CHIEF ENGINEER/MTPS-I
CHIEF ENGINEER/MTPS-I
MTPS-I ES Circle EMI Complete Cleaning, tightness checking and checking IR value of 6.6KV HT bus 2A 2B and its Bus ducts and and Annual maintenance works to be carried out in respect of critical LT modules LT breakers in USSG2A 2B, SSSG-2 NE2 BMCC2
2026_EB_699795_1
CE-MTPSI-SE-ES-EMI-OT17-26-27
Open Tender
Electrical Works
Works
20 days
MTPS-I/METTURDAM
As per tender specification
4 documents required · 4 mandatory
₹0
₹2,100
Yes
31 Aug 2026
31 Aug 2026
16 Sept 2026
31 Aug 2026
15 Sept 2026
31 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Charges for releasing the back doors (top and bottom),Bus separator, racking out of all 18 Nos.HT Breakers and cleaning of all the released doors and checking of IR value of Bus for 1 No. panel. | 39 | Nos | - | - |
| 2 | Charges for complete cleaning of Horizontal, vertical bus bars and supporting insulators with the help of air blower and Acetone/IPA, tightness checking of Horizontal, vertical bus bars and outgoing power cable terminals for 1 No. panel. | 39 | Nos | - | - |
| 3 | Charges for cleaning and lubricating of all moving parts of HT Breakers, upper and lower pole arms, vacuum bottles with Acetone/IPA. All bolts and nuts tightness checking, checking healthiness of Interrupters, closing/Tripping operations mechanically and checking of IR value for 1 No. breaker. | 35 | Nos | - | - |
| 4 | Charges for refixing of back doors(top and bottom) by providing all bolts and nuts racking in all HT breakers and checking of IR value and satisfactory commissioning for 1 No. panel. | 39 | Nos | - | - |
| 5 | Charges for releasing all inspection covers of Bus-ducts- 2 nos (I/c bus duct &Tie bus duct) checking of Initial IR value, thorough cleaning by applying Acetone/IPA and checking healthiness of supporting insulators & tightness checking of bus bar joints and checking of Healthiness of Rubber bellows for the incomer & tie bus ducts of one bus. | 2 | Nos | - | - |
| 6 | Charges for checking final IR value of Bus-bars, re-fixing of inspection covers and satisfactory commissioning & checking of Top cover gaskets, rubber bellows and replacement if necessary. | 2 | Nos | - | - |
| 7 | Charges for complete O/H of LT Bus (Critical Modules only). Releasing and cleaning of critical modules, healthiness checking of power Contactor tips and replacing if necessary and terminal tightness of all components and re fixing the modules in the respective panels. Checking of cable tightness at module end and motor end, replacing of lugs if necessary. | 33 | Nos | - | - |
| 8 | Charges for opening of all modules, complete cleaning of modules by air blowing and closing the modules for 1 no. LT bus. | 9 | Nos | - | - |
| 9 | Charges for releasing, checking and cleaning of finger contacts in breaker with acetone, healthiness of spring charging motors and mechanism, tightness checking of all components of breakers and lubrication of all moving parts and checking their operations and re-fixing the breakers. Opening of breaker panel back doors, checking cable tightness, cleaning and re-fixing etc. | 16 | Nos | - | - |
| 10 | Acetone | 11 | Litres | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.78 MB
BOQ_841215.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].