EXECUTIVE ENGINEER BOLPUR MECHANICAL DIVISION PHED
SRINIKETAN ROAD NEAR HOTEL MARK MEADOWS PO SRINIKETAN DIST BIRBHUM PIN 731236
Supply, Installation and Commissioning of Iron Elimination Plant at Bolpur S.D Hospital for setting up of Mechanised Laundry under Bolpur Mechanical Division, PHE Dte
2024_PHED_675125_3
PHED/51/EE/BOLMD/2023-24
Open Tender
MECHANICAL
Item Rate
30 days
BOLPUR BIRBHUM
Please refer Tender documents.
5 documents required · 5 mandatory
₹51,000
3 Jan 2025
27 Feb 2024
22 Mar 2024
28 Feb 2024
20 Mar 2024
28 Feb 2024
Amount
Preparation of design & drawing as per C.P.H & E.E.O and P.H.E guidline including fulfiment of all criteria in latest I.S code provision for all required materials, plant, machine, electrical accessories etc. for the following capacity Iron removel plant (Pressure type) and submission the same duly vetted from Govt. recognised institution e.g. Jadavpur University, IIEST etc. i) Capacity: 25 cum/hr.
i) Iron removal plant (pressure type) having capacity 25 cum/Hr as per requirement with provision of fabricated shell with minimum 10 mm thick MS plate and MS media supporting plate minimum 12 mm thick including detailing of capacity and size of all accessories i.e pipe connection, valve, gauge, other instrument, fabricated oxidation chamber, filter media, air compressor & air blower with motor starter, main switch etc.(The treatment unit should capable to reduce iron content as per I.S 10500:2012 with latest ammendment.) Raw water containing dissolve iron may be in the tune of 10 ppm can easily be treated in the iron removal plant. ii) R.C.C. foundation considering all load and criteria i.e. seismic, wind pressure etc. as per site condition.
Fabrication of 25 cum/Hour capacity I.R. plant as per approved design & drawing including performing satisfactory hydraulic test of fabricated shell vessel and installation at site over R.C.C. foundation base with fitting, fixing stainer, placing filter media, all valves ( air/vent, inlet, outlet, backwash as per approved unified vendor list vide official website of WBPHED) and specials, all pipe line works underground & over ground including inlet, outlet within I.E. plant with connection to the existing rising main and also filter water main connection to the existing distribution main with all cost etc. Including fitting, fixing all accessories such as pressure gauge, manhole cover of approve make and painting with approved quality anticorrosive paint with indicating flow direction i.e. inlet, outlet, backwash etc. complete in all respect as per approved design and drawing and as per specification given in NIT with satisfaction of E.I.C.including testing on satisfactory completion of complete Iron Removal Plant(Pressure type).
Fabrication and installation suitable size Oxidation chamber for 25 cum/Hour capacity I.R. plant as per approved design and drawing including performing satisfactory hydraulic test of fabricated shell vessel and installation at site over R.C.C. foundation base including supply of all chemical, valve, gauge etc of approved quality with fitting, fixing all accessories as per specification given in NIT and direction of E.I.C.
Supplying, fitting, fixing of suitable capacity Air Compressor and Air Blower (capacity of Air Compressor and Air Blower should not be less than the capacity mentioned in NIT specification) with starter, main switch & all other accessories as per IS specification and specification given in NIT and as per direction of E.I.C.
Power connection from existing main line to the compressor room as per I.E. rule with supply of all materials fitting, fixing, necessary wiring connection in the air compressor as per required capacity motor, starter, main switch & all other accessories complete in all respect as per specification given in NIT and direction of E.I.C
Construction of R.C.C foundation for installation of IR plant, with masonry working platform surrounded to the plant for smooth operating all valves of I.R. Plant & Oxidation Chamber, Air Compressor & Air Blower, as per approved design & drawing complete in all respect as per direction of E.I.C.
Construction masonry surface srain of suitable section capable for discharging the back wash water from plant to existing drain of minimum length 10.00 Mtr. And construction of suitable platfrom with minimum size 20sqm. complete in all respect as per specification given in NIT and direction of E.I.C.
Construction of compressor room with internal size 3.60 mtr. X 3.00 mtr. & height 3.10 mtr. Including internal wiring and illumination. As per departmental approved type design & drawing complete in all respect & as per specification given in NIT and direction of E.I.C.
Trial run for 90 (Ninety) days after successful installation and commissioning the plant complete in all respect as per direction of E.I.C.
Supply, Installation and Commissioning of Iron Elimination Plant. (Capacity- 25 m3/hr)
Add: GST @ 18% on sum of Item No: 1 to 2
Add Cess @1% on sum of Item No. 3
Jal Pravahika Pvt. Ltd.
Jai Bharat Commercial Corporation
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .