Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.3 LAccepted-AOC SWAGAT CO OP HSG SOCIETY LTD 22 303 CHAITANYA SHIVAJI RAJE COMPLEX MHADA COMPLEX OPP EKA NAGAR KANDIVALI W MUMBAI 400 067 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400067 | L1 | Accepted-AOC AOC | |
| 2 | L2₹30.9 L+₹2.6 L (9.33%)Rejected-Finance B 101 SURAJ TOWER MIRA BHAYANDER ROAD OPP SAI PETROL PUMP MIRA ROAD EAST THANE 401107 | MIRA ROAD EAST | THANE | MAHARASHTRA | 401107 | L2 | Rejected-Finance Other Than Being Lowest | |
| 3 | L3₹31.0 L+₹2.7 L (9.55%)Rejected-Finance 1 14 SUJAL MANSION B BLOCK BHANGWADI KALBADEVI ROAD MUMBAI 400 002 | MUMBAI | MAHARASHTRA | 400002 | L3 | Rejected-Finance Other Than Being Lowest | |
| 4 | L4₹31.5 L+₹3.2 L (11.5%)Rejected-Finance | L4 | Rejected-Finance Other Than Being Lowest | |
| 5 | L5₹35.7 L+₹7.4 L (26.3%)Rejected-Finance ROOM NO D 297 PART III GANESH MURTI NAGAR CUFF PARADE ROAD COLABA MUMBAI 400005 | MUMBAI | MAHARASHTRA | 400005 | L5 | Rejected-Finance Other Than Being Lowest |
| Sl No | Description | Qty | Unit | cooltech engineering services L1 | Saviour Security Systems L2 | Chakshu Enterprise L3 | GANGAJAL L5 | shubham construction L4 |
|---|---|---|---|---|---|---|---|---|
| 1.00 | Supplying, Installation, Testing & Commissioning of Fire Alarm Control Panel
1.Type: Microprocessor-based, Networkable, Analogue Addressable Fire Alarm Control Panel.
2.Capacity: Minimum 2 loops with 10–15% spare capacity.
Each loop capable of supporting minimum 99 detectors and 99 analog addressable devices.
3.Display & Interface:
Minimum 600-character LCD/LED display.
Minimum 4 access levels for operator security.
4.Memory & Processing:Capable of taking Flash Scan devices.
Equipped with flash EPROM memory.
5.Controls & Monitoring:Programmable relay controls for integration with:
(a)AHUs (Air Handling Units)
(b)Pressurization fans
(c)Ventilation fans at Fire Pump Room
(d)Monitoring of Fire Sprinkler and Fire Hydrant Pumps
6.Power Supply:
240V AC primary power supply.
Automatic battery charger with standby battery backup as per IS/UL standards.
7.Compliance:
Panel shall conform to relevant NFPA/UL/EN/IS standards.
Complete in all respects as specified and directed by Engineer-in-charge at site. MAKE- Honeywell/SiemensBosch/Morley | 4 | Each | 1,36,000 ₹5,44,000 | 1,70,000 ₹6,80,000 | 1,81,000 ₹7,24,000 | 1,85,000 ₹7,40,000 | 1,10,000 ₹4,40,000 Lowest |
| 2.00 | Supplying, Fixing, Testing & Commissioning of Multi-Sensor Detectors
1.Type & Compliance: Addressable type, multi-sensor detectors (Heat + Smoke combination).
Certified to EN-45 series (for fire detection & alarm systems).
Designed as per IS:11360 requirements.
2.Detection Principle:
Photoelectric/optical smoke detection combined with heat sensing element.
Equipped with self-built intelligence (on-board microprocessor for signal processing, false alarm rejection).
3.Construction & Mounting:
With mounting base and LED indicator for local alarm status.
Suitable for installation above ceiling & below ceiling areas.
Supplied with suitable enclosures, glands, and mounting accessories as required.
4.Interface & Compatibility:
Fully compatible with the analogue addressable fire alarm control panel (AFC).
Detectors shall have a unique address and be capable of loop communication.
5.Installation & Testing:
Supply, fixing, connection, and testing shall be carried out as per manufacturer’s instructions and relevant IS/NBC codes.
Work executed under the direction of the Engineer-in-Charge. MAKE- Honeywell/SiemensBosch/Morley | 249 | Each | 2,340 ₹5,82,660 Lowest | 2,975 ₹7,40,775 | 2,700 ₹6,72,300 | 2,700 ₹6,72,300 | 4,000 ₹9,96,000 |
| 3.00 | Supply, Installation, Testing & Commissioning Addressable Manual Call Point with resettable (Pull down/Break Glass type). The device shall have an LED which shall blink in normal state and get steady on activation to monitor the health status of the device and shall be UL listed, semi flush type complete all as specified and directed by Engineer_in_charge.
MAKE- Honeywell/SiemensBosch/Morley | 17 | Each | 3,540 ₹60,180 | 3,900 ₹66,300 | 2,700 ₹45,900 | 2,647 ₹44,999 Lowest | 4,500 ₹76,500 |
| 4.00 | Supply, Installation, Testing & Commissioning of LED type Remote response indicator with steady glowing LED as per specifications for Above celling detectors & Cabin Detectors complete all as specified and directed by Engineer-in-Charge.MAKE- Honeywell/SiemensBosch/Morley | 60 | Each Job | 125 ₹7,500 Lowest | 200 ₹12,000 | 190 ₹11,400 | 1,400 ₹84,000 | 1,500 ₹90,000 |
| 5.00 | Supply, Installation & Testing of Short Circuit Isolators, fault isolator module with automatic resetting arrangement as per specification (UL Listed) complete all as specified and directed by Engineer-in-Charge. MAKE- Honeywell/SiemensBosch/Morley | 24 | Each | 3,120 ₹74,880 | 2,400 ₹57,600 | 2,200 ₹52,800 Lowest | 3,700 ₹88,800 | 4,200 ₹1,00,800 |
| 6.00 | Supplying, Installing, Testing & Commissioning of Fire Alarm Sounders / Sirens
1)Type & Operation:
Electronic type, horizontal mounting, two-stage fire alarm sounders/sirens.
Built-in amplifier unit with two-tone generator (alarm tones selectable).
2)Performance:
Capable of continuous normal operation for at least 50 minutes.
3)Sound level: 65 dB to 120 dB measured at 1.5m distance.
Sound output variation: ±5 dB with effective range up to 100m.
4)Construction:
Rugged and reliable design, suitable for indoor or outdoor installation as per site requirements.
Housing to be dust and moisture-resistant (IP-rated as per standard).
5)Power & Compatibility:
Compatible with the analogue addressable fire alarm system.
Operable on the system’s supply voltage with built-in protection.
6)Compliance & Standards:
Conforms to IS / EN-54 / UL standards for fire alarm sounders.
7)Installation & Commissioning:
Proper fixing, wiring, loop integration, testing, and commissioning to be carried out & complete work executed under the supervision of the Engineer-in-Charge. MAKE- Honeywell/SiemensBosch/Morley | 18 | Each | 4,956 ₹89,208 | 4,500 ₹81,000 Lowest | 4,500 ₹81,000 Lowest | 7,847 ₹1,41,246 | 7,800 ₹1,40,400 |
| 7.00 | Supply & laying PVC FRLS armoured cable 1.5sq mm solid copper conductor 2 core, XLPE Insulated, Extruded PVC sheathed, galvanized steel strip, electric power cables (heavy duty) 1100 Volts grade including all accessories (thimbles/lugs and cable gland etc complete) laid in duct / along pole/wall etc including making connection complete and making good the distrubed surface matching with existing surface complete all as specified and directed by Engineer-in-Charge. | 5,450 | RM | 150 ₹8,17,500 | 145 ₹7,90,250 | 160 ₹8,72,000 | 185 ₹10,08,250 | 90 ₹4,90,500 Lowest |
| 8.00 | Material and labour, rigid non mettalic FRLS PVC conduit exclusive of boxes (Junction/Terminal), but inclusive of all tees, bends elbows, reducers, bell mouth tube ends and fixing accessories, such as couplers, lock nuts, saddles, pipe hooks etc complete all as specified and directed by Engineer-in-Charge.. | 590 | RM | 75 ₹44,250 | 150 ₹88,500 | 35 ₹20,650 Lowest | 65 ₹38,350 | 80 ₹47,200 |
| 9.00 | Supplying installation, Testing & Commissioning of Addressable control modules suitable for integration with microprocessor based addressable fire alarm system, UL listed, two wire configuration, controlling and monitoring fire alarms/ sprinklers/ fire dampers etc, auto addressing, LED indicators, short circuit protection etc.as per tender specificaiton complete all as specified and as directed by Engineer-in Charge..
Make : Honeywell/Siemens/Morley/Siemens | 4 | Each | 3,680 ₹14,720 | 3,500 ₹14,000 | 2,950 ₹11,800 Lowest | 4,700 ₹18,800 | 4,500 ₹18,000 |
| 10.00 | Supplying installation, Testing & Commissioning of Addressable monitor modules, two wire, microelectronic device to interface with Heat/Smoke detectors, provide system address for each connected device, compatible with Fire control panel including necessary wiring etc as per tender specification complete all as specified and as directed by Engineer-in Charge.
MAKE- Honeywell/SiemensBosch/Morley | 4 | Each | 3,250 ₹13,000 | 3,450 ₹13,800 | 2,500 ₹10,000 Lowest | 2,700 ₹10,800 | 4,500 ₹18,000 |
Tender Value
₹39 L
EMD Value
₹78,000
Closing Date
1 Dec 2025, 6:00 pmClosed
CWE (NW) Mumbai
CWE (NW) Mumbai
PROVISION OF AUTOMATIC FIRE DETECTION SYSTEM AT C 92 MCM BLDG NO T 65 OF DAS FACTORY C NO 13 NWRF DEPT UNDER GE NW KUNJALI AT NAVAL DOCKYARD MUMBAI
2025_MES_738408_1
8489/CWE(NW)Mumbai/E8
Open Tender
Civil Works
Item Rate
150 days
GE (NW) Kunjali
Class D category c (vi)
7 documents required · 7 mandatory
₹500
GE (NW) Kunjali
₹78,000
Yes
16 Feb 2026
4 Nov 2025
3 Dec 2025
4 Nov 2025
1 Dec 2025
26 Nov 2025
4 Nov 2025 - 25 Nov 2025
Amount
Supplying, Installation, Testing & Commissioning of Fire Alarm Control Panel 1.Type: Microprocessor-based, Networkable, Analogue Addressable Fire Alarm Control Panel. 2.Capacity: Minimum 2 loops with 10–15% spare capacity. Each loop capable of supporting minimum 99 detectors and 99 analog addressable devices. 3.Display & Interface: Minimum 600-character LCD/LED display. Minimum 4 access levels for operator security. 4.Memory & Processing:Capable of taking Flash Scan devices. Equipped with flash EPROM memory. 5.Controls & Monitoring:Programmable relay controls for integration with: (a)AHUs (Air Handling Units) (b)Pressurization fans (c)Ventilation fans at Fire Pump Room (d)Monitoring of Fire Sprinkler and Fire Hydrant Pumps 6.Power Supply: 240V AC primary power supply. Automatic battery charger with standby battery backup as per IS/UL standards. 7.Compliance: Panel shall conform to relevant NFPA/UL/EN/IS standards. Complete in all respects as specified and directed by Engineer-in-charge at site. MAKE- Honeywell/SiemensBosch/Morley
Supplying, Fixing, Testing & Commissioning of Multi-Sensor Detectors 1.Type & Compliance: Addressable type, multi-sensor detectors (Heat + Smoke combination). Certified to EN-45 series (for fire detection & alarm systems). Designed as per IS:11360 requirements. 2.Detection Principle: Photoelectric/optical smoke detection combined with heat sensing element. Equipped with self-built intelligence (on-board microprocessor for signal processing, false alarm rejection). 3.Construction & Mounting: With mounting base and LED indicator for local alarm status. Suitable for installation above ceiling & below ceiling areas. Supplied with suitable enclosures, glands, and mounting accessories as required. 4.Interface & Compatibility: Fully compatible with the analogue addressable fire alarm control panel (AFC). Detectors shall have a unique address and be capable of loop communication. 5.Installation & Testing: Supply, fixing, connection, and testing shall be carried out as per manufacturer’s instructions and relevant IS/NBC codes. Work executed under the direction of the Engineer-in-Charge. MAKE- Honeywell/SiemensBosch/Morley
Supply, Installation, Testing & Commissioning Addressable Manual Call Point with resettable (Pull down/Break Glass type). The device shall have an LED which shall blink in normal state and get steady on activation to monitor the health status of the device and shall be UL listed, semi flush type complete all as specified and directed by Engineer_in_charge. MAKE- Honeywell/SiemensBosch/Morley
Supply, Installation, Testing & Commissioning of LED type Remote response indicator with steady glowing LED as per specifications for Above celling detectors & Cabin Detectors complete all as specified and directed by Engineer-in-Charge.MAKE- Honeywell/SiemensBosch/Morley
Supply, Installation & Testing of Short Circuit Isolators, fault isolator module with automatic resetting arrangement as per specification (UL Listed) complete all as specified and directed by Engineer-in-Charge. MAKE- Honeywell/SiemensBosch/Morley
Supply & laying PVC FRLS armoured cable 1.5sq mm solid copper conductor 2 core, XLPE Insulated, Extruded PVC sheathed, galvanized steel strip, electric power cables (heavy duty) 1100 Volts grade including all accessories (thimbles/lugs and cable gland etc complete) laid in duct / along pole/wall etc including making connection complete and making good the distrubed surface matching with existing surface complete all as specified and directed by Engineer-in-Charge.
Material and labour, rigid non mettalic FRLS PVC conduit exclusive of boxes (Junction/Terminal), but inclusive of all tees, bends elbows, reducers, bell mouth tube ends and fixing accessories, such as couplers, lock nuts, saddles, pipe hooks etc complete all as specified and directed by Engineer-in-Charge..
Supplying installation, Testing & Commissioning of Addressable control modules suitable for integration with microprocessor based addressable fire alarm system, UL listed, two wire configuration, controlling and monitoring fire alarms/ sprinklers/ fire dampers etc, auto addressing, LED indicators, short circuit protection etc.as per tender specificaiton complete all as specified and as directed by Engineer-in Charge.. Make : Honeywell/Siemens/Morley/Siemens
Supplying installation, Testing & Commissioning of Addressable monitor modules, two wire, microelectronic device to interface with Heat/Smoke detectors, provide system address for each connected device, compatible with Fire control panel including necessary wiring etc as per tender specification complete all as specified and as directed by Engineer-in Charge. MAKE- Honeywell/SiemensBosch/Morley
Supplying, Installing, Testing & Commissioning of 1 KVA Online UPS System 1.Capacity & Type: 1 KVA Online UPS system, designed specifically for powering Fire Alarm & Control Panel. Equipped with inbuilt battery backup and suitable accessories. 2.Performance Features: (a)True sine wave output – 230V AC. (b)Power factor correction for efficient load handling. (c)Boost function for low input voltage conditions. (d)Over-voltage, overload, and short-circuit protection. 3.Battery Backup: (a)Integrated sealed maintenance-free (MF) batteries. (b)Battery backup capacity of minimum 2 days (48 hours) under system load requirements. 5.Construction & Protection: (a)Rugged, reliable design with automatic changeover. (b)Complete with protective circuitry for safe and uninterrupted operation. 6.Certification: UL Listed and conforming to relevant IS/NFPA/IEC standards for UPS systems used in life-safety applications. 7.Installation & Commissioning: Includes supply of UPS, batteries, cabling, terminations, accessories, and testing. Work to be carried out as per manufacturer’s recommendations and under the supervision of the Engineer-in-Charge.
Supply, Installation of carbon-di-oxide fire extinguisher of capacity 5 Kilogram consisting of welded Mild Steel Cylindrical body, squeeze lever discharge valve fitted with internal discharge tube, 300mm long high pressure discharge hose, discharge nozzle, suspension bracket, IS:15683 marked, finishing externally with red enamel paint and fixed to wall with brackets with rawl plug/dash fasteners with internal charge, complete all as specified and as directed by Engineer-in Charge.
Supply and Fix heavy duty, fire retardant, FRLS PVC junction box 4 way/ terminal connectors incl all accessories screws, plugs etc of required size complete all as specified and as directed by Engineer-in Charge.
Supply and fixing of PVC DLP - On wall trunking of size 80mmx50mm body with cover including all finishing accessories, partitions, joints, variable interior and exterior angles, end caps, joint of lid, joint of body, derivation, support for mounting cable clips, cable ties etc complete all as directed by Engineer-in Charge.
Supply and fixing of PVC DLP - On wall trunking of size 105mmx50mm body with cover including all finishing accessories, partitions, joints, variable interior and exterior angles, end caps, joint of lid, joint of body, derivation, support for mounting cable clips, cable ties etc complete all as directed by Engineer-in Charge.
Supply and fixing perforated GI cable tray made out of sheet thickness not less than 1.6mm ,50 mm height of tray and width not less than 350mm fixed on any wall (brick/stone) vertically/ horizontally, including tray cover of thickness not less than 2.00mm, including all accessories complete bending, shaping, drilling, welding, cutting and including all fixing arrangement such as suitable size of nuts, bolts, coupler plates etc complete all as specified and directed by Engr-in-charge.
Saviour Security Systems (BID ID -3491922)
Chakshu Enterprise (BID ID -3492627)
shubham construction (BID ID -3486576)
GANGAJAL (BID ID -3486407)
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.41 MB
BOQ_826807.xls
BOQ • 0.37 MB
8489.rar
Tender Documents • 3.21 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .