Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.0 LAccepted-AOC | ₹5.0 L | L1 | Accepted-AOC Awarded to the 1st lowest bidder. |
| 2 | L2₹5.4 L+₹47,013 (9.48%)Rejected-AOC 22 IIIRD FLOOR MAIN MARKET MOTI NAGAR DELHI DELHI 110015 | WEST DELHI | DELHI | 110015 | ₹5.4 L+₹47,013 (9.48%) | L2 | Rejected-AOC 2nd lowest bidder. |
| 3 | L3₹5.6 L+₹59,994 (12.1%)Rejected-AOC | ₹5.6 L+₹59,994 (12.1%) | L3 | Rejected-AOC 3rd lowest bidder. |
Tender Value
₹6.4 L
EMD Value
₹6,400
Closing Date
10 Aug 2020, 5:00 pmClosed
E.E., Harabhangi Irr. Division, Adava
E.E., Harabhangi Irr. Division, Adava, Gajapati
Procurement of DG Set
2020_CEBMB_62123_1
EE-HID- 04/2020-21
Open Tender
Laboratory Equipment
Item Rate
30 days
Adava
Please refer Tender documents.
2 documents required · 2 mandatory
₹4,000
E.E., Harabhangi Irr. Division, Adava
₹6,400
Yes
29 Sept 2020
31 Jul 2020
11 Aug 2020
31 Jul 2020
10 Aug 2020
31 Jul 2020
31 Jul 2020 - 5 Aug 2020
Supplying, Installing, Testing & Commissioning of 'Silent Type' Diesel Generating set along with having Prime Power Rating of 62.5 KVA,415 volts at 1500RPM, 0.8 lagging power factor at 415 V suitable for 50Hz 3 phase system and for 0.85 load factor consisting of followings : (i) Diesel Engine : Diesel Engine 4 Stroke liquid cooled, electric start of suitable BHP at 1500 RPM suitable for above output of alternator at 47ºC, 50 % RH & at 1000 meter MSL and conforming to BS 5514, BS 649, IS 10000, Capable of taking 10% overloading for 1 hour after 12 hour of continues operation. The engine will be fitted complete with all the required accessories. (ii)Engine mounted Instrument Panel fitted with and having digital display for following: (a) Star- Stop switch with key (b) Water temperature indication (c) Lubrication oil pressure indication (d) Lubrication oil temperature indication (e) Battery charging indication (f) RPM indication (g) Over speed indication (h) Low Lub. Oil trip indication (i) Engine Hours indication (iii) Alternator : Synchronous alternator rated at 62.5 KVA, 415V at 1500RPM,3 phase 50 Hz, AC supply with 0.8 lagging power factor at 47ºC, 50% RH & at 1000 Meter MSL. The alternator shall be having SP DP enclosure, brushless, continuous duty, self exist excited & self- regulated through AVR conforming to IS : 4722/BS 2613 suitable for tropical condition and with class - F/H insulation.
GSP POWER PROJECTS RETAIL DIVISION
FORTUNE IMPEX
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .