Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.9 CrAdmitted-Finance JHARIA BENIGANJ HARDOI | BENIGANJ | HARDOI | UTTAR PRADESH | ₹1.9 Cr | L1 | Admitted-Finance |
| 2 | L2₹2.0 Cr+₹16.4 L (8.77%)Admitted-Finance | ₹2.0 Cr+₹16.4 L (8.77%) | L2 | Admitted-Finance |
| 3 | L3₹2.1 Cr+₹24.3 L (13.0%)Admitted-Finance | ₹2.1 Cr+₹24.3 L (13.0%) | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | M/s Anil kumar singh L1 | INDIA SUPPY CORPORATION L3 | ARK ENGINEERING L2 |
|---|---|---|---|---|---|---|
| 1.00(WORK-1) Part A (Materials Provided by contractor) | ||||||
| 1.01 | 33 KV ‘XLPE’ C/J Kit 3x300mm² Outdoor | 12 | Nos. | 8,500 ₹1,02,000 Lowest | 10,500 ₹1,26,000 | 10,000 ₹1,20,000 |
| 1.02 | 33 KV ‘XLPE’ C/J Kit 3x300mm² Straight Through | 52 | No | 24,500 ₹12,74,000 Lowest | 25,050 ₹13,02,600 | 25,000 ₹13,00,000 |
| 1.03 | 33 KV Top channel with clamp (125 x 65 x 3200 mm) | 1 | No. | 4,250 ₹4,250 Lowest | 4,530 ₹4,530 | 4,500 ₹4,500 |
| 1.04 | 33 KV Top channel for cable stand | 2 | No. | 4,250 ₹8,500 Lowest | 4,530 ₹9,060 | 4,500 ₹9,000 |
| 1.05 | extra support angle for cable support | 3 | No. | 1,290 ₹3,870 Lowest | 1,320 ₹3,960 | 1,300 ₹3,900 |
| 1.06 | clamp for extra angle | 6 | No. | 450 ₹2,700 Lowest | 510 ₹3,060 | 500 ₹3,000 |
| 1.07 | Number Plate with clamps. | 2 | No. | 250 ₹500 Lowest | 350 ₹700 | 300 ₹600 |
| 1.08 | Danger Board with Clamps. | 1 | No. | 360 ₹360 Lowest | 412 ₹412 | 400 ₹400 |
| 1.09 | Barbed wire. | 2 | Kg | 160 ₹320 Lowest | 210 ₹420 | 200 ₹400 |
Tender Value
Refer Docs
EMD Value
₹2.4 L
Closing Date
8 Apr 2024, 4:00 pmClosed
SE EWC Gorakhpur
Srirampuram Colony Mohaddipur Gorakhpur.
Construction of New 33 KV Line and Increasing Capacity of T/F under EUDC Gkp
2024_PVVNV_920955_1
60/EWC(G)/2023-24
Open Tender
Electrical Works
Item Wise
30 days
Gorakhpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹5,900
SE EWC Gorakhpur
₹2.4 L
Yes
10 May 2024
1 Apr 2024
9 Apr 2024
1 Apr 2024
8 Apr 2024
1 Apr 2024
Amount
(WORK-1) Part A (Materials Provided by contractor)
33 KV ‘XLPE’ C/J Kit 3x300mm² Outdoor
33 KV ‘XLPE’ C/J Kit 3x300mm² Straight Through
33 KV Top channel with clamp (125 x 65 x 3200 mm)
33 KV Top channel for cable stand
extra support angle for cable support
clamp for extra angle
Number Plate with clamps.
Danger Board with Clamps.
Barbed wire.
Alumunium Paint.
Bolts, Nuts, & Washers.
Red Oxide Paint.
33 KV Stay Rod 20x1800mm
33 KV Stay clamp
stay wire 7/8 SWG
GI Wire 5mm
Earthing rod 20x2500mm
Al. lug for Dog conductor
PART-B WORK (Shifting, Loading Carriage & Unloading of following materials from store centre Gorakhpur to work site)
33 KV Line Isolator (01 Set)
33 KV Line Isolator Structure (01 Set)
MS angle for structure (01 Set)
3x300 Sq mm XLPE Cable 33 KV
ST Pole 9 m Long
ACSR Dog conductor
Laying of 33 KV 3x300 mm² ‘XLPE’ cable(D/C) in Cable trench (Cable trench constructed by PWD with hanger) with proper laying on cable trey/channel and filling sand if required as per site.
Laying of 33 KV 3x300 mm² ‘XLPE’ cable(D/C) by digging pit & making trench in Proper size (1.2M depth x1.2M wide) below ground level by fixing bricks(4½˝) on both side of trench wall and 9˝ brick work at the centre of the trench along the cable. Fixing brick slab on top after filling sand around both the cable including cost of bricks and sand. as per site requirement HDD mathod can be used.
Extra cost for drilling horizontal hole 3 Mtr below the road & inserting 6” dia. HDPE Pipe PN-8 as per RESSPO for passing of 33 KV XLPE cable 3x300 mm². (Pipe and related materials provided by contractor)
Jointing charge of 33 KV ‘XLPE’ C/J Kit 3x300 mm² Outdoor/Straight Through
For risinig of 33 KV ‘XLPE’ cable in air after providing 6” dia.M.S. pipe 3m long Complete work.
Labour charges for inserting of MS Pipe, Rising of 33 KV cable and jumpering complete work
Providing and boring of Special Pipe earthing for 33 KV Jointing Kit.
Erection of Double pole structure on 9 mtr ST Pole for only Cable rising including all works of evocation of pit, pole erection, making plinth for poles 30 cm above, grouting in the ratio 1:4:8 (cement, sand, 40 mm brick ballast), back filling of earth, proper ramming & fitting of all accessories (extra angle for cable support with clamps, top channel 125 x 65 x 3200 mm with clamps, danger board with clamp, Aluminium paint, red oxide paint, barbed wire, earthing etc. complete) .
Grouting of stay rods (20 x 1800) mm including all work of excavation, cement concrete in size (0.60 x 0.60 x 0.30) m in ratio 1:4:8 cement, sand, 40mm brick ballast) including back filling, proper ramming etc. Fixing tightening & nozzling of stay wire with stay rod with the poles of required tension.
Erection of Line Isolator Structure and install Line Isolator, earthing and fixing al. Lug, PG clamp, jumpring with bus bar complete work.
Charges of NOC for Road crossing/GDA/electrical etc.
Erection & Grouting of Top channel for cable stand
(WORK-2) Part A (Materials Provided by contractor)
33 KV ‘XLPE’ C/J Kit 3x300mm² Outdoor
33 KV Top channel with clamp (125 x 65 x 3200 mm)
33 KV Top channel for cable stand
extra support angle for cable support
clamp for extra angle
Number Plate with clamps.
Danger Board with Clamps.
Barbed wire.
Alumunium Paint.
Bolts, Nuts, & Washers.
Red Oxide Paint.
33 KV Stay Rod 20x1800mm
33 KV Stay clamp
stay wire 7/8 SWG
GI Wire 5mm
Earthing Rod 20x2500mm
Al. lug for Dog conductor
PART-B WORK (Shifting, Loading Carriage & Unloading of following materials from store centre Gorakhpur to work site)
33 KV Line Isolator (02 Set)
33 KV Line Isolator Structure (02 Set)
MS angle for structure (02 Set)
3x300 Sq mm XLPE Cable 33 KV
ST Pole 9 m Long
ACSR Dog conductor
Laying of 33 KV 3x300 mm² ‘XLPE’ cable(D/C) by digging pit & making trench in Proper size (1.2M depth x1.2M wide) below ground level by fixing bricks(4½˝) on both side of trench wall and 9˝ brick work at the centre of the trench along the cable. Fixing brick slab on top after filling sand around both the cable including cost of bricks and sand. as per site requirement HDD mathod can be used.
Jointing charge of 33 KV ‘XLPE’ C/J Kit 3x300 mm² Outdoor/Straight Through
Laying of 33 KV ‘XLPE’ cable in air after providing 6” dia.M.S. pipe 3m long Complete work.
Labour charges for inserting of MS Pipe, Rising of 33 KV cable and jumpering complete work
Providing and boring of Special Pipe earthing for 33 KV Jointing Kit.
Erection of Double pole structure on 9 mtr ST Pole for only Cable rising including all works of evocation of pit, pole erection, making plinth for poles 30 cm above, grouting in the ratio 1:4:8 (cement, sand, 40 mm brick ballast), back filling of earth, proper ramming & fitting of all accessories (extra angle for cable support with clamps, top channel 125 x 65 x 3200 mm with clamps, danger board with clamp, Aluminium paint, red oxide paint, barbed wire, earthing etc. complete) .
Grouting of stay rods (20 x 1800) mm including all work of excavation, cement concrete in size (0.60 x 0.60 x 0.30) m in ratio 1:4:8 cement, sand, 40mm brick ballast) as per drg including back filling, proper ramming etc. Fixing tightening & nozzling of stay wire with stay rod with the poles of required tension as per drawing.
Erection of Line Isolator Structure and install Line Isolator, earthing and fixing al. Lug, PG clamp, jumpring with bus bar complete work.
Erection & Grouting of Top channel for cable stand
(WORK-3) Part A (Materials Provided by contractor)
33 KV V type X-arm
X-arm clamp with nut bolt for ST Pole with nut bolt by 50x8 mm MS flat Iron make
F-bracket with nut bolt for ST Pole with nut bolt by 50x8 mm MS flat Iron make
Danger Board with Clamp
Barbed wire
Bolts, Nuts, & Washers
Top channel clamp with nut bolt for ST Pole with nut bolt by 50x8 mm MS flat Iron make
33 KV. Top channel (125x65mmX3200 mm (10.7 Kg/m)
Stay Clamp for ST Pole with Nut and Bolt by 50x8 mm MS Flat Iron make.
Stay Rod 20x1800 mm
Stay wire 7/8 SWG
MS Earthing Rod 20x2500 mm
P.G. Clamp for Panther conductor
‘E’ Bracket for 33 KV with clamp and nut bolt.
M.S. Angle Iron 65x65x6mm bracing
33 KV M.S. bracing Angle clamp with nut bolt for ST Pole with nut bolt by 50x8 mm MS flat Iron make
33 KV Guarding angle 75x40x3010mm
GI Wire 5 mm
33 KV Guarding angle Clamp with nut bolt for ST Pole with Nut and Bolt by 50x8 mm MS Flat Iron make.
33 KV Polymer Pin Insulator
33 KV Polymer Disc insulator B&S 120 KN
33 KV Polymer Disc fitting for Panther conductor
Al. paint
Red oxide paint
PART-B WORK (Shifting, Loading Carriage & Unloading of following materials from store centre Gorakhpur to work site)
ST Pole 11 M Long
ACSR Panther Conductor
Erection of Single pole structure on 11mtr ST. (SP-55) Pole including all works of evocation of pit, pole erection, making plinth for poles 30 cm above, grouting in the ratio 1:4:8 (cement, sand, 40mm brick ballast), back filling of earth, proper ramming & fitting of all accessories ( 'V' type cross arm 100 x 50 x 6 mm, clamps with bolt and nut, composite polymer pin insulator, danger board with clamp, Aluminium paint, red oxide paint, barbed wire earthing, etc. complete).
Erection of Double pole structure on 11 mtr ST Pole including all works of evocation of pit, pole erection, making plinth for poles 30 cm above, grouting in the ratio 1:4:8 (cement, sand, 40 mm brick ballast), back filling of earth, proper ramming & fitting of all accessories (M.S. angle iron 65 x 65 x 6 mm bracing with clamps, top channel 125 x 65 x 3200 mm with clamps, danger board with clamp, Aluminium paint, red oxide paint, barbed wire earthing, etc. complete) .
Dismanteling of existing ACSR Dog conductor, rolling in piece and receive back to store centre Gorakhpur
Rolling in piece of Dismantled ACSR Dog Conductor and receive back to store centre Gorakhpur.
Dismantling of old and damaged Pin Insulator/Disc Insulator/ Disc fitting/PG clamp.
Charges for installation of new Pin Insulator-30 No/Disc Insulator-21 No/ Disc fitting-21 No/PG clamp-21 by New Pin Insulator/Disc Insulator/ Disc fitting/PG clamp.
Dismantling of old and damaged existing X-arm with clamp and nut-bolt, receive back to store centre Gorakhpur.
Charges for installation of new X-arm with clamp-15 No.
Laying, spreading, lifting and final sagging of 3 phases of ACSR Panther conductor in accordance with profile and sag chart including binding, Jumpering and fixing of P.G. Clamp as per requirement in 03 Nos. conductor in parallel.
Extra cost for maintenance of Existing 33 KV line i.e. to straighten bent Pole, welding corroded Poles and regrouting, tightening stay etc.
Grouting of stay rods (20 x 1800) mm including all work of excavation, cement concrete in size (0.60 x 0.60 x 0.30) m in ratio 1:4:8 cement, sand, 40mm brick ballast) as per drg including back filling, proper ramming etc. Fixing tightening & nozzling of stay wire with stay rod with the poles of required tension.
Guarding between two poles like single poles, double poles, four poles, etc. to guard LT, 11 KV Line telephone and river crossing, road crossing etc. with G.I. wire no. 6 SWG and G.I. wire no. 8 SWG, cutting, fabrication and fixing of guarding channel 75 x 40 x 3010 mm with clamps nut & bolts etc.
(WORK-4) Part A (Materials Provided by contractor)
3x300 mm² XLPE Cable C/J Kit indoor
3x300 mm² XLPE Cable C/J Kit outdoor
33 KV. Top channel for cable stand & neutral earthing
33 KV PG clamp
PART-B WORK Shifting & loading of following materials on private truck at store centre Gorakhpur & carriage up to 33/11 KV Sub-Station Ranibagh Distt-Gorakhpur & Un-loading of the same with proper stacking (Distance about 0 to 6 km)
11 KV ‘XLPE’ Power cable.
ACSR Dog conductor
Repairing of plinth and foundation for 10 MVA transformer as per required specification. Dismantling of T/F all connection, Rail pieces and T/F shifting to another place by crane and 1.5 mtr increasing height of T/F plinth over the ground level.
Dismantling of Bus bar Jumpers, different earthings of existing 5 MVA T/F. etc. complete work
Installation, wiring and earthing of 33 KV C.T. complete work
Transformer body earthing including cost of G.I. strip, G.I. pipe and other earthing materials required. (delta type)
Laying of 11 KV “XLPE” cable 3 x 300 mm2 including digging of pits of size 0.5 x 0.5 mtr. covering of cable with sand and 1st class bricks around and top of the cable.
Neutral earthing of 10 MVA transformer complete including cost of G.I. strip, G.I. pipe 1.5” dia 30’ long and other earthing materials. (delta type)
Grouting of M.S. Channel 3.2 mtr. long for neutral earthing support of 10 MVA transformer with help of G.I. strip 50 x 6 mm and copper flexible bond etc.
Grouting of M.S. channel 3.2 mtr long for cable stand and welding of M.S. flat at equal distance for fastening cable by clamp with nuts and bolts mounting of cable at cable stand and connection of jumpers.
Providing and Jointing charges of 11 KV “XLPE” C/J kit 3 x 300 mm2 indoor/outdoor.
Dismantling of existing pale fencing and resetting after completion of trnasformer work.
Painting of erected structure in switchyard.
(WORK-5) Part A (Materials Provided by contractor)
Battery charger with 24 Volt battery with cabinet. (As per Instruction of Supervision Authority)
33 KV. Top channel for cable stand & neutral earthing
33 KV ‘XLPE’ C/J Kit 3x300mm² Outdoor
11 KV C/J Kit 3X185 mm² XLPE Indoor
11 KV C/J Kit 3X185 mm² XLPE Outdoor
11 KV C/J Kit 3X300 mm² XLPE Indoor
11 KV C/J Kit 3X300 mm² XLPE Outdoor
Armoured copper control cable 2 x 2.5 mm2
Armoured copper control cable 4 x 2.5 mm2
11 KV Top channel with clamp
extra support angle for cable support
clamp for extra angle
Number Plate with clamps.
Danger Board with Clamps.
Barbed wire.
Allumunium Paint.
Bolts, Nuts, & Washers.
Red Oxide Paint.
11 KV Stay Rod 16x1800mm
11 KV Stay clamp
Stay wire 7/10 SWG
Earthing Rod 20x2500mm
GI wire 5 mm
PART-B WORK Shifting & loading of following materials on private truck at store centre Gorakhpur & carriage up to 33/11 KV Sub-Station Rushtampur, Distt- Gorakhpur & Un-loading of the same with proper stacking (Distance about 0 to 6 km)
33 KV ‘XLPE’ Cable 3x300mm²
11 KV ‘XLPE’ power cable.
11 KV Incoming Pannel
33 KV ‘VCB’ complete with all structure.
33 KV Bus Type Isolator
33 KV Line Isolator
33 KV control Pannel
33 KV lightening arrester
33 KV Small structure (Line isolator structure, Bus isolater structure, post insulator structure, fuse set structure, CT Structure, LA Structure, PT Structure etc)
33 KV Post insulator
11 KV Switchgear panels(O/G)
Bus coupler
ACSR Dog conductor
33 KV Fuse set
2.6 m MS angle for structure
90 Ib, Rail pieces (44.64 Kg/M)
ST Pole 11 M long
Construction of power transformer plinth for 5 MVA transformer of size 3.5 x 3.5 x 1.5 mtr. including cost of all material as per drawing.
Earthing of 5 MVA power transformer body earthing at two places including cost of G.I. strip, G.I. pipe and other earthing materials required.
Jointing charges of 11 KV “XLPE” C/J kit 3 x 300/185 mm2 indoor/Outdoor type
Jointing charges of 33 KV “XLPE” C/J kit 3 x 300 mm2 indoor/Outdoor type
Neutral earthing of 5 MVA transformer complete including cost of G.I. strip, G.I. pipe 1.5” dia 20’ long and other earthing materials.
Grouting of M.S. Channel 3.2 mtr. long for neutral earthing support of 5 MVA transformer with help of G.I. strip 50 x 6 mm and copper flexible bond etc.
Grouting of M.S. channel 3.2 mtr long for cable stand and welding of M.S. flat (3 Nos.) at equal distance for fastening cable by clamp with nuts and bolts mounting of cable at cable stand and connection of jumpers.
Erection of VCB Structure and Installation of 33 KV control panel for “VCB” with complete earthing with installation of battery and battery charger in control room and making connection. (complete wiring and istallation)
Laying of 11 KV “XLPE” power cable 3 x 300 mm2 / 185 mm2 including digging of pits of xize 0.5 x 0.5 mtr. covering of cable with sand and 1st class brick around the cable.
Laying of 33 KV “XLPE” power cable 3 x 300 mm2 mm2 including digging of pits of xize 1.0 x 1.0 mtr. covering of cable with sand and 1st class brick around the cable.
Shifting of 11 KV switchgear to control room and placing in control room with grouting of bolts and mounting of switchgear panels properly.
Installation of Bus Coupler with complete earthing and making connection, Testing and all respect work.
Electrical connection of 11 KV switchgear panel and fitting of Bus Bar and P.T.
Testing of 11 KV switchgear panel in all respect.
laying of control cable from switchyard to control room 33 KV panel by digging trench in switchyard including cost of sand and 1st class bricks with covering and making connection complete and including cost of laying.
Earthing of indoor equipments
Erection and grouting of following structure.
33 KV Bus Isolator structure
33 KV Line Isolator structure
33 KV fuse set structure
33 KV Post insulator structure
33 KV L.A. structure
33 KV CT structure
33 KV PT structure
33 KV VCB structure
Installation of following Equipments on erected structure and related connection
33 KV Bus Isolator
33 KV Line Isolator
33 KV fuse set (Providing Copper strip as required size for 33 KV fuse set)
33 KV Post insulator
Earhing of outdoor type switchyard earthing for newly erected structure as per proper specification with GI Earthing strip.
Jumpring from 33 KV Bus bar to post insulator, bus isolator, VCB, CT and LA to 5 MVA transformer etc. (Providing alluminium Lug and PG Clamp)
Construction of approach road inside the switchyard 1.5 Mtr. wide with 1st class bricks on edge soling and tipping complete work including cost of all materials.
Painting of newly erected structure in switchyard (Applying on coat of good quality red oxide primer then two coats of good quality of high class luxol aluminium paint)
Erection of Double pole structure on 11 mtr ST Pole for only Cable rising including all works of evocation of pit, pole erection, making plinth for poles 30 cm above, grouting in the ratio 1:4:8 (cement, sand, 40 mm brick ballast), back filling of earth, proper ramming & fitting of all accessories (extra angle for cable support with clamps, top channel 125 x 65 x 2240 mm with clamps, danger board with clamp, Aluminium paint, red oxide paint, barbed wire, earthing etc. complete) .
Grouting of stay rods (16 x 1800) mm including all work of excavation, cement concrete in size (0.60 x 0.60 x 0.30) m in ratio 1:4:8 cement, sand, 40mm brick ballast) including back filling, proper ramming etc. Fixing tightening & nozzling of stay wire with stay rod with the poles of required tension.
ARK ENGINEERING
INDIA SUPPY CORPORATION
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .