isolation Type Breaker as per Relevant IS as amended up to Date and Additional Specifications, having Capacities as Mentioned Below, Single break trip free mechanism, manually charged and Auto/Manually closing breaker suitable for use on 11kv, 3 phase 50hz AC, Supply with short circuit fault level of 500 Amps Capacity, breaker featured with local ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 2NO plus 2NC and equipped with following switchgears and accessories including making suitable structure arrangement for installation, control wiring and connections etc. as reqd. (1 IC plus 2 OG) a). VCB, 11KV, 630Amp, 50KA. b). 1ph 11KV/110 Volts PT (indoor type) Class 0.2 Accuracy and 100 VA burden -3 no’s. c). 33KV indoor dead type dual core dual ratio 3CTs of ratio 200-100/5-5 A of 15 VA burden, PS 5 P10 and accuracy class 0.2. d). Control panel- Cubicle type control panel suitable for floor mounting made out of 1.63 mm CR sheet duly powder coated and with following relays. e). Microprocessor based numerical relay for O/L, E/F and SC Protection suitable for above. f). Master trip relay -2 no’s. g). Indicator type Annunciator panel with buzzer. h). Digital Volt Meter- 0-11 KV. i). Digital Amp Meter- 0-100 Amp. j). RYB/ Trip/Closing/Spring charged indicator lamp. k). Fault Annunciator panel for O/L, WTI, OTI and Buchhloz Relay Alarm And Trip Auxiliary relay. l). TNC Switch for Operation. m). Multifunction Meter EM6400NG. n). TCS Relay for Safe (At Raw Water pumping station) Job Excess(+) Full Conversion INR
1.3 NON CLOG SEWAGE PUMP: Supplying, erection, testing and commissioning of Submersible motor pumping set non clog for sewerage having head below mentioned as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked. ` 5100 LPM x 25.00 M Head (For IPS-1) Nos. Excess(+) Full Conversion INR
1.4 NON CLOG SEWAGE PUMP: Supplying, erection, testing and commissioning of Submersible motor pumping set non clog for sewerage having head below mentioned as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked. ` 1700 LPM x 25.00 M Head (For IPS-1) Nos. Excess(+) Full Conversion INR
1.5 NON CLOG SEWAGE PUMP: Supplying, erection, testing and commissioning of Submersible motor pumping set non clog for sewerage having head below mentioned as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked. `850 LPM x 25.00 M Head (For IPS-1) Nos. Excess(+) Full Conversion INR
1.6 Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 5100 LPM 25 Mtr. Head Compatible to work with cable length of 100 meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For IPS-1) Nos. Excess(+) Full Conversion INR
1.7 Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 1700 LPM 25 Mtr. Head Compatible to work with cable length of 100 meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For IPS-1) Nos. Excess(+) Full Conversion INR
1.8 Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 850 LPM 25 Mtr. Head Compatible to work with cable length of 100 meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For IPS-1) Nos. Excess(+) Full Conversion INR
1.9 COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. (70 Sqmm size) Metre Excess(+) Full Conversion INR
2.1 COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. (25 Sqmm size) Metre Excess(+) Full Conversion INR
2.2 COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. (16 Sqmm size) Metre Excess(+) Full Conversion INR
2.3 HT. ALLUMINIUM CABLE: Supply erection testing of standard make XLPE 3 core HT / 11 KV grade ISI marked Stranded compact circular aluminium conductor, conductor screen with extruded semi conducting compound, XLPE insulated, insulation screening with extruded semi conducting compound in combination with copper tape, cores laid up, innersheath of PVC, galvanised steel flat strip armoured, and overall PVC sheathed cable conforming to is 7098 (part-2) 2011 with up to date amendments for making following connection a) from G.O switch to metering equipment . b) from metering equipment to transformer complete in all respect. (35 Sqmm size) Metre Excess(+) Full Conversion INR
2.4 LT CABLE ALLUMINIUM: Supply, erection, testing and commissioning of IS marked 3.5 core Cables, Solid Aluminum conductor up to 10sqmm and balance stranded conductor, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Aluminium wire for single core up to 70sqmm and balance Aluminium strip, Glavanised wire for cables up to2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip) extruded PVC type ST2 Outer sheathed, 650/1100V grade as per IS7098 (Part-1) 1988 with up to date amendments along with all accessories complete in all respect. (95 Sqmm size) Metre Excess(+) Full Conversion INR
Total in Figures
Quoted Rate in Figures Select
Select, At Par, Excess (+), Less (-) IOCL
Tender Inviting Authority: EE PHED-2 Hisar
DNIT Name :UKLANA TOWN: DPR FOR STRENGTHENING OF EXISTING SEWERAGE SCHEME BY PROVIDING IPS and LAYING THE BALANCE SEWER LINES AT UKLANA TOWN DISTRICT HISAR. “Construction of IPS comprising collecting tank, pump chamber, boundary wall, Rising main lines, D.G set, electric transformer and pumping machinery. Laying the sewer lines and construction of manholes etc. and all other works contingent thereto`.
Contract No: 01662-246249
Name of the Bidder/ Bidding Firm / Company :
Sl. No. Item Description Item Code / Make Quantity Units Estimated Rate in Rs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category
1 Item Description BI01010001010000000000000515BI0100001112
1.01 HSR Items for DNIT Name : UKLANA TOWN: DPR FOR STRENGTHENING OF EXISTING SEWERAGE SCHEME BY PROVIDING IPS and LAYING THE BALANCE SEWER LINES AT UKLANA TOWN DISTRICT HISAR. “Construction of IPS comprising collecting tank, pump chamber, boundary wall, Rising main lines, D.G set, electric transformer and pumping machinery. Laying the sewer lines and construction of manholes etc. and all other works contingent thereto`. BI01010001010000000000000515BI0100001113 Nos 120247200 Excess(+) Full Conversion INR
Total in Figures
Quoted Rate in Figures Select
Please Enable Macros to View BoQ information
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.95 MB
BOQ_580919.xls
BOQ • 0.26 MB
777957Z149563.pdf
Additional Documents • 1.22 MB
Download all tender documents and submit your bid