| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹46.8 LAccepted-AOC INDEX NO E 29 CWE JRC 352 3 GURU NANAK PURA EAST JALANDHAR CITY PIN 144001 | JALANDHAR CITY | JALANDHAR | PUNJAB | 144001 | L1 | Accepted-AOC L1 | |
| 2 | L2₹49.0 L+₹91,360 (1.90%)Rejected-Finance | L2 | Rejected-Finance Other than lowest. | |
| 3 | L3₹50.9 L+₹2.8 L (5.81%)Rejected-Finance | L3 | Rejected-Finance Other than lowest. |
Tender Value
Refer Docs
EMD Value
₹96,000
Closing Date
7 Nov 2023, 6:00 pmClosed
GE AF Adampur
Military Engineer Services AF Stn Adampur 144103
REPAIR/ REPLACEMENTS TO INTERNAL ELECTRIFICATION and EARTHING IN TECH AREA AT AF STN ADAMPUR
2023_MES_622522_1
GE/AF/ADM-43/2023-24
Open Tender
Miscellaneous Works
Item Rate
180 days
Under GE AF Adampur
Refer NIT and Tender Documents
8 documents required · 8 mandatory
₹500
GE AF Adampur
₹96,000
Yes
27 Dec 2023
10 Oct 2023
8 Nov 2023
17 Oct 2023
7 Nov 2023
25 Oct 2023
11 Oct 2023 - 24 Oct 2023
Amount
INTERNAL ELECTRIFICATION WORKS
Point wiring with multi-stranded copper conductor, single core, FRLSH PVC insulated and unsheathed cable, including FRLSH PVC insulated unsheathed stranded copper conductor single core cable as earth continuity conductor to common earth and connected to earth dolly, with and including GI terminal boxes with 3 mm thick plastic laminated sheet cover having necessary cutting for fixing switches/ sockets comprising the following: -
One light point controlled by one switch or one fan point controlled by one switch & fan regulator etc. or for bell/buzzer with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC medium duty concealed conduit all as specified.
One light point controlled by two no., 2 way switches with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC medium duty concealed conduit all as specified.
One Socket outlet three pin, 6 Amp, on the same board, with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, all as specified.
One Socket outlet three pin, 6 Amp, independent, with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC heavy duty concealed conduit all as specified.
One socket outlet three pin, 6/16 Amp, independent, with 2.5 Sq. mm (nominal area) cable & 2.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC medium duty concealed conduit all as specified.
One socket outlet three pin, 6/16 Amp, independent, with 4 Sq. mm (nominal area) cable & 4 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC medium duty concealed conduit all as specified.
NOTES: (a) Switch(es) & socket(s) shall be measured & paid for separately under respective item of Schedule 'A'. (b) GI boxes shall be fixed flush to walls in position with cement mortar (1:4) complete all as directed. (c) Conduit shall be laid on surface in case of RCC ceiling surfaces.
Switch piano flush button single pole one way, 6 Amp complete all as specified.
Switch piano flush button single pole twe way, 6 Amp complete all as specified.
Switch piano, bell/buzzer push, flush button single pole one way, 6 Amp complete all as specified.
Switch piano flush button single pole one way, 16 Amp complete all as specified.
Socket outlet multipurpose having provision for 2&3 pin, 6 Amp, flush type, complete all as specified.
Socket outlet multipurpose having provision for two-in-one 3 pin 6 Amp & 3 pin 16 Amp, flush type complete, all as specified.
Ceiling rose, surface bakelite, 65 x 50mm, three terminals complete, all as specified.
Lamp (angle) holder, insulated body, cord grip pattern, complete, all as specified.
Electric buzzer AC 230 volt, single pole, Ding Dong type complete, all as specified.
Fan regulator (electronic) suitable for 48”/56” sweep fan, step down type, single phase, complete all as specified.
Sub main wiring (with approved colour coding as per IS) with single core FRLSH PVC insulated flexible stranded copper conductor 1.1 KV grade (main cable: number of runs as indicated below along with single core FRLSH PVC insulated flexible stranded copper conductor 1.1 KV grade for earthing in conduits, complete all as specified for the following: -
2 runs of 2.5 Sq. mm main cable + 1 run of 2.5 Sq. mm earth cable.
2 runs of 4 Sq. mm main cable + 1 run of 4 Sq. mm earth cable. (150 Rm for ordinary & 300 Rm for flame proof wiring)
2 runs of 6 Sq. mm main cable + 1 run of 6 Sq. mm earth cable. (250 Rm for ordinary & 100 Rm for flame proof wiring)
NOTES: (i) Conduit & conduit accessories shall be measured & paid for separately. (ii) For payment purposes, total runs of main cable (each run of one running metre) as mentioned above and one run (one running metre) of earth cable shall be considered together as "1 RUNNING METRE"
Rigid non metallic, PVC concealed conduit, 20 mm bore, medium grade, ISI marked, inclusive of all fitings (such as junction boxes, bends, elbows, tees, reducers, bell mouth tube ends) and all fixing acessories such as couplers, lock nuts, saddles, pipe hook etc. for sub main wiring and the like complete all as specified. (500 Rm for sub main wiring & 200 Rm for earthing)
ERW rigid stove enamelled surface conduit 25 mm bore, ISI marked, inclusive of all fitings and all fixing acessories such as couplers, lock nuts, saddles, pipe hook etc. for flame proof sub main wiring and the like complete all as specified.
Sheet metal enclosure for DB for fixing MCB’s, isolators etc., having IP-43 protection, suitable for surface and flush mounting, complete all as specified comprising the following: -
SPN, 2 way with 200 Amp rated bus bar, 240 V.
SPN, 4 way with 200 Amp rated bus bar, 240 V, double door type.
SPN, 8 way with 200 Amp rated bus bar, 240 V, double door type.
SPN, 12 way with 200 Amp rated bus bar, 240 V, double door type.
TPN, 4 way with 200 Amp rated bus bar, 415 V, double door type
TPN, 4 way with 200 Amp rated bus bar, 415 V, double door type having housing and including MCCB 4 pole 63 Amp, 16kA.
MCB suitable for 240 volt AC supply, SP with over load and short circuit protection and rupturing capacity not less than 10 kA, 'C' curve type of rating 6 to 32 Amp complete all as specified.
MCB suitable for 240 volt AC supply, SPN with over load and short circuit protection and rupturing capacity not less than 10 kA, 'C' curve type of rating 6-32 Amp complete all as specified.
MCB suitable for 415 volt AC supply, TPN with over load and short circuit protection and rupturing capacity not less than 10 kA, 'C' curve type of rating 63 Amp complete all as specified.
Blanking plate to cover unused space in DB's complete all as specified..
Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amp, 240 volt, breaking capacity not less than 10 kA, complete all as specified.
Environment friendly, modern design, energy saving surface mounted, decorative 10 W bulk head LED luminaire with premium quality diffuser for glarefree light, 6000K, including making connections, complete. MAKE: Havells Cat No. HEXAFT10WLED857SSYMBOPC or equivalent in makes mentioned in Appendix 'B' here-in-after.
Surface mounted environment friendly LED 10 W batten with polycarbonate housing & integrated electronic driver, lumen output should not be less than 90 lumens per watt complete. MAKE: Havells Cat No. LUMILINEBS10WLED865SPCWH or equivalent in makes mentioned in Appendix 'B' here-in-after.
Surface and wall mounted decorative ultra slim LED lighting fixture with extruded polycarbonate, eenvironment, energy efficient ready to use pack LED 18 W lighting , 6500K, lumen output should not be less than 90 lumens per watt complete. MAKE: Havells Cat No. LUMILINEPLUSNEOBS18WLED840SPCSSIND or equivalent in makes mentioned in Appendix 'B' here-in-after.
Surface mounted environment friendly with eye soft technology & glarefree diffuser LED 20 W lighting , 6500K, lumen output should not be less than 90 lumens per watt complete. MAKE: Havells Cat No. ENDURALINEARNEOBS20WLED865SPCWH or equivalent in makes mentioned in Appendix 'B' here-in-after.
Energy saving, environment friendly, long life, exclusive innovative die-cast aluminium IP66 flood light, suitable for highlighting architectural facade and general purpose lighting complete. MAKE: Havells Cat No. JETAALBAFLOODLIGHT70W or equivalent in makes mentioned in Appendix 'B' here-in-after.
Recess mounted bottom opening LED 36W cool day light luminaire (2x2) CRCA powder coated housing, IP- 54 protection, suitable for grid ceiling lumen output should not be less than 90 lumens per watt complete. MAKE: Havells Cat No. DROPDOWNFLAT2X2PLR36WLED857 or equivalent in makes mentioned in Appendix 'B' here-in-after.
Flame proof tube LED light fitting 2x 20 watt with & including LED tube 16W each, CMRI certified recommended suitable for gas/vapur of IIA & IIB and Zone 1& 2 having IP-65 protection with die cast aluminium housing with heat resistant toughened glass with driver, holder, connector etc complete suitable for fixation on wall/roof including connecting up with three core suitable size twisted flexible copper conductor with complete. MAKE: Shyaam Switchgear Pvt Ltd. Cat No. SSPL/FF/1271 or equivalent in makes mentioned in Appendix 'B' here-in-after.
LED light fitting 120 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum housing with heat resistant toughened glass, with LED tube light fixtures driver, holders, connector etc. with all accessories prewired and including connecting up with suitable size three core flexible copper conductor complete. MAKE: Shyaam Switchgear Pvt Ltd. Cat No. SSPL/1251 or equivalent in makes mentioned in Appendix 'B' here-in-after.
LED light fitting 100 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum housing with heat resistant toughened glass, with LED tube light fixtures driver, holders, connector etc. with all accessories prewired and including connecting up with suitable size three core flexible copper conductor complete. MAKE: Shyaam Switchgear Pvt Ltd. Cat No. SSPL/1233 or equivalent in makes mentioned in Appendix 'B' here-in-after.
Flame proof point wiring with 1.5 Sqmm nominal area PVC insulated unsheathed multistranded copper conductor cable in and including ERW rigid conduit stove enamelled surface conduit for one light point / Fan point / 6Amp multipurpose switch socket with and including necessary conduit acessories like flame proof junction box(es), bend(s), reducer(s) and unions etc, independent for one light point controlled by one (MCB) including 1.5 Sqmm nominal area PVC insulated unsheathed multistranded copper conductor cable for earth wire to common earth and connected to earth dolly complete all as specified.
Flame proof weather proof rotary switch, single pole on & off with cable termination box in LM6, 16 Amp rating, 250 volt, IN REPLACEMENT, complete. MAKE: Sudhir Cat No. RI/OA/1010-2A or equivalent in makes mentioned in Appendix 'B' here-in-after.
Flame proof weather proof rotary switch-socket and plug combination in LM6, three pin (two pole & earth) with cable termination enclosure box, 16-25 Amp rating, 250 volt, IN REPLACEMENT, complete. MAKE: Shyaam Switchgear Pvt Ltd. Cat No. SSPL/SS/1010 or equivalent in makes mentioned in Appendix 'B' here-in-after.
Collecton of items like ceiling fans, exhaust fans, wall mounted fans, cabin/table fans, flame proof ceiling fans from EM store yard for repair, transporting to workshop, opening and reassembling after including necessary cleaning greasing oiling etc, testing and depositing back to EM store yard of GE (AF) Adampur including necessary loading unloading and transporting etc. complete. NOTE: Supply only spares & rewinding of fan(s) shall be measured & paid for separately under respective items of BoQ.
Rewinding fan of any description with super enamelled copper winding wire of size, gauge & weight as per original specifications providing insulating material and varnishing with synthetic varnish, oiling, greasing including replacement of bush/bearing, condenser, 'U' clamp with reel to the entire satisfaction of Engineer-in-Charge including taking out burnt winding wire after opening the ceiling fan and other unserviceable parts, of size: -
Ceiling fan 1200 mm sweep
Ceiling fan 1400 mm sweep
Exhaust fan 300 mm sweep
Exhaust fan 450 mm sweep
Wall mounted fan 650 mm sweep
Cabin/table fan 450 mm sweep
Flame proof wether proof ceiling fan any sweep & description
Flame proof wether proof exhaust fan any sweep & description
NOTE: Collecton of fan items from EM store yard, transporting to workshop and back including loading unloading shall be measured & paid for separately under respective items of BoQ.
EARTHING & CONNECTED WORKS
Earthing with and including GI earth plate electrode 6 mm thick of size 600 mm x 600 mm with 4 Sq.mm GI wire earthing lead complete all as shown in electrical plate No. 3 and as specified in Particular Specifications clause 19.5.1 of contract, IN REPAIR/REPLACEMENT.
Earthing with and including GI earth plate electrode 6 mm thick of size 600 mm x 600 mm with 25 mm x 4 mm GI strip earthing lead complete all as shown in electrical plate No. 3 and as specified in Particular Specifications clause 19.5.1 of contract, IN REPAIR/REPLACEMENT.
Earthing with and including GI earth plate electrode 6 mm thick of size 600 mm x 600 mm with 32 mm x 6 mm GI strip earthing lead complete all as shown in electrical plate No. 3 and as specified in Particular Specifications clause 19.5.1 of contract, IN REPAIR/REPLACEMET.
NOTES APPLICABLE TO SERIAL ITEM 37 to 39: (a) The unit rate includes earthing lead and protection pipe upto 7.5 metre from top of earth plate. (b) Factory made PCC pit with cover shall be fixed at least 500 mm away from earth pit. (c) Earth resstance shall be less than 3 ohm. In case the test results are not found less than 3 ohm, complete earthing shall be redone by the contractor without any extra cost to Govt.
Earthing with and including copper earth plate electrode 3.15 mm thick of size 600 mm x 600 mm with 20 mm x 3 mm copper earthing strip complete all as shown in electrical plate No. 3 and as specified in Particular Specifications clause 19.5.2 of contract, IN REPAIR/REPLACEMENT. NOTE: (a) The unit rate includes earthing lead and protection pipe upto 7.5 metre from top of earth plate. (b) Factory made PCC pit with cover shall be fixed at least 500 mm away from earth pit. (c) Earth resstance shall be less than 2 ohm. In case the test results are not found less than 3 ohm, complete earthing shall be redone by the contractor without any extra cost to Govt.
Maintenance free chemical pipe-in-pipe earthing electrod as per HEX Cat No. HSPG-503-100 (using hot dip galvanised pipe) or equivalent in TRUEPOWER including necessary excavation & earth work by making bore of 80 mm dia and 3500 mm in depth, all as recommended by manufacturers and connecting to earthing strip with necessary nuts, washers and bolts, IN REPAIR/REPLACEMENT, complete.
Maintenance free chemical pipe-in-pipe earthing electrod as per HEX Cat No. HSPC-503-100 (using copper plated pipe) or equivalent in TRUEPOWER including necessary excavation & earth work by making bore of 80 mm dia and 3500 mm in depth, all as recommended by manufacturers and connecting to earthing strip with necessary nuts, washers and bolts IN REPAIR/REPLACEMENT, complete.
NOTES APPLICABLE TO SERIAL ITEM 41 & 42: (a) Earth resistance should be less than one Ohm. In case the test results are not found below one Ohm, complete earthing shall be redone by contractor without any extra cost to Govt . (b) Pipe earth electrod shall be inserted into the bore and spece around will be filled wth Back Fill Compound TERRAHEX of M/s HEX or equivalent conforming to IEC 62561-7 & RoHs2 standards. (c) Pit & cover shall be of precast PCC of size as per manufacturers recommendation. (d) "Performance Guarantee" as mentioned in PS clause 19.5.5.
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required complete all as specified, IN REPLACEMENT, with & including the following: -
Copper strip of size 20mm x3mm.
GI strip of size 25mm x4mm.
GI strip of size 32mm x6mm.
Aluminium strip of size 25mm x3.15mm.
NOTES: (a) Strips to be fixed with porcelain/polymer insulators at the intervals of 0.6 metre so as not to be in electrical contact with building structure. (b) Brazing shall be done on both sides (overlapping) at all joints except test point.
Earth continuty conductor galvanised iron main earth lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles/DBs or any other directed location, IN REPLACEMENT, complete all as specified, of size: -
4 sq. mm dia.
6 sq. mm dia.
Air termination, single pointed aluminium rod 12 mm dia 300 mm long IN REPLACEMENT, complete all as specified.
Air termination, single pointed copper rod 12 mm dia 300 mm long IN REPLACEMENT, complete all as specified.
Test point terminal block made of gun metal or phosphorus bronze size 75 x 75x 25 mm drilled and screwed including 3 Nos. 8 mm dia 25 mm long hex head screw IN REPLACEMENT, complete all as specified.
Salt (quantity recommended by Engineer-in-Charge) pouring into earth pit thrugh watering pipe by mixing the same with water to maintain earth resistance value of earthing within permissible limit complete.
Charcoal/coke powder (quantity recommended by Engineer-in-Charge) pouring into earth pit through watering pipe by mixing the same with water to maintain earth resistance value of earthing within permissible limit complete.
Magnesium sulphate chemical (quantity recommended by Engineer-in-Charge) pouring into earth pit thrugh watering pipe by mixing the same with water to maintain earth resistance value of earthing within permissible limit complete.
Brazing/soldering on both sides (overlapping) to the metal strip of any size provided as earthing lead including dismanting the old from the existing position/ equipment without disturbing the functional requirement and reconnecting complete .
Reinforced cement concrete, type A-1 (1:1½:3), using 20 mm graded stone aggregates as in precast earth pit & cover 100 mm thick of inner size 300 mm x 300mm & depth not less than 450mm reinforced with XPM weighing not less than 4 kg/Sq.m and fixed on directed location IN REPLACEMENT of existing broken cover complete all as specified.
Medium grade GI tubes, with necessary GI fittings laid in floors / wall complete all as specified, IN REPLACEMENT, of size -
20 mm bore
25 mm bore
40 mm bore
Cast iron funnel of size 25mm dia for earthing, fixed IN REPLACEMENT, complete.
GI light grade 25 mm bore tube, ISI marked, cut to piece of 1.00 metre length, fixed verticall from bottom in & including PCC(1:2:4) type B-1 block of size 200 mm x 200 mm x 150 mm including necessary form work, fixed to air termination rod with necessary bolts, nuts as required, complete all as specified.
GI light grade 40 mm bore tube, ISI marked, cut to piece of 1.00 metre length, fixed verticall from bottom in & including PCC(1:2:4) type B-1 block of size 200 mm x 200 mm x 150 mm including necessary form work, fixed to air termination rod with necessary bolts, nuts as required, complete all as specified.
GI light grade 50 mm bore tube, ISI marked, cut to piece of 1.00 metre length, fixed verticall from bottom in & including PCC(1:2:4) type B-1 block of size 200 mm x 200 mm x 150 mm including necessary form work, fixed to air termination rod with necessary bolts, nuts as required, complete all as specified.
DISMANTLING/DEMOLITION WORKS
Taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete with batten, casing caping of MS or and PVC conduit on surface or concealed, including switches, ceiling roses, pendants, regulators, sockets, mild steel terminal boxes etc., removing materials and making good disturbed surfaces due to taking down etc. to the entire satisfaction of Engineer-In-Charge, complete all as specified.
Taking down carefully copper/aluminium sub main wiring complete, including existing batten/conduit consealed/surface etc., removing materials and making good disturbed surfaces due to taking down etc. to the entire satisfaction of Engineer-In-Charge, complete all as specified.
Dismantling of unservisible existing DBs of any description with all accessories and MCBs, isolators etc. and making good surface as per existing, complete all as specified.
Taking down carefully light fitting of any description, complete all as specified.
Building Block Constructions
Bains Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .