Tender Value
₹1.3 Cr
EMD Value
₹2.0 L
Closing Date
6 Jan 2022, 6:00 pmClosed
CWE (ARMY) SECUNDERABAD
CWE (ARMY) MUDFORT COMPLEX, SECUNDERABAD- 500003
UP GRADATION OF LT TAKEOVER POINT TO HT 11 KV FROM TSSPDCL AT LAKE LINE FAMILY ACCN, GOLDEN FAMILY ACCN, SWIMMING POOL AND DENTAL CENTRE INCLUDING PROVN OF TRANSFORMER UNDER GE(UTILITY) SECUNDERABAD
2021_MES_492650_1
CWE(S)/UTILITY/TOKEN-25 OF 2021-2022
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Secunderabad
As per NIT
7 documents required · 7 mandatory
₹1,000
GE Utility Secunderabad
₹2.0 L
Yes
15 Feb 2022
4 Dec 2021
13 Jan 2022
4 Dec 2021
6 Jan 2022
31 Dec 2021
Amount
M&L for Supply,test,erection & commissioning of Steel tubalar swaged poles staying in a truely vertical position till the foundations are properly set with the help crane complete with cast iron base plate, finial taper plug, bolts, nuts & screws including drilling of holes to poles for clamps & hooks for running of earth wire/Strip complete all as specified type 410 SP-55,11 mtrs HT poles complete all as directed Note:-(i)Crane charges for erection shall be deemed to be including in quoted rate. (ii) Earth work, excavation ,PCC,coping shall be measured and paid separately. (iii) The rates include staying the poles in at truely vertical position till the foundations are properly set. (iv)The rates include cast iron base plate,nuts,bolts,screws,painting of steel tubular poles,drilling of holes in steel tubular poles for fixing of clamps,hooks for continuous earth wire/strip.
Supply, Laying, connecting, Testing and Commissioning of XLPE insulated screned PVC beded galvanised steel strip or wire armoured earthed electric power cable (heavy duty) with aluminium couductor 11 KV(E) grade suitable for earthed system cross sectional area 95 sqmm 3 core H.T.U.G cable laid in tranches/through GI pipe/fixed along with pole complete all as specified & directed .
M&L Switch air break gang operated triple pole mechanically operated mounted on 9 Nos 10 KN insulators insulator and steel frame out door type suitable for Horizontal / vertical installation single / double brake provided with locking arrangement, consisting of MS channel ,HT post type insulator ,copper alloy high pressure assembly ,operating rod of 25 mm dia GI pipe medium grade confirming to IS-1818 of 1972 ,suitable for 11000 volt ,400 Amps, short time withstand current 25 KA for 3 sec complete all as specified and directed.
M&L for air break switch, rocking type, Gang operated, triple pole, mechanically operated, mounted on 6 Insulators insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 200 amps suitable for 11000 volts complete all as specified and as directed.
Supply and fix drop out fuse unit woth 10 KN insulator suitable for 11000 volt ,100 amps mounted on MS channel complete with post insulator fuse barrel etc for 3 phase complete all as specified and directed
M&L for Lightning arrester non linear complete with all fittings distribution class discharge capacity 65 kilo amp, current rating 5 kA suitable for 11000 volt complete with all fittings complete all as specified and directed
M&L for Anti-climbing device, spikes type fabricated out of MS bars (round,square and flat) including nuts, bolts, washers,and welding in two halves made to shape to suit cross section of the pole and painting with two coats of aluminium paint over a coat of primer complete all as specified and directed
M&L for Danger notice plate of 1.6 mm thick mild steel sheet vitreous white ,with letters ,figures and fixed with ms clamps bolts and nuts of size approved size for HT of size 25cmx20cm confirming to IS-2531 complete all as specified and directed
Supply and fix cable end termination suitable for XLPE ,HT 11 kv (E) under ground cable,95 sqmm,3 core,11000 volt ,heat shrink type out door end termination incuding ALL JOINTING MATERIAL complete all as specified and directed.
Supply and fix cable end termination suitable for XLPE ,HT 11KV (E) under ground cable,95 sqmm,3 core,11000 volt ,heat shrink type in door end termination including ALL JOINTING MATERIAL complete all as specified and directed.
Supply and fixing of cable route indicator for HT round shaped 150mm dia 10mm thick with marking of 11 KV, HT welded bolted on angle iron of 25x25cmof 60 cm length grouted in PCC 1:3:6 TYPE C2 block of size 150X150X150mm embedded in ground including necessary excavation and earth work complete all as specified and directed.
M&L cross arm bracing support clamp back plates fabricated from structural steel section including nut bolt washer welding, bending, cold or not drilling holes for bolt in any shape or size as directed & incl two coat of aluminium paint over a coat of red oxide primer complete all as specified & directed.
Supply , Install, Testing and Commissioning of Advance Maintenance Free G.I. SAFE EARTHING Electrode with PIPE of not less than 50 mm outer dia) and two meter length, The electrode should be of galvinised (80 -100 micron) along with earth lead as Galvanised steel strip of size 32 X6 mm 7.5 m . The GI Electrode shall be pre-filled with Cristaline Conductive Material (CCM) . The GI electrode shall be surrounded with 25 kg BackFill compound to provide maximum contact between the electrode and Back Fill Compound. The earting pit cover should be factorty built ( size TOP- 10 Inch, Bottom -13 Inch, Height 10.25 Inch ) made of heavy duty Polypropylene complete all as specified and directed make ASHLOK / INDELEC/JMV /TERCEL/TRUE POWER
Supply and fix galvanized earth strip 32 mm x 6 mm for earthing from earth plate to equipment complete all as specified and as directed.
M&L Aluminium conductor steel rainforced for over head lines,securing on poles complete including binding wire jointing sleeves ,aluminium taps etc all as specified of sizes squirrel/weasel/ferret/mink.complete all as specified and directed.
S&F for pin type porcelain , vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150 mm height and 150 mm dia suitable for working pressure 11000 Volts grade complete all as specified and directed..
Supply and fix disc type insulator vitreous 145 mm high and 255 mm dia ball and socket type white /brown 70 KN "two in one series" assembly for tension with clamps for conductor suitable for 11000 volt working pressure complete all as specified and as directed.
Excavation in trenches not exc 1.5 mtr wide and above 1.5 m depth but not.exc 3.0 mtr in deep and getting out as in Hard/Dense soil laying of cables etc complete all as specified and as directed.
Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth, for foundation of PCC/Steel pole, laying of cable in trenches etc and getting out in Hard / Dense soil complete all as specified and directed.
Earth work in excavation by mechanical means in trenches in all kind of soil not exceeding 1.5 m in width including dressing of side , lift upto 1.5 m including getting out the excavated soil for laying of LTUG cable and disposal of surplus excavated soil as directed
Excavation in trenches not exceeding 1.5 m width and not exc 1.5 m in depth and getting out in hard rock for /laying of pipe line complete all as specified and directed including removing of debries from site complete all as specified and as directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm in soils complete all as specified and directed.
Removing excavated material (soils) n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed.
M&L for filling sand in trenches for sand cushioning of laying of cables to the full width of excavated trench 8 cm thick before laying the cable and 15 cm above the cable, gently punned down, stretching and testing of cable on transformer yard etc complete all as specified and directed. Note :- Thickness of sand cushion after punning down i.e 18 Cm shall be measured for payment
Supplying and laying un reinforced precast concrete cable cover class LV , Type 1 flat with size 250mm x150 mm x 40mm laid dry in trenches over under ground cables all as specified and directed
Supply and lay un-reinforced precast concrete cable cover , class , HV , Type I flat size 300 x 180 x 40 mm laid dry in trenches over under ground cables complete all as specified and directed.
M&L for cement concrete 1:2:4 type B-1 (using 20mm graded stone aggregate) as lean concrete in foundation of poles, stay assembly, etc., including formwork and for foundation of GI pipe, bollard light (as/if required), complete all as specified and as directed.
M&L for cement concrete 1:3:6 Type C-1 (using 20mm graded stone aggregate) as in coping of poles, etc. including necessary formwork, complete all as specified and as directed.
Supply and laying of following size HDPE pipe pn 10 ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground , wall , floor complete all as specified and directed
75 mm dia
110 mm dia
M&L for Cutting the existing road / hardstanding straight by manual, depth and width not less than 0.6 mtr below ground level for passing of underground cable and filling back with excavated soil upto 75% road portion and 25% shall be made with cement concrete 1:2:4 (using 20 mm graded aggregate stone complete all as specified and directed. Note : Quoted rates inclusive of PCC
M&L for road crossing/drain crossing by adopting trench less tunneling work through specified pipe jacking method by erecting the equipment to true to the allignment and gradient by hydraulic pipe jacking technique complete including tunneling, excavation in any type of soils including hard rock, HDPE pipe upto 110 mm dia of max length 15 m including jointing materials to carry LT UG cables of size upto 240 Sqmm and necessary conveyance charges of machinery and other required materials in co-ordination with the concerned authorites complete all as specified and as directed including refilling and making good of disturbed surface . Note : Quoted rate exclusive of HDPE pipe but including of necessary machinaries required for the above work
Supply , installation, Testing and Commissioning of double wound copper transformer step down, outdoor type complete with standard fittings, primary voltage of HT 11000 Volts and secondary LT 433 volts, 3 Phase 4 wire with frequency 50 c/s. Provided with 5 No of off load tappings on HT side to vary secondary voltage within range of +7.5% to - 2.5% (in steps of 2.5%), star delta connections with vector group of Dyn 11, Impedance of 5% and including PCC Foundation , first filling of transformer oil as per IS:335 and color coating with one coat of primer and two coats of BS grey colour. Losses all as per IS:1180 (Level -II) of capacity of 500 KVA with the following accessories :-
(a) Rating and Terminal marking plate- one (b) Earthing Terminal- Two (c )Lifting Lugs- Two (d) Drain valve with Blanking plate - One (e) Filter Valve with blanking plate- One (f) Conservator-One (g) Oil Level indicator with minimum marking (h) Dyhydrating breather-One (j) Air Release devise - One (k) Thermometer Pocket-One (l)Pressure relief valve - One (m)Roller unidirectional-Four (n)HV side Bare Bushing and LV side cable end Box (o)Separate Brought out Neutral Terminal (p)Off Circuit Tap Changer (q)100 MM dia stem type Thermometer ® provn Suitable Foundation for Transformer of size 1.5MX1.5Mx1.5 M as specified and directed by Engineer-in-charge including provn of cable entry on LT Side
Supply , installation, Testing and Commissioning of double wound copper transformer step down, outdoor type complete with standard fittings, primary voltage of HT 11000 Volts and secondary LT 433 volts, 3 Phase 4 wire with frequency 50 c/s. Provided with 5 No of off load tappings on HT side to vary secondary voltage within range of +7.5% to - 2.5% (in steps of 2.5%), star delta connections with vector group of Dyn 11, Impedance of 5% and including PCC Foundation , first filling of transformer oil as per IS:335 and color coating with one coat of primer and two coats of BS grey colour. Losses all as per IS:1180 (Level - ii) of capacity of 315 KVA with the following accessories :-
(a) Rating and Terminal marking plate- one (b) Earthing Terminal- Two (c)Lifting Lugs- Two (d) Drain valve with Blanking plate - One (e) Filter Valve with blanking plate- One (f) Conservator-One (g) Oil Level indicator with minimum marking (h) Dyhydrating breather-One (j) Air Release devise - One (k) Thermometer Pocket-One (l) Pressure relief valve - One (m) Roller unidirectional-Four (n) HV side Bare Bushing and LV side cable end Box (o) Separate Brought out Neutral Terminal (p) Off Circuit Tap Changer (q) 100 MM dia stem type Thermometer ® provn Suitable Foundation for Transformer of size 1.5MX1.5Mx1.5 M as specified and directed by Engineer-in-charge including provn of cable entry on LT Side
Supply , installation, Testing and Commissioning of double wound copper transformer step down, outdoor type complete with standard fittings, primary voltage of HT 11000 Volts and secondary LT 433 volts, 3 Phase 4 wire with frequency 50 c/s. Provided with 5 No of off load tappings on HT side to vary secondary voltage within range of +7.5% to - 2.5% (in steps of 2.5%), star delta connections with vector group of Dyn 11, Impedance of 5% and including PCC Foundation , first filling of transformer oil as per IS:335 and color coating with one coat of primer and two coats of BS grey colour. Losses all as per IS:1180 (Level - ii) of capacity of 200 KVA with the following accessories :-
(a) Rating and Terminal marking plate- one (b) Earthing Terminal- Two (c ) Lifting Lugs- Two (d) Drain valve with Blanking plate - One (e) Filter Valve with blanking plate- One (f) Conservator-One (g) Oil Level indicator with minimum marking (h) Dyhydrating breather-One (j) Air Release devise - One (k) Thermometer Pocket-One (l) Pressure relief valve - One (m) Roller unidirectional-Four (n) HV side Bare Bushing and LV side cable end Box (o) Separate Brought out Neutral Terminal (p) Off Circuit Tap Changer (q) 100 MM dia stem type Thermometer ® provn Suitable Foundation for Transformer of size 1.5MX1.5Mx1.5 M as specified and directed by Engineer-in-charge including provn of cable entry on LT Side
Supply , installation, Testing and Commissioning of double wound copper transformer step down, outdoor type complete with standard fittings, primary voltage of HT 11000 Volts and secondary LT 433 volts, 3 Phase 4 wire with frequency 50 c/s. Provided with 5 No of off load tappings on HT side to vary secondary voltage within range of +7.5% to - 2.5% (in steps of 2.5%), star delta connections with vector group of Dyn 11, Impedance of 5% and including PCC Foundation , first filling of transformer oil as per IS:335 and color coating with one coat of primer and two coats of BS grey colour. Losses all as per IS:1180 (Level - II) of capacity of 160 KVA with the following accessories :-
(a) Rating and Terminal marking plate- one (b) Earthing Terminal- Two © Lifting Lugs- Two (d) Drain valve with Blanking plate - One (e) Filter Valve with blanking plate- One (f) Conservator-One (g) Oil Level indicator with minimum marking (h) Dyhydrating breather-One (j) Air Release devise - One (k) Thermometer Pocket-One (l) Pressure relief valve - One (m) Roller unidirectional-Four (n) HV side Bare Bushing and LV side cable end Box (o) Separate Brought out Neutral Terminal (p) Off Circuit Tap Changer (q)100 MM dia stem type Thermometer ® provn Suitable Foundation for Transformer of size 1.5MX1.5Mx1.5 M as specified and directed by Engineer-in-charge including provn of cable entry on LT Side
Supply , installation, Testing and Commissioning of double wound copper transformer step down, outdoor type complete with standard fittings, primary voltage of HT 11000 Volts and secondary LT 433 volts, 3 Phase 4 wire with frequency 50 c/s. Provided with 5 No of off load tappings on HT side to vary secondary voltage within range of +7.5% to - 2.5% (in steps of 2.5%), star delta connections with vector group of Dyn 11, Impedance of 5% and including PCC Foundation , first filling of transformer oil as per IS:335 and color coating with one coat of primer and two coats of BS grey colour. Losses all as per IS:1180 (Level - II) of capacity of 63 KVA with the following accessories :-
(a) Rating and Terminal marking plate- one (b) Earthing Terminal- Two © Lifting Lugs- Two (d) Drain valve with Blanking plate - One (e) Filter Valve with blanking plate- One (f) Conservator-One (g) Oil Level indicator with minimum marking (h) Dyhydrating breather-One (j) Air Release devise - One (k) Thermometer Pocket-One (l) Pressure relief valve - One (m) Roller unidirectional-Four (n) HV side Bare Bushing and LV side cable end Box (o) Separate Brought out Neutral Terminal (p) Off Circuit Tap Changer (q)100 MM dia stem type Thermometer ® provn Suitable Foundation for Transformer of size 1.5MX1.5Mx1.5 M as specified and directed by Engineer-in-charge including provn of cable entry on LT Side
Note FOR SL NO 32 TO 36 : a) Factory inspection and testing of the transformer to be done by the rep of accepting officer. Necessary arrangement for factory inspection and testing to be done by the contractor. Rates for the same deemed to be included in the quoted rates. b) Contractor should submit the drawing of the transformer based on the IS and Energy level mentioned in BOQ and take necessary approval from GE before finalisation order to the manufacturer.
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following accessories/components :- (Size of the panel board should not be less than 1.25 M X1.6 MX0.40M) ((Panel Board No. 01, Location :- Near Transformer))
(a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 1000 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 630 Amps 50KA -01 Nos. adjustable type (incommer) (c) MCCB 4 Pole 400 Amps 36KA -02 Nos. (Outgoing) (d) MCCB 4 Pole 250 Amps 25KA -02 Nos. (Outgoing) (e) MCCB 4 Pole 160 Amps 16KA -02 Nos. (Outgoing) (f) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 630/5A LT-CT operated complete - 01 Set (g) Indicating type lamp for Red, Yellow and Blue phases - 01 Set
Notes for Sl no 37 to 44 : (a) All incoming and out going cables are to be connected to the above panels with proper lugs, double compression brass cable gland, nuts, bolts etc the cost of the items deemed to be included in the quoted rates. (b) The panel shall be Fabricated from a reputed firm(CPRI Approved) . (c) All Internal connection between ACB, MCCB ( ABOVE 63 AMPS ) and Changeover and Bus bar shall be done by aluminium strip of suitable size and capacity .
(e) All MCCB to be connected with both side Spreader link and All Incomer and outgoing MCCB of Panels should be thermal magnetic release with adjustable settings ( Min 70 % to 100 %) and Ics = 100% Icu
(f) Sufficient space to be provided for cable connection between MCCB and Bottom of the panel board.( Minimum space for MCCB up to 200 amps = 35 CM , Minimum space for MCCB 250 to 400 amps = 45 CM , Minimum space for MCCB above 400 amps = 55 CM )
(g) Base of the panel should not be less than 400 mm above the ground level. Necessary PCC for base /foundation required deemed to be included in the quoted rate.
h) Cable alley / chamber to along with connector of suitable size to be provided for connection of Out going cable .
j) Necessary approval of drawing to be taken from GE before placing order to the manufacturer.
k)All existing incoming and out going cables also to be connected to the above panel as per site requirement with proper lugs, glands nuts, bolts etc
(l) Door hinge of industrial type heavy duty to be provoded minimum 3 nos for each door
(m) The rate shall deemed to be include in the item rate for all the points mentioned above.
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following accessories/components :- (Size of the panel board should not be less than 1.15 M X2.0 MX0.40M)
(a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 650 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 400 Amps 36KA -01 Nos. adjustable type (incommer) (c) MCCB 4 Pole 160 Amps 16KA -05 Nos. (Outgoing) (d) MCCB 4 Pole 63 Amps 16KA -04 Nos. (Outgoing) (f) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 400/5A LT-CT operated complete - 01 Set (g) Indicating type lamp for Red, Yellow and Blue phases - 01 Set (h) The rate shall deemed to be include in the item rate for all the items mentioned above.
Design , Supply, Installation, testing and Commissioning CPRI APPROVED factory fabricated, out door type,LT FEEDER PILLAR BOX IP 55 protection grade, made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers , cable glands of appropriate size , etc. and supported with 65X65X6mm Mild Steel Angle Iron Frame and 500 mm above ground lavel , embeded in PCC 1:2:4, type C-2, 45 Cm below ground level and 50 Cm above ground level complete with internal connection with suitable size of strip ,cable lugs,and cable glands and Test-ing after Installation complete all as specified and comprising of the following accessories/components :- (Size of the panel board should not be less than 1.15 M X1.6 MX0.40M) ((Panel Board No. 01, Location :- Near Transformer))
(a) Bus bar aluminium duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic, non combustible, track resistant high strength FRP insulators 1000 Amps for phases and Neural, set of 4 for RYB &N - 01 set. (b) MCCB 4 Pole 630 Amps 50KA -01 Nos. adjustable type (incommer) (c) MCCB 4 Pole 400 Amps 36KA -03 Nos. (Outgoing) (d) MCCB 4 Pole 63 Amps 16KA -01 Nos. (Outgoing) (e) MCCB 4 Pole 16 Amps 10/16KA -02 Nos. (Outgoing) (f) Three phase Panel mounted Digital type Voltmeter meter 0-500 Volts, Ammeter 630/5A LT-CT operated complete - 01 Set (g) Indicating type lamp for Red, Yellow and Blue phases - 01 Set (h) The rate shall deemed to be include in the item rate for all the items mentioned above.
Design, Supply, Install, testing and commissioning factory made and tested CPRI approved APFC capacitor bank 70 KVAR double door panel board out door type hood on top weather vermin proof cubical type platform mounted suitable for 415 Volts phase, 4 wire 50 Hz AC supply system all as specified and directed with necessary busbar arrangement insulated aluminium busbar 200 Amps rating for phase and 100 Amps for neutral 4 strips installed on porcelin insulators housed in separate bus chamber covered with heat shrinkable sleeves with necessary busbar tapings automatic power factor control relay and copper control wiring of required size, the panel shall be dust proof IP-54 class protection and made of 3 mm CRCA MS sheet with 50 X 50 X 6 mm angle Iron frame 30 Cm below ground level and 30 Cm above ground level with necessary earth work excavation, hinged door's front & Rear openings and locking arrangements duly power coated on the out side and inside including provision of PCC plat form 100 mm thick with PCC 1:4:8 type D2 using 40MM graded stone aggregate one metre all around the panel board, cable gland and lugs for incomming and out going cables etc independent chambers to accommodates complete all as specified and directed including the following accessories:- (Size of the panel board should not be less than 1.15 M X1.15 MX0.40M)
(a) MCCB 4 Pole 415 Volts 50 Hz 160 Amps Adjustable thermal magnetic release type with breaking capacity 25KA -01 As I ncoming
b) MCB TP 40 Amps 10 KA, 415 Volts - 02 Nos (Out going for capacitor )
c) MCB TP 20 Amps 10 KA, 415 Volts - 04 Nos (Out going for capacitor )
d) APP Power Factor Improvement Capacitor 3 Phase, 415 Volts 50 HZ ,20 KVAR - 02 Nos: 10 KVAR - 02 Nos and 5 KVAR - 02 Nos
(e) Power contactor TP 40 Amps - 02 Nos ( capacitor Duty)
(f) Power contactor TP 20 Amps - 04 Nos ( capacitor Duty)
(g) Digital Ammetor 0 to 100 Amps - 01 No
(h) Digital Volt meter 0 to 500 Volts
(j) Indicator Lamps LED Type Set 01 Set
(j) APFC controller 8 stage eta con of L&T model No ETACONM008R / equivalent - 01 Nos
(k) Digital PF Meter - 01 Nos
(l) Quoted Rates inclusive of CT of suitable ratio ( to be fitted on existing LT Panel) and copper wire 2 core 2.5 Sqmm sheathed for connection between existing LT Distribution panel to Capacitor panel
Design,Supply, Install, testing and commissioning factory made and tested CPRI approved APFC capacitor bank 100 KVAR double door panel board out door type hood on top weather vermin proof cubical type platform mounted suitable for 415 Volts phase, 4 wire 50 Hz AC supply system all as specified and directed with necessary busbar arrangement insulated aluminium busbar 200 Amps rating for phase and 100 Amps for neutral 4 strips installed on porcelin insulators housed in separate bus chamber covered with heat shrinkable sleeves with necessary busbar tapings automatic power factor control relay and copper control wiring of required size, the panel shall be dust proof IP-54 class protection and made of 3 mm CRCA MS sheet with 50 X 50 X 6 mm angle Iron frame 30 Cm below ground level and 30 Cm above ground level with necessary earth work excavation, hinged door's front & Rear openings and locking arrangements duly power coated on the out side and inside including provision of PCC plat form 100 mm thick with PCC 1:4:8 type D2 using 40MM graded stone aggregate one metre all around the panel board, cable gland and lugs for incomming and out going cables etc independent chambers to accommodates complete all as specified and directed including the following accessories:- (Size of the panel board should not be less than 1.25 M X1.25 MX0.40M)
(a) MCCB 4 Pole 415 Volts 50 Hz 200 Amps Adjustable thermal magnetic release type with breaking capacity 25KA -01 as I ncoming
(b) MCCB TP 63 Amps 3 Pole 16 KA - 2 nos ( Outgoing to Capacitor )
c) MCB TP 40 Amps 10 KA, 415 Volts - 03 Nos ( Outgoing to Capacitor )
d) MCB TP 20 Amps 10 KA, 415 Volts - 02 Nos( Outgoing to Capacitor )
e) APP Power Factor Improvement Capacitor 3 Phase, 415 Volts 50 HZ ,25 KVAR - 02 Nos: 20 KVAR - 01 Nos, 10 KVAR -2 Nos and 5 KVAR - 02 Nos
(f) Power contactor TP 63 Amps - 02 Nos capacitor duty
(g) Power contactor TP 40 Amps - 03 Nos capacitor duty
(h) Power contactor TP 20 Amps - 02 Nos capacitor duty
(j) Digital Ammetor 0 to 100 Amps - 01 No capacitor duty
(k) Digital Volt meter 0 to 500 Volts
(l) Indicator Lamps LED Type Set 01 Set
(m) APFC controller 8 stage eta con of L&T model No ETACONM008R / equivalent - 01 Nos
(n) Digital PF Meter - 01 Nos
(o) Quoted Rates inclusive of CT of suitable ratio ( to be fitted on existing LT Panel) and copper wire 2 core 2.5 Sqmm sheathed for connection between existing LT Distribution panel to Capacitor panel
Design,Supply, Install, testing and commissioning factory made and tested CPRI approved APFC capacitor bank 50 KVAR double door panel board out door type hood on top weather vermin proof cubical type platform mounted suitable for 415 Volts phase, 4 wire 50 Hz AC supply system all as specified and directed with necessary busbar arrangement insulated aluminium busbar 200 Amps rating for phase and 100 Amps for neutral 4 strips installed on porcelin insulators housed in separate bus chamber covered with heat shrinkable sleeves with necessary busbar tapings automatic power factor control relay and copper control wiring of required size, the panel shall be dust proof IP-54 class protection and made of 3 mm CRCA MS sheet with 50 X 50 X 6 mm angle Iron frame 30 Cm below ground level and 30 Cm above ground level with necessary earth work excavation, hinged door's front & Rear openings and locking arrangements duly power coated on the out side and inside including provision of PCC plat form 100 mm thick with PCC 1:4:8 type D2 using 40MM graded stone aggregate one metre all around the panel board, cable gland and lugs for incomming and out going cables etc independent chambers to accommodates complete all as specified and directed including the following accessories:- (Size of the panel board should not be less than 1.15 M X0.75 MX0.40M)
(a) MCCB 4 Pole 415 Volts 50 Hz 100 Amps Adjustable thermal magnetic release type with breaking capacity 25KA -01 As I ncoming
b) MCB TP 40 Amps 10 KA, 415 Volts - 03 Nos (Out going for capacitor )
c) MCB TP 20 Amps 10 KA, 415 Volts - 02 Nos (Out going for capacitor )
d) APP Power Factor Improvement Capacitor 3 Phase, 415 Volts 50 HZ ,20 KVAR - 01 Nos: 10 KVAR - 02 Nos and 5 KVAR - 02 Nos
(e) Power contactor TP 40 Amps - 03 Nos ( capacitor Duty)
(f) Power contactor TP 20 Amps - 02 Nos ( capacitor Duty)
(g) Digital Ammetor 0 to 100 Amps - 01 No
(h) Digital Volt meter 0 to 500 Volts
(j) Indicator Lamps LED Type Set 01 Set
(j) APFC controller 8 stage eta con of L&T model No ETACONM008R / equivalent - 01 Nos
(k) Digital PF Meter - 01 Nos
(l) Quoted Rates inclusive of CT of suitable ratio ( to be fitted on existing LT Panel) and copper wire 2 core 2.5 Sqmm sheathed for connection between existing LT Distribution panel to Capacitor panel
Design,Supply, Install, testing and commissioning factory made and tested CPRI approved APFC capacitor bank 40 KVAR double door panel board out door type hood on top weather vermin proof cubical type platform mounted suitable for 415 Volts phase, 4 wire 50 Hz AC supply system all as specified and directed with necessary busbar arrangement insulated aluminium busbar 200 Amps rating for phase and 100 Amps for neutral 4 strips installed on porcelin insulators housed in separate bus chamber covered with heat shrinkable sleeves with necessary busbar tapings automatic power factor control relay and copper control wiring of required size, the panel shall be dust proof IP-54 class protection and made of 3 mm CRCA MS sheet with 50 X 50 X 6 mm angle Iron frame 30 Cm below ground level and 30 Cm above ground level with necessary earth work excavation, hinged door's front & Rear openings and locking arrangements duly power coated on the out side and inside including provision of PCC plat form 100 mm thick with PCC 1:4:8 type D2 using 40MM graded stone aggregate one metre all around the panel board, cable gland and lugs for incomming and out going cables etc independent chambers to accommodates complete all as specified and directed including the following accessories:- (Size of the panel board should not be less than 1.00 M X0.75 MX0.40M)
(a) MCCB 4 Pole 415 Volts 50 Hz 100 Amps Adjustable thermal magnetic release type with breaking capacity 25KA -01 As I ncoming
b) MCB TP 40 Amps 10 KA, 415 Volts - 02 Nos (Out going for capacitor )
c) MCB TP 20 Amps 10 KA, 415 Volts - 01 Nos (Out going for capacitor )
c) MCB TP 10 Amps 10 KA, 415 Volts - 03 Nos (Out going for capacitor )
d) APP Power Factor Improvement Capacitor 3 Phase, 415 Volts 50 HZ ,20 KVAR - 01 Nos: 10 KVAR - 01 Nos and 5 KVAR - 01 Nos, 2 KVAR - 2 Nos and 1 KVAR 1 nos
(e) Power contactor TP 40 Amps - 02 Nos ( capacitor Duty)
(f) Power contactor TP 20 Amps - 04 Nos ( capacitor Duty)
(g) Digital Ammetor 0 to 100 Amps - 01 No
(h) Digital Volt meter 0 to 500 Volts
(j) Indicator Lamps LED Type Set 01 Set
(j) APFC controller 8 stage eta con of L&T model No ETACONM008R or equivalent - 01 Nos
(k) Digital PF Meter - 01 Nos
(l) Quoted Rates inclusive of CT of suitable ratio ( to be fitted on existing LT Panel) and copper wire 2 core 2.5 Sqmm sheathed for connection between existing LT Distribution panel to Capacitor panel
Design,,Supply, Install, testing and commissioning factory made and tested CPRI approved APFC capacitor bank 30 KVAR double door panel board out door type hood on top weather vermin proof cubical type platform mounted suitable for 415 Volts phase, 4 wire 50 Hz AC supply system all as specified and directed with necessary busbar arrangement insulated aluminium busbar 200 Amps rating for phase and 100 Amps for neutral 4 strips installed on porcelin insulators housed in separate bus chamber covered with heat shrinkable sleeves with necessary busbar tapings automatic power factor control relay and copper control wiring of required size, the panel shall be dust proof IP-54 class protection and made of 3 mm CRCA MS sheet with 50 X 50 X 6 mm angle Iron frame 30 Cm below ground level and 30 Cm above ground level with necessary earth work excavation, hinged door's front & Rear openings and locking arrangements duly power coated on the out side and inside including provision of PCC plat form 100 mm thick with PCC 1:4:8 type D2 using 40MM graded stone aggregate one metre all around the panel board, cable gland and lugs for incomming and out going cables etc independent chambers to accommodates complete all as specified and directed including the following accessories:- (Size of the panel board should not be less than 0.75 M X0.70 MX0.40M)
(a) MCCB 4 Pole 415 Volts 50 Hz 63 Amps Adjustable thermal magnetic release type with breaking capacity 25KA -01 As I ncoming
b) MCB TP 40 Amps 10 KA, 415 Volts - 02 Nos (Out going for capacitor )
c) MCB TP 20 Amps 10 KA, 415 Volts - 01 Nos (Out going for capacitor )
c) MCB TP 10 Amps 10 KA, 415 Volts - 03 Nos (Out going for capacitor )
d) APP Power Factor Improvement Capacitor 3 Phase, 415 Volts 50 HZ , 10 KVAR - 02 Nos and 5 KVAR - 01 Nos, 2 KVAR - 2 Nos and 1 KVAR 1 nos
(e) Power contactor TP 40 Amps - 02 Nos ( capacitor Duty)
(f) Power contactor TP 20 Amps - 04 Nos ( capacitor Duty)
(g) Digital Ammetor 0 to 100 Amps - 01 No
(h) Digital Volt meter 0 to 500 Volts
(j) Indicator Lamps LED Type Set 01 Set
(j) APFC controller 8 stage eta con of L&T model No ETACONM008R / equivalent - 01 Nos
(k) Digital PF Meter - 01 Nos
(l) Quoted Rates inclusive of CT of suitable ratio ( to be fitted on existing LT Panel) and copper wire 2 core 2.5 Sqmm sheathed for connection between existing LT Distribution panel to Capacitor panel
Supply , laying in trenches/fixed to walls/poles etc and CONNECTING BY USING LUGS OF APPROPRIATE SIZE and testing of XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor of 3.5 Core 300 Sqmm all as specified and directed.
Supply , laying in trenches/fixed to walls/poles etc and CONNECTING BY USING LUGS OF APPROPRIATE SIZE and testing of XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor of 3.5 Core 240 Sqmm all as specified and directed.
Supply , laying in trenches/fixed to walls/poles etc and CONNECTING BY USING LUGS OF APPROPRIATE SIZE and testing of XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor of 3.5 Core 185 Sqmm all as specified and directed.
Supply , laying in trenches/fixed to walls/poles etc and CONNECTING BY USING LUGS OF APPROPRIATE SIZE and testing of XLPE insulated and PVC sheathed heavy duty LT 1100 Volts grade armoured under ground cable with stranded aluminium conductor of 3.5 Core 95 Sqmm all as specified and directed.
Supply and Fixing of cable jointing kit for 1.1 KV grade cable for outdoor end termination heat shrinkable type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 sqmm to 150 sqmm complete all as specifide and directed.
Supply and Fixing of cable jointing kit for 1.1 KV grade cable for outdoor end termination heat shrinkable type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 185 sqmm to 300 sqmm complete all as specifide and directed.
Excavation in post holes (or similar holes) each n.exc 0.50 cu.m getting out in hard/dense soil , returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25cm complete all as specified and directed.
M&L PCC 1:3:6, type C-2 (using 40 mm graded crushed stone aggregate) in foundations, filling and mass concrete complete all as specified and directed.
M&L for framed works in posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe-290 Gde E-165 including dismantling of old fencing complete all as specified and directed.
Supply and fixing chain link MS galvanised fencing wire any size including line wires of weight not less than 3.08kg/sqm, to any type of standards rails, straining bolts etc., including provision of binding with mild steel wire annealed not less than 0.9mm dia etc. complete all as specified and directed.
M&L Applying two coats of synthetic enamel paint on steel surfaces of any description, over 10cm in width or girth, over a coat of primer incl preperation of new surfaces all as specified and directed
Surface excavation not exc 30 cm deep and averaging 15cm deep and getting out HARD / DENSE soil and romoving debries from site as directed
M&L for shingle filling on substation of Gauge 40 to 63 mm, deposited, spread and levelled in layers not exc. 150mm thick, watered and rammed to a True Surface, complete all as specified and as directed.
SANJEEV CONSTRUCTIONS
Electricals India
vvcenterprises
POWER CONSTRUCTION COMPANY
STANDARD AGENCIES
Sri Associates
Universal refrigeration and Engineering Company
eldi techs
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .