Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.8 LAccepted-AOC GURUGRAM | GURUGRAM | HARYANA | 122001 | L1 | Accepted-AOC L1 | |
| 2 | L2₹3.0 L+₹19,350 (6.90%)Rejected-Finance NA | NA | NA | 121004 | L2 | Rejected-Finance L2 |
Tender Value
₹3.4 L
EMD Value
₹6,756
Closing Date
18 Jun 2024, 5:00 pmClosed
RAVI Ladwal
ED - Rewari
Providing High Mast Light in the Park of Judicial Officers Colony at Nuh in District Nuh
2024_HRY_374320_1
2024603A1356 62D1 44CE A536 CB9F5CE0DE38668BAR
Open Tender
Civil Works
Works
30 days
Nuh
2 documents required · 2 mandatory
₹500
₹6,756
Yes
9 Jul 2024
7 Jun 2024
19 Jun 2024
7 Jun 2024
18 Jun 2024
7 Jun 2024
Amount
[23.22.1.9]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 1.9. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. 4 pole MCCB 6 amp to 100 amp , 25 KA
[23.22.2.1]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 2.1. MCCB Enclosure made of Sheet Steel suitable for mounting MCCB of following ratings MCCB up to 125 A FP
[23.22.3.3]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 3.3. Supply and erection of sheet steel enclosures 1pole/2 pole/4 pole on wall/on existing pedestal complete as required. TPN enclosure suitable for TP , TPN or FP MCB
[23.22.5.7]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.7. Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:- 6 amp. to 32 amp MCBs FOUR POLE
[23.27.2]Supply and erection of Godrej Almirah typeM.S. pedestal made of 50 mm x 50 mm x 6 mm angle iron frame with 3.00 mm thick M.S. sheet covering including shutters with suitable hinges and locking arrangement with Godrej type handle including round bars . The top covering should have downward overhang of 75 mm on all sides of pedestal , having two sets of water proof ventilation holes of suitable size on the sides , at top and bottom , each set containing four Nos. holes to discharge the heat produced by the current . The shutters fixed with rubber gasket of superior quality and of suitable size to make it water proof . The pedestal duly painted both inside and outside with two coats of approved paint and primary coat and its legs are embeded upto the entire depth in 1:2:4 cement concrete block , projected 75 mm all around the pedestal and and 200 mm above the ground level including the cost of all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-in-charge of the work:- 2. M.S. pedestal of size 750 mm wide , 900 mm high , 300 mm deep and bottom totally open , duly embeded in cement concrete block of size 900 mm x 450 mm x 200 mm above ground level , having a base of size 1050 mm x 600 mm x 250 mm below ground level . 0 0
[24.1.3]EARTHING AND LIGHTENING ARRESTOR 3. Earthing with G.I. earth plate 600 mmx 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) complete as required.
[24.1.5]EARTHING AND LIGHTENING ARRESTOR 5. Extra for charcoal or coke and salt for G.I. plate or copper plate earth electrode.
[24.1.8]EARTHING AND LIGHTENING ARRESTOR 8. Providing and fixing 25 mm x 3mm G.I. strip on surface or in recess for connections etc. as required with all labour and material.
[24.2.8.5]LT CABLE 8.5. Supply and erection of aluminium lugs heavy duty including crimping etc. up to the entire satisfaction of the Engineer-in-charge of the work. 25 sqmm
[24.4.15.2]STREET LIGHT 15.2. B.S.E.N. 10025 High Masts "Supply, installation, testing and commissioning of 16 mtr. long High Mast manufactured from B.S.E.N. 10025 or equivalent grade material in, 2 (two) section hot dip, galvanized inside and outside in single dip, suitable for wind velocity as per IS 875 Part-3 suitable for 9/12 nos. luminaire loading fully motorized (power tool) with starter & cable complete along with standard accessories supplied by the manufacturer with 3 nos. steel wire rope double drum system and twin dome aviation light with LED without foundation but including cost of set of foundation nut and bolts, installation at site complete in all respect upto entire satisfaction of Engineer -in-Charge Thickness of Top and Bottom Section = 3 mm & 4mm (minimum) Top Dia = 150 mm and Bottom Dia = 410mm Thickness of Galvanization - Top = 65 micron (minimum) and Bottom = 85 micron (minimum)"
[24.9.2]RCC FOUNDATIONS FOR HIGH MAST OCTAGONAL POLES 2. Providing RCC foundation of M25 grade (1 Cement:1 Stone aggregate: 2 Coarse sand) i/c excavation, steel reinforcement (Fe 500) @ 75 kg/cum of concrete contents, concrete cover 50mm, anchor bolts etc. over a bed of PCC 1:5:10 of required dimensions for high mast octagonal poles of various heights as per following specifications complete in all respects and as per directions of Engineer-in-charge 16m high mast pole
Supply and erection of 120Watt Flood light on existing pole / High Mast to complete the job in all respect upto the Engineer-in-Charge of the work.
Supply and erection of ard / unard. cables in pipe / existing / closed trench complete the job in all respect upto the Engineer-in-Charge of the work. 25sqmm 4core ard. aluminium
kunwar electricals
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .