SPL REPAIR TO CIRCUIT BREAKERS OF PB SUB STATION I AND II UNDER GE UTILITIES UDHAMPUR
2021_MES_491441_1
CA NO CWE/U(U)-75/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
UDHAMPUR
As per tender documents
7 documents required · 7 mandatory
₹500
GE UTILITY UDHAMPUR
₹76,960
Yes
25 Jan 2022
30 Nov 2021
5 Jan 2022
30 Nov 2021
3 Jan 2022
18 Dec 2021
Amount
Drawing out the SF 6 / RMU from the Circuit system of 11 KV , Servicing the Circuit breaker by checking the following parameters for proper functioning using CTC for clear off the carbon deposited. a) Checking / fault diagnisis of Isolator & earth switch mechanism slips b) Checking of Gas inside the tank c) Checking the functionality of relay protection system d) Checking the Mechanism of isolator module and vcb module e) Checking the voltage presence indicator f) Checking the complete control wiring for tripping/ closing / indication system Necessary spare parts shall be measured as Supply only in following items Note : a) Servicing shall be performed by authorised service personnel of M/s ABB b) Servicing certficate shall be provided to engineer-in-charge. c) replacement of minor spares like Push button lever, Green push button, red push buttons and shaft for operating handles are inclusive of rate quoted by tenderer.
Supply & Fixing Spare parts of SF6/RMUs 630Amperes ( Make : M/s ABB ):-
a) 2 PA Mechanism w/o hex rod for VCB Module
b) ASHIDA ADR241S NANO Relay
c) Voltage Presence Indictor ( Capacitor unit & Chord )
d) SF6 Gas for RMU Tank ( 9 kg )
e) CT 200-100/1A 5P10 for protection
f) CT 200-100/1a, Ci.1 for metering
g) V module push button bracket
Supply,Installation,Testing and Commisioning of Indoor Type HT 11KV, 3Phase 50Hz,having rupturing capacity minimum 350 MVA totally metal clad withdraw able type Vacuum Circuit Breaker INCOMER panel with Copper bus bar of suitable rating, horizontal isolation type VCB of capacity 630 Amps rated current, as per IEC 62271-100-200. The switchgear panel shall be of sheet steel construction with ALUZINC not less than 2.5mm thickness for load bearing section and not less than 2 mm thickness for non-load bearing and shall be totally dust and vermin proof. The offered panels shall be tested for IAC level of 25kA/1 Sec., No. of operation of Vacuum Interrupter Bottles (ABB/Siemens/ Schneider make) for better performance: (i) Mechanical life -30,000 Nos , (ii) Rated Current – 10,000 Nos (iii) Rated Short Circuit Current – 100 nos.- All the main components like VI/ VCB/ Relays/ Meters shall be of same make.Approved Makes: ABB (Unigear) / Siemens (NX-Air) / Schneider (PIX). Panel and VCB parameters are as below: (i) Rated Voltage level/ PF withstand voltage/ Impulse level:12KV/ 28kV/ 75 kVp (ii) Continuous current rating: minimum 800 A
(iii) Short circuit withstand current: minimum 25KA for 3sec. (iv) One no. minimum 800 Amps horizontal draw out type vacuum circuit breaker in 12KV metal clad floor mounting panel complete with following:- (a)Manually & Motor operated(230V,AC,50Hz) spring charged type, manually and electrically open (electrical – 110 VDC) operation type, incorporating mechanical as well as electrical ON/OFF indication "OFF" push button, test/service position limit switches, with minimum 6NO+6NC breaker auxiliary contacts in service position. (b) Cast resin Current transformer 11KV, 150-200/5-5A, Core1: class1, 15VA for 3 phase , Core2: 5P10, 15VA, (c) Cast resin potential transformer 11KV/V3/110V/V3/110V/3, 50VA, Cl 1.0, Cl 3P and HT Fuse at the primary end and 04 pole MCB at the secondary end of the PT (Confirming related IS specifications). A) Protection arrangements for the breaker shall comprise of the following: ( i) E/F, O/C, S/C, TCS with MODBUS protocol - Numerical Type Siemens (Siprotec)/ ABB (REF series)/ Schneider (MICOM P111)
Supply,Installation,Testing and Commisioning of indoor type HT 11KV, 3Phase 50Hz,having rupturing capacity minimum 350 MVA totally metal clad withdraw able type Vacuum Circuit Breaker BUS COUPLER with RISER panel with Copper bus bar of suitable rating, horizontal isolation type VCB of capacity 630 Amps rated current, as per IEC 62271-100-200. The switchgear panel shall be of sheet steel construction with ALUZINC not less than 2.5mm thickness for load bearing section and not less than 2 mm thickness for non-load bearing and shall be totally dust and vermin proof. The offered panels shall be tested for IAC level of 25kA/1 Sec., No. of operation of Vacuum Interrupter Bottles (ABB/Siemens/ Schneider make) for better performance: (i) Mechanical life -30,000 Nos , (ii) Rated Current – 10,000 Nos (iii) Rated Short Circuit Current – 100 nos.- All the main components like VI/ VCB/ Relays/ Meters shall be of same make.Approved Makes: ABB (Unigear) / Siemens (NX-Air) / Schneider (PIX). Panel and VCB parameters are as below: (i) Rated Voltage level/ PF withstand voltage/ Impulse level:12KV/ 28kV/ 75 kVp (ii) Continuous current rating: minimum 630 A
(iii) Short circuit withstand current: minimum 25KA for 3sec. (iv) One no. minimum 630 Amps horizontal draw out type vacuum circuit breaker in 12KV metal clad floor mounting panel complete with following:- (a)Manually & Motor operated(230V,AC,50Hz) spring charged type, manually and electrically open (electrical – 110 VDC) operation type, incorporating mechanical as well as electrical ON/OFF indication "OFF" push button, test/service position limit switches, with minimum 6NO+6NC breaker auxiliary contacts in service position. (b) Cast resin Current transformer 11KV, 150-200/5-5A, Core1: class1, 15VA for 3 phase , Core2: 5P10, 15VA, (c) Cast resin potential transformer 11KV/V3/110V/V3/110V/3, 50VA, Cl 1.0, Cl 3P and HT Fuse at the primary end and 04 pole MCB at the secondary end of the PT (Conforming to related IS specifications). A) Protection arrangements for the breaker shall comprise of the following: ( i) E/F, O/C, S/C, TCS with MODBUS protocol - Numerical Type Siemens (Siprotec)/ ABB (REF series)/ Schneider (MICOM P111)
Supply,Installation,Testing and Commisioning of indoor type HT 11KV, 3Phase 50Hz,having rupturing capacity minimum 250 MVA totally metal clad withdraw able type Vacuum Circuit Breaker OUTGOING panel with Copper bus bar of suitable rating, horizontal isolation type VCB of capacity 400 Amps rated current, as per IEC 62271-100-200. The switchgear panel shall be of sheet steel construction with ALUZINC not less than 2.5mm thickness for load bearing section and not less than 2 mm thickness for non-load bearing and shall be totally dust and vermin proof. The offered panels shall be tested for IAC level of 25kA/1 Sec., No. of operation of Vacuum Interrupter Bottles (ABB/Siemens/ Schneider make) for better performance: (i) Mechanical life -30,000 Nos , (ii) Rated Current – 10,000 Nos (iii) Rated Short Circuit Current – 100 nos.- All the main components like VI/ VCB/ Relays/ Meters shall be of same make.Approved Makes: ABB (Unigear) / Siemens (NX-Air) / Schneider (PIX). Panel and VCB parameters are as below: (i) Rated Voltage level/ PF withstand voltage/ Impulse level:12KV/ 28kV/ 75 kVp (ii) Continuous current rating: minimum 400 A
(iii) Short circuit withstand current: minimum 25KA for 3sec. (iv) One no. minimum 400 Amps horizontal draw out type vacuum circuit breaker in 12KV metal clad floor mounting panel complete with following:- (a)Manually & Motor operated(230V,AC,50Hz) spring charged type, manually and electrically open (electrical – 110 VDC) operation type, incorporating mechanical as well as electrical ON/OFF indication "OFF" push button, test/service position limit switches, with minimum 6NO+6NC breaker auxiliary contacts in service position. (b) Cast resin Current transformer 11KV, 150-200/5-5A, Core1: class1, 15VA for 3 phase , Core2: 5P10, 15VA, (c) Cast resin potential transformer 11KV/V3/110V/V3/110V/3, 50VA, Cl 1.0, Cl 3P and HT Fuse at the primary end and 04 pole MCB at the secondary end of the PT (Confirming related IS specifications). A) Protection arrangements for the breaker shall comprise of the following: ( i) E/F, O/C, S/C, TCS with MODBUS protocol - Numerical Type Siemens (Siprotec)/ ABB (REF series)/ Schneider (MICOM P111)
Notes for Srl Item No 3 to 5.02:- Retrieved Circuit Breakers shall be deposited to the AGE E/M E/S with proper ledger taking over by JE. (ii) Any B/R related items required during erection of circuit breakers shall be deemed to be included in the rates quoted by the tenderer.
Taking down the old / deterioted HT Cable from the Substation . Supply & fix for XLPE insulated, armoured, aluminium conductor cable, 11000 volts grade, heavy duty, cross sectional area 95 sq mm ,3 core, laid in trenches/ducts/through pipe complete all as specified and directed by Engr-in-Charge.
Cable jointing kit for 11 KV grade cable for out door termination heat shrinkable type joint complete with jointing material and acessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sq.mm complete all as specified and directed by Engr-in-Charge.
M & L for providing earthing with Copper earth plate electrode 600 X 600 X 3.15 mm buried directly in ground (earth pit not less than 2.25M deep below ground level ) with top edge of the earth plate not less than 1.5M below ground level connected to copper strip 20x3 mm thick for earthing lead fixed by means of nuts,bolt,washers etc connected to earth test point complete all as specified in electrical plate NO 3 of SSR 1996 part 1 ,including necessary excavation and earth work in any strata of soil,comman salt, charcoal dust, 40 mm dia light grade GI pipe for protection to earth lead, GI water pipe 20mm dia with funnel &wire mesh , PCC pit with CI cover and frame etc all as specified and directed by Engineer-in-charge. Note:- (a) All the joints shall be made with welding to get proper conductivity. (b) Copper Earth strip GI 32 x6 mm shall be provided till the earth pit which may be beyond 7.5 mtrs
Excavating in trenches, n exc 1.5 m wide and n.exc 1.5 m in depth; for laying cables/pipes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth in any type of soil and getting out soil, complete all as specified and as directed by Engr-in-Charge.
Returning filling in (soil) including spreading leveling watering and well ramming in layers not exceeding 25cm thick, all as specified.
Removal of excavated material (soil) to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5m above the starting point all as specified.
Supply and lay DWC Pipe ( Double wall corruguated) confirming to IS: 14930(Part-II) along with necessary Snap fit Coupler for interconnection Suitable for HT Cable of size 95 sq.mm (90/76 mm as diameter) all as specified & directed by Engineer in charge .
MOHAN LAL AND SONS
FANGALIA TRADERS
proach associates
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .