Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹89.9 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹94.5 L+₹2.2 L (2.43%)Rejected-AOC NO 205 KAMMAN DHARWAJA STREET BHARATHI SALAI TRIPLICANE CHENNAI 600 005 | L2 | Rejected-AOC Rejected | |
| 3 | Rejected-Technical NO 18 S7 THIYAGARAYA STREET NORTH USMAN ROAD T NAGAR CHENNAI 600 017 | CHENNAI | CHENNAI | TAMIL NADU | 600017 | - | Rejected-Technical Not uploaded relevant document |
Tender Value
₹90 L
EMD Value
₹55,000
Closing Date
26 Dec 2024, 3:00 pmClosed
Chief Engineer
Office of Chief Engineer, Sardar Patel Road, Dote Campus, Chennai 25
Providing EI, AC, UPS, CCTV, LAN cable and Generator to PF COE Workshop in Central Polytechnic College, Korkai, Thiruvarur
2024_HE_509855_1
KorkaiEle_2024
Open Tender
Electrical Works
Lump-sum
150 days
Korkai
Please refer Tender documents.
7 documents required · 7 mandatory
₹0
₹55,000
Yes
30 Apr 2025
11 Dec 2024
27 Dec 2024
11 Dec 2024
26 Dec 2024
11 Dec 2024
Amount
Wiring with 2 x1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable MS pipe on I beam or grider beam support and remaining wall portion in suitable MS pipe concealed in wall with MS accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate with continuous earth wire connection of 1.5 sq.mm copper wire with painting of Suitable colour for PVC Light point / fan point (for electronic regulator) ( 4 points / Coil) Higher End etc., complete complying with standard specification and as directed by the departmental officers.
Wiring with 2 x1.5 sq.mm PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate with continuous earth wire connection of 1.5 sqmm copper wire and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (5 points / Coil) Higher End ) etc., complete complying with standard specification and as directed by the departmental officers.
Wiring with 2 x1.5 sq.mm PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe on wall and ceiling and switch drop portion PVC rigid piple concealed in wall with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate with continuous earth wire connection of 1.5 sqmm copper wire and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (5 points / Coil) Higher End ) etc., complete complying with standard specification and as directed by the departmental officers.
Wiring with 2 x1.5 sq.mm PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate with continuous earth wire connection of 1.5 sqmm copper wire and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (6 points / Coil) Higher End etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of 24W LED 2x2 square type Recessed fitting with LED (Higher end) on false Ceiling with suitable hanging support from ceiling with PVC unsheathed copper leads from terminals to the fitting etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of 18W LED square type Recessed fitting with LED (Higher end) on false Ceiling with suitable hanging support from ceiling with PVC unsheathed copper leads from terminals to the fitting etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of single box type 4 feet 20W LED fitting complete with 20W LED tube light with TW round blocks on wall or ceiling with PVC unsheathed copper leads from terminals to the fitting with necessary connections. (Higher end) etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of 100W High bay LED IP66 with suitable special type of MS clamps with PVC unsheathed copper leads from terminals to the fittings. (Higher end) etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of 48W LED street light fitting with LED (Higher end) with 32mm dia. GI pipe (class B) with 1 no.32 mm GI bend complete on the existing post/ on wall with VC unsheathed copper leads with MS clamps and with painting etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of WT bulk head fitting with guard (Higher end) suitable for 7W/9W LED Bulb etc., complete complying with standard specification and as directed by the departmental officers.
supply and fixing of 1200mm (48") sweep AC ceiling fan High speed complete with 2 module 100W fan step regulator (Higher end) with 300 mm down rod with fan clamp. etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of 300 mm (12") sweep (light duty) AC exhaust fan complete with necessary wall opening and making good of the wall. etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of louvers shuters arrangements for 300mm (12") sweep (light duty) AC exhasut fan. etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of 450 mm (18") sweep (Heavy duty) AC exhaust fan complete with necessary wall opening and making good of the wall. etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of louvers shuters arrangements for 450mm (18") sweep exhaust fan. etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of 400 mm Oscillating type wall mounting fan with regulator complete on wall with connection complete. (Higher end) etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of 1 no. 6A two module 5 pin socket, 1 no. 6A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. (Higher End ) etc., complete complying with standard specification and as directed by the departmental officers..
Supply and run of 2 of 1.5 sqmm PVC insulated SC unsheathed FRLS copper conductor of 1100V Grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 1.5 sqmm copper wire and making good of the concealed portion with suitable colour. (For 6A Plug-28Nos.400mm wall fan) etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of 450 mm Oscillating type wall fan with suitable bolts and nuts with regular complete with connection. (Higher end) etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of 1No 6A/16A 2module socket (higher end) concealed in suitable MS modular (GI) Box covered with modular white cover plate in flush with wall with earth connection etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of 1No 16A flush type control switch (higher end) concealed in suitable MS modular GI Box covered with modular white cover plate in flush with wall with earth connection etc., complete complying with standard specification and as directed by the departmental officers.
Supply and run of 2 of 2.5 sqmm PVC insulated SC unsheathed FRLS copper conductor of 1100V Grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 2.5 sqmm PVC insulated sc unsheathed copper wire and making good of the concealed portion with suitable colour. (For 450 wall mounting fan-16A plug & socket-16Nos. 2Nos.6A & 1No.16A Plug-FF) etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of 2 Nos. 6/16A two module socket, 2Nos 16A module switch on suitable module surface mounting Box (GI) with module cover plate (plastic) on wall with connections. (Higher end) etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of 25 Amps flush type wall Socket with 25A DP MCB in flush with wall with earth connection (For AC Plug) [Higher end make].etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of 10A DP MCB in sheet steel enclosure in flush with wall and making good of the concealed portion with earth connection. (Higher end) etc., complete complying with standard specification and as directed by the departmental officers. (For Machines-1No., Street light control-2Nos.))
Supply and fixing of 8 way single pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no.32A DP MCB switch as incoming and 6 Nos 6A to 32A SP MCB as outgoing on suitable angle iron frame on wall with earth connection only. Higher End (SD-511) 8w SPN MCB DB-4Nos.(Lt.pts.) 8w SPN MCB DB-1No.(bay fitting) 8w SPN MCB DB-1No.(wall fan) etc., complete complying with standard specification and as directed by the departmental officers.
Supply and run of 2 of 4 sqmm PVC insulated SC unsheathed FRLS copper conductor of 1100V Grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 4 sqmm PVC insulated sc unsheathed copper wire and making good of the concealed portion with suitable colour etc., complete complying with standard specification and as directed by the departmental officers. (For 2Nos.6A & 1No.16A plugs-GF, AC Plug, 10A DP enclosure-1 & 8w SPN-6)
Supply and fixing of 12 way single pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no.40A DP MCB switch as incoming and 10 Nos 6A to 32A SP MCB as outgoing on suitable angle iron frame on wall with earth connection only. Higher End etc., complete complying with standard specification and as directed by the departmental officers. (For UPS Line Distribution)
Supply and fixing of 16A 200/250V 2P+E surface mounting sockets (industrial type) on wall with earth connection. (Higher end) etc., complete complying with standard specification and as directed by the departmental officers. (For EV charging)
Supply and run of 2 of 6 sqmm PVC insulated SC unsheathed FRLS copper conductor of 1100V Grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 6 sqmm PVC insulated sc unsheathed copper wire and making good of the concealed portion with suitable colour. etc., complete complying with standard specification and as directed by the departmental officers. (For UPS-12W 40A SPN DB-5Nos. & 16A Industrial plug-2Nos.)
Supply and fixing of 32A 380/415V 3P+N+E surface mounting sockets (industrial type) on wall with earth connection.(Higher end) etc., complete complying with standard specification and as directed by the departmental officers. (For Machines)
Supply and fixing of 32A FP MCB in sheet steel enclosure in flush with wall and making good of the concealed portion with earth connection. (Higher end) etc., complete complying with standard specification and as directed by the departmental officers. (For Machines)
Supply and run of 4 of 6 sqmm PVC insulated SC unsheathed FRLS copper conductor of 1100V Grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 6 sqmm PVC insulated sc unsheathed copper wire and making good of the concealed portion with suitable colour. etc., complete complying with standard specification and as directed by the departmental officers. (For 32A Industril plug-6Nos. & 32A FP MCB-16Nos.)
Supply and fixing of 63A FP MCB in sheet steel enclosure in flush with wall and making good of the concealed portion with earth connection. (Higher end) etc., complete complying with standard specification and as directed by the departmental officers. (For Machines)
Supply and fixing of 7 segment 4 way TPN MCB sheet steel distribution board (Higher end) with metal /acrylic door cover flush type /surface type fitted with busbars and neutral links with single / Three phase MCB outgoings and seperate 4 way provision for accomodating one no 4 pole incoming MCB / Isolator and another seperate 4 way provision for accomodating one no. 4 pole ELCB / RCD (totally 8 ways in one segment) (3x 4 ways in each segment) and seperate provision for MCB / Isolators (totally 12 nos) for sub incomers in 3 segments with lable holder and provison for taking up cable for size not less than 35 sq mm with the following in flush with wall with earth connection only.i) 63A 4P MCB - 1 no. ii) 63A 4P 30MA RCCB/ELCB - 1 no. iii) 63A DP MCB Isolator -3 nos. iv) 6A to 32A SP MCB - 12 nos. etc., complete complying with standard specification and as directed by the departmental officers. (Lighting DB's distribution-5Nos.)
Supply and run of 4 of 10 sqmm PVC insulated SC unsheathed FRLS copper conductor of 1100V Grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 10 sqmm PVC insulated sc unsheathed copper wire and making good of the concealed portion with suitable colour. etc., complete complying with standard specification and as directed by the departmental officers. (For 63A FP MCB-5Nos. 4w 7S DB-5Nos. (Lighting)
Supply and fixing of 7 segment 6 way TPN MCB sheet steel distribution board (Higher end) with metal / acrylic door cover flush type /surface type fitted with busbars and neutral links with single / three phase MCB outgoings and seperate 4 way provision for accomodating one no. 4 pole incoming MCB / Isolator and another seperate 4 way provision for accomodating one no. 4 pole ELCB / RCD (totally 8 ways in one segment) (3x 6 ways in each segment) and seperate provision for MCB / Isolators ( totally 18 nos.) for sub incomers in 3 segments with lable holder and provison for taking up cable for size not less than 35 sq.mm. with the following in flush with wall with earth connection only. i) 63A 4P MCB - 1 no. ii) 63A 4P 30MA RCCB/ELCB - 1 no. iii) 63A DP MCB Isolator -3 nos. iv) 6A to 32A SP MCB - 12 nos. etc., complete complying with standard specification and as directed by the departmental officers. (2Nos.6 & 1No.16A Power Plug Distribution)
Supply and run of 4 of 16 sqmm PVC insulated SC unsheathed FRLS copper conductor of 1100V Grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 16 sqmm PVC insulated sc unsheathed copper wire and making good of the concealed portion with suitable colour. etc., complete complying with standard specification and as directed by the departmental officers. (6w 7Seg.DB-5Nos.)
Supply and fixing of 8 way Vertical type Triple pole neutral MCCB sheet steel enclosure distribution board ( with MCCB incomer) with double door (metal door) with 1No.125A 4 pole MCCB switch as incoming and 4 Nos 63 A TP MCB and 4 Nos 32 A TP MCB as outgoing on suitable angle iron frame work with MS cable entry boxes with earth connection. (Higher end) etc., complete complying with standard specification and as directed by the departmental officers. (for 32A TP MCB & 63A FP MCB power Distribution)
Supply and laying of 3 1/2 x 70 sq.mm PVC armoured LTUG cable in a trench to be excavated at a depth of 0.75 metre and laying the cable through 90mm / 76mm dia HDPE Pipe and refilling the earth to make good. etc., complete complying with standard specification and as directed by the departmental officers. (For 8w 125A MCCB DB-6Nos.)
Supply and clamping of 3 1/2 x 70 sq.mm PVC LTUG armoured LTUG cable on post or on wall with MS Clamps. etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of brass cable gland for 3 1/2 x 70 sqmm PVC armoured LTUG cable with earth connection. etc., complete complying with standard specification and as directed by the departmental officers.
Supply and providing cable end termination of 3 1/2 x 70 sqmm PVC LTUG Aluminium armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection complete etc., complete complying with standard specification and as directed by the departmental officers.)
Supply and Erection of 250A capacity Dust and Vermin Proof Cubical Panel Board made up of 16 SWG CRCA steel with supply and fixing of the following interior mounting fuse switches with HRC fuses arranged in two Horizontal rows with one switch over the other with a central bus bar chamber and two nos of cable chambers and confirming to IE rules. (1) 250A FP switch disconnector fuse units interior only with HRC fuses double break - 1 Nos. (Higher end make) (2) 125A TPN switch disconnector fuse units interior only with HRC fuses double break-7 nos (Higher end make) (3) 63A TPN switch disconnector fuse units interior only with HRC fuses double break - 4 nos. (Higher end make) The bus bar chamber will consist of suitable size of tinned copper flat for phase and neutral buses on epoxy moulded bus insulated at proper and sufficient spacing between the buses as per IE Rules. This bus bar chamber should be segregated from the adjacent chamber by providing hylem sheet of suitable thickness as partisans. 2 Nos 25x3mm tinned copper flats should be provided all round the panel for earth bus.
Earthing as per the ISI specification with an earth electrode of 2.1mt class 'B' GI pipe of dia not less than 40mm, with copper earth plate of size 125mm x 50mm x 6mm, with necessary funneling arrangements with necessary masonry work and with 38mm RCC cover slab for the brick masonry. etc., complete complying with standard specification and as directed by the departmental officers.
Supply and run of 25mm x 3mm tinned copper flat with necessary clamps / supports on wall / floor / ground for earth connection. etc., complete complying with standard specification and as directed by the departmental officers.
Supply and Run of 1 of No.8 SWG copper wire for earth connection etc., complete complying with standard specification and as directed by the departmental officers.
Supply and run of 1" x 1/8" copper flat of 30cm length on suitable bus insulators with necessary bolt and nuts. (Earth Bus) etc., complete complying with standard specification and as directed by the departmental officers.
Supply, Installation, Testing and commissioning of 30 KVA Online UPS system 3 phase input and Three phase output and as per the detailed specification enclosed, Sealed Maintenance free batteries 100AH -32Nos to support 30 KVA for 2 hrs backup complete with intercell connectors & copper cables, battery stand made out of powder coated MS Angles with adequate support to carry the load of the batteries. The vendor shall submit dimensional GA drawing of complete UPS/ Inverter system battery rack with batteries, Service panel and battery bank calculation. etc., complete complying with standard specification and as directed by the departmental officers.
Supply and installation of 4 Megapixel resolution Infrared Network Bullet Camera with IR Range upto 30 meters,120dB WDR,Video Compression in H.264/MJPEG format, Day & Night auto switch IR cut filter, IP67 Protection level with mounting Bracket included (Make and Model: Hikvision/ Dahua/ Equivalent) etc., complete complying with standard specification and as directed by the departmental officers.
Supply and installation 16 channel Network Video Recorder with 2 Nos Hard disc supports up to 8 Megapixels resolution recording, It supports various VCA detection alarm and VCA search H.265 /H.264/ MPEG4 video formats. (Make: Hikvision / Dahua /equivalent).etc., complete complying with standard specification and as directed by the departmental officers.
Supply and installation of 8 port PoE switch (higher end) provides advanced PoE technology and supports extend mode with long-range access up to 250 m. Make :Dlink or equivalent etc., complete complying with standard specification and as directed by the departmental officers.
Supply and installation 8Tb Surveillance Internal Hard Disk Drive for NVR (higher end) with 30 days recording backup which supports SATA 6 Gb/s interface and 64 MB cache optimized with All Frame Technology Make : WD/Seagate / Toshiba /equivalent etc., complete complying with standard specification and as directed by the departmental officers.
Supply and laying of UTP Cat 6 cable through 25mm PVC rigid pipe concealed in the wall/ceiling with necessary connection and making good of the concealed portion with painting of suitable colour Make : Finolex or Dlink or equivalent etc., complete complying with standard specification and as directed by the departmental officers.
Supply and installation of 24 port Gigabyte semi-managed 10/100/1000 Mbps switch (higher end) with 24 port jack panel and necessary accessories. (Make: Netgear or Cisco or HP or equivalent) etc., complete complying with standard specification and as directed by the departmental officers.
Supply and installation of 16port Gigabyte semi-managed 10/100/1000 Mbps switch (higher end) with 24 port jack panel and necessary accessories. (Make: Netgear or Cisco or HP or equivalent) etc., complete complying with standard specification and as directed by the departmental officers.
Supply, Installation and termination of RJ 45 Cat-6 I/O Socket with, Back box, Face plate with surface mount. (Make:D link/Legrand/ Equivalent) etc., complete complying with standard specification and as directed by the departmental officers.
Supply, fixing and termination of Cat 6 UTP Patch cord (higher end) of 2 metre.Make:D link or ADC or Molex or Digilink or equivalent.etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of Media converter optical fibre cable single mode. (higher end) etc., complete complying with standard specification and as directed by the departmental officers.
Supply and installation 19" 9U three tier MS Rack for housing LAN Switches with top and Bottom Cable Entry provision along with necessary power distribution unit,cable manager, fan and Lockable Toughened Glass Door. etc., complete complying with standard specification and as directed by the departmental officers.
Supply and run of Power cable in suitable PVC rigid pipe on wall and ceiling with painting of suitable colour with necessary electrical accessories. Make:Finolex or Orient or Polycab. etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of 50” LED Colour 4K Smart UHD Television Set with IPS display with 2 HDMI Port, 1 VGA Port, 2 USB Port. Make Samsung AU770 Crystal 4K UHD Smart TV/equivalent suitable to view CCTV Cameras. etc., complete complying with standard specification and as directed by the departmental officers.
Supply and run of 20 Meters HDMI Cable. (Make:Liberty/ Eq.) etc., complete complying with standard specification and as directed by the departmental officers.
Supply of 1No 58.5KVA Diesel generator set of 0.8PF, 3phase, 415/ 420Volts, 50Hz, 1500 RPM with standard control panel complete in all respects as detailed below. A) ENGINE : Water cooled diesel engine suitable for generator application with a shaft out put of 154 BHP suitable at 1500 RPM under NTP conditions . The engine shall comprise the following standard scope of supply: (Make : Kirloskar/Ashok Leyland ) 1) Dry type Air cleaner 2) Expansion bellow 3) Radiator, radiator fan and mounting 4) Air to air charge cooler 5) Exhaust gas turbo charger 6) Lube oil cooler and lube oil filter 7) Fuel filter (pre and micro) 8) In-line mono-block fuel injection pump with governor and fuel feed pump 9) Electronic governor 10) 12V / 24V battery charging alternator 11) 12V / 24V Volt electric starter motor 12) Engine test certificate 13) Residential Mufler 14) Fly wheel with starter ring. Engine instrument panel/mounting: Engine control panel consisting of ON/OFF/START/KEY, lube oil pressure gauge, oil temperature gauge, high water temperature gauge and electronic hour meter and RPM indicator.
Safety system of Engine: The engines shall trip for the following conditions with Visual alarm device. 1) Low lubricating oil pressure 2) High water temperature 3) Vee - belt failure and over speed 4) Low battery indication. The Engine should be capable of providing 10% over load for one hour for every 11 hours continuous running at full load. B) ALTERNATOR : 58.5KVA/46.8KW capacity of Brushless Alternator AC 3phase, 50HZ, 415/420Volts, 0.8P.F, 4 wire self exited,self regulated designto run at 1500 RPM under NTP conditions confirming to IS 13364 (part-II) 1992 to be coupled directly to the Diesel engine and test certificate (Make : Kirloskar/Green/ Crompton/Ashok Leyland) C) STANDARD CONTROL PANEL: The control panel (cubical) should be vermin and dust proof and fabricated with 16 SWG CRCA sheet metal and floor mounted with suitable hinged doors, enamel painted & incorporating the following.
1Set of audio and visual indications arrangement for: i) Low lubrication oil pressure ii) Over speed iii) High water temperature 1no Isolator to isolate the neutral 1no “set on” indicating lamp and 1no “load on” indicating lamp 1no Earth fault relay Note: the engine shall trip for the following conditions 1) Low lubrication oil pressure 2) Over speed 3) High water temperature D) ACOUSTIC ENCLOSURE : Acoustic enclosure shall be powder coated and fabricated of 16SWG CRCA MS sheet. The silent canopy shall be nut bolt type construction. Critical processes of punching are done on CNC machine to maintain dimensional accuracy of hole within 0.1mm power coating done after seven-tank surface preparation process of sheet metal. Canopy panel and door shall have inside lining of FIRE-RETARDANT 64kg/m density mineral wool of 100mm thickness as acoustic material. Four hinged doors shall be provided to canopy.
The maximum permissble sound pressue level should be as per the norms prescribed by the Central Pollution Control Board / State Pollution Control Board/ Competent Authority concerened or shouble be 75 db(A) at 1 meter from the enclosure surface whichever is advantageous to the department. The emergency stop should be available on the enclosure panel. The enclosure provided shall be duly approved by the Engine Manufacturer of the Engine provided for Diesel Generator Sets mounted inside and should be to the satisfaction of inspection / testing authority concerned. SURFACE TREATMENT – PAINTING : The enclosure shall be suitably treated for degreasing, de-rusting and phospating. The canopies are passed through seven-tank treatment thoroughly. ADDITIONAL FEATURES OF CANOPIES : Canopy fabricated on CNC machines with dimensional accuracy of 0.1mm so as to increase its durability. Special designed supporting rips/structures are used in canopies so as to give sturdiness and to reduce the vibrations of the DG sets if any. WORLD CLASS COOLING PACKAGE: Canopies shall have cooling package for which it can perform at 45 deg c/ambient temperature. No grounding required on the ground, only a level surface capable of with standing the DG weight. Lifting hooks shall be provided for the acoustic enclosure, which should be unloaded independently of the DG set. The Gen set frame shall also be provided with hooks for unloading.
Temperature rise inside the canopy: Canopies shall be designed so as to maintain the temperature difference between ambient and air inlet at cleaner within the enclosure well with in 5-7 deg centigrade. D) Base Frame Base frame should be fabricated in sheet metal. The base frame is rugged in construction and designed for mounting engine and brush less alternator closely coupled, with cross members mounted on AVM. The base frame shall have provision for mounting of acoustic enclosure on it. The supply of Gen set includes loading, unloading and transportation charges. E) Fuel Tank 150 Ltrs. Removable Fuel tank shall be fabricated out of 14 SWG CRCA MS sheet and is part of base frame. It is duly painted and fitted with inlet an outlet connections and mechanical fuel gauge. Fuel tank can be easily removed for cleaning or any maintenance. F) Battery 2Nos 12V 88AH battery (Kirloskar/Ashok Leyland) G) Supply of manuals for operation & maintenance of DG set with warranty card etc. etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of 200 A Three phase 500V 4 Pole Change over Switch on suitable angle iron frame work with MS cable entry boxes with earth connection only. etc., complete complying with standard specification and as directed by the departmental officers.
Supply and Laying of 3 1/2 x 95 sq.mm. PVC armoured LTUG cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75 metre and refilling the earth to make good. etc., complete complying with standard specification and as directed by the departmental officers. (For Gen.set)
Supply and clamping of of 3½ X 95 sq.mm PVC LTUG armoured cable on post or on wall with MS clamps.etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of brass cable gland for 3-1/2 x 95 sq.mm. PVC LTUG aluminium armoured cable with earth connection. etc., complete complying with standard specification and as directed by the departmental officers.
Supply and providing cable end termination of 3½ x 95sqmm PVC LTUG Aluminium armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection complete etc., complete complying with standard specification and as directed by the departmental officers.
Supply and installation of exhaust piping of sufficient length with suitable MS pipe so as to extend outside the generator with necessary thermal insulation etc., complete complying with standard specification and as directed by the departmental officers.
supply of lubricating oil to run the genset for minimum of 8 hours by supply of 100 litre diesel. etc., complete complying with standard specification and as directed by the departmental officers.
Supply of tools like such as 15" cutting plier- 1No,Serew driver 9"X6" - 2 Nos,DE spaners ( 6 Nos) - 1set,Adjustable spanner - 1No,1/2 Ip Hammer - 1 No,spanner for removing engine oil plug-1No,Line tester - 1 No and line tester for the maintenance and operation of generator set-1set. etc., complete complying with standard specification and as directed by the departmental officers.
Preparation of site plan, physical layout, electrical line schematic diagram in 10 sets getting drawing approval from CEIG preparation of completion report, rectification report and arranging CEIG inspection and obtaining safety certificate preparation of 1 set of approved drawing and a copy of safety certificate in a neat frame work to be fixed in generator room and payment of CEIG inspection fees. etc., complete complying with standard specification and as directed by the departmental officers.
Supply erection, testing and commissioning of 2.0 TR (6000 K.cal/Hr) ABS Plastic Split type Air conditioner conforming to IS 1391 (Part-2) 1992 with Amdt No. 1 to 2 fitted with rotary compressor operating on refrigerant R-32/non CFC suitable for wall mounting for operation on 230V, 50HZ single phase AC supply with star rating of 3 star as per BEE specification and capable of performing the functions of Cooling Dehumidifying Air Circulating Filtering The installation works for the above split type AC units includes the following. 1.Mounting / Fitting Indoor and outdoor units at their respective locations. 2. Laying refrigerant pipeline of required length connecting not exceeding 3 metre distance and both units after drilling hole/holes in the wall if required. 3. Insulating the suction pipe with expanded polyethylene foam 5mm tubing. 4. Laying 15mm dia flexible PVC drain pipe to throw out the condensate water being formed within the indoor unit. 5. Leakage testing the entire system unit. 6. Charging refrigerant gas in the unit. 7. Suitable electric wiring to be provided with 2.5 Sq mm PVC insulated copper wire between indoor and outdoor units up to 6 Mtrs length and up to switch within 3 Meters of location of indoor unit (Make: Carrier/Voltas/equivalent) etc., complete complying with standard specification and as directed by the departmental officers.
Supply of 5 KVA Electronic Automatic Voltage Stabilizer (Higher end) with Input Voltage range of 170 Volt – 270 Volt and Output Voltage range 200Volts to 240 Volts with High and Low Voltage cut off and 3 minutes time delay relay with demonstration etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of water drain pipe line (1" PVC pipe) etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of MS stand for fixing Outdoor unit.etc., complete complying with standard specification and as directed by the departmental officers.
Supply and laying of 5/8" and 3/8" copper refrigerant pipe of 0.8mm thick with 2.5 sqmm 3 core chord between indoor and outdoor unit. (Extra beyond 3 mts supplied with AC unit) etc., complete complying with standard specification and as directed by the departmental officers.
Supply and Laying of 31/2 x 240 sq.mm. PVC armoured LTUG cable in120mm/103.50mm dia size HDPE pipe in a trench to be excavated at a depth of 0.75 metre and refilling the earth to make good etc., complete complying with standard specification and as directed by the departmental officers. (Existing Work shop panel to 250A Panel)
Supply and clamping of 3½ X 240 sq.mm PVC LTUG armoured cable on post or on wall with MS clamps etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of brass cable gland for 3-1/2 x 240 sq.mm. PVC LTUG aluminium armoured cable with earth connection. etc., complete complying with standard specification and as directed by the departmental officers.
Supply and providing cable end termination of 3½ x 240 sqmm PVC LTUG Aluminium armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection complete etc., complete complying with standard specification and as directed by the departmental officers.
Sub Total
Kanniappa Electricals (BID ID -1218925)
PENTAGREEN (BID ID -1218719)
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .