| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.3 CrAccepted-AOC | ₹14.3 Cr | L1 | Accepted-AOC Being Lowest Bidder |
| 2 | L2₹15.1 CrRejected-Finance | ₹15.1 Cr | L2 | Rejected-Finance Not Lowest Bidder |
| 3 | L3₹15.6 CrRejected-Finance | ₹15.6 Cr | L3 | Rejected-Finance Not Lowest Bidder |
| 4 | L4₹15.6 CrRejected-Finance | ₹15.6 Cr | L4 | Rejected-Finance Not Lowest Bidder |
| 5 | L5₹16.0 CrRejected-Finance 00 00 NAPASAR ROAD NENO KA BASS BIKANER RAJASTHAN BIKANER RAJASTHAN 334022 UDYAM RJ 08 0001676 | BIKANER | RAJASTHAN | 334022 | ₹16.0 Cr | L5 | Rejected-Finance Not Lowest Bidder |
Tender Value
₹14.5 Cr
EMD Value
₹10.5 L
Closing Date
20 Sept 2021, 6:00 pmClosed
Chief Engineer Bathinda
HQ Chief Engineer Bathinda, Bathinda Mil Stn
PROVISION OF KLP (PH-I) (SW-182) AT SURATGARH MIL STN
2021_MES_463324_2
CA NO CE BTZ SOG TOKEN of 11 OF 2021-22
Open Tender
Civil Works
790 days
Suratgarh Mil Stn
As per NIT
8 documents required · 8 mandatory
₹3,000
Garrison Engineer (A) Suratgarh
₹10.5 L
Yes
29 Sept 2021
1 Sept 2021
22 Sept 2021
1 Sept 2021
20 Sept 2021
15 Sept 2021
1 Sept 2021 - 11 Sept 2021
Amount
Sch 'A' Sec - I, ( BUILDING/STRUCTURE WORK)
Lump sum price worked out by the Contractor for **Rs. ______________ “Building Work / Structure Work” as listed in Schedule ‘A’ Section - I Representing ** _______ % ____________ percent *Above / Below the lump sum price on col 5 inserted by the MES in Schedule ‘A’ Section I
Sch 'A' Sec - II ( Part-I) (INTERNAL ELECTRIFICATION WORKS)
Lump sum price worked out by the Contractor for **Rs. ______________ “Internal Electrification” as listed in Schedule ‘A’ Section - II (Part-I) Representing ** _______ % ____________ percent *Above / Below the lump sum price on col 5 inserted by the MES in Schedule ‘A’ Section II (Part-I)
Sch 'A' Sec - II ( Part-II) (INTERNAL ELECTRIFICATION WORKS)
Material and Labour Flame proof Point wiring with 1.5 Sqmm nominal area PVC insulated FRLS unsheathed and stranded copper conductor cable in and including ERW rigid conduit stove enamelled ) 20mm dia concealed conduit for light point/Fan point/ 5 Amp switch socket with other than FP junction box, FP bend, FP reducer independent for One light points controlled by one flame proof rotary switch including copper wire as specified above for earth wire to common earth and connected to earth dolly complete all as specified . Following and all other flame proof fitting for wiring shall be incorporated in wiring as required basis and cost there of shall be included in the rate quoted. (a) Flame proof junction box 3 way suitable for 20mm ERW conduit material. (b) Flame proof bend suitable for 20mm ERW conduit material. (c) Flame proof union suitable for 20mm dia ERW conduit material.
Supply and fixing LED lamp minimum 3 star rated 5 W LED Bulb B-22 base including lamp holder complete all as specified and directed by Engr - in Charge with following specification:- (a) Lumen system efficacy of luminaire should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to plus 45° (d) Power factor : Minimum 0.90 (e) CRI : More than 80
Supply and fixing LED lamp minimum 3 star rated 10 W LED Bulb B-22 base including lamp holder complete all as specified and directed by Engr-in-Charge with following specification:- (a) Lumen system efficacy of luminaries should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to plus 45° (d) Power factor : Minimum 0.90 (e) CRI : More than 80 as specified.
Wiring with TV coaxial RG-6 heavy duty PVC insulated sheathed cable with copper conductor having single strand of 0.7 mm dia and a copper wire net for TV antenna from terminal boxes to TV socket complete all as specified (conduit pipe and fittings shall be measured and paid separately).
GI box flush mounted 100mm x100mmx100mm having holes for 20 mm conduit entry including 2 pin TV socket outlet flush type duly marked with symbol of TV and 3 mm thick plastic laminated sheet cover complete for TV connection all as specified.
Wiring with twin core PVC insulated sheathed cable with copper conductor having single strand of 0.6 mm dia taped for telephone wiring from terminal box to telephone socket complete all as specified (conduit and conduit accessories shall be measured and paid separately).
GI box flush mounted 100mm x100mmx100mm having holes for 20 mm conduit entry including 3 pin telephone socket outlet flush type duly marked with symbol of telephone and 3 mm thick plastic laminated sheet cover complete for telephone connection all as specified.
Ceiling fan 1200 mm sweep 5 star rated (26 Watt plus/minus 10%) with brushless direct current motor (BLDC) with service value 6.00 BEE single phase, AC supply, 240 Volt, including canopies, three number blades, down rod, double ball bearing with capacitor of 2.5 mfd and making connection with and including PVC insulated PVC sheathed copper conductor flexible cable 3 core of suitable size from ceiling rose or connector to fan including marking of MES number complete all as specified. NOTE:The length of suspension rod shall be as per site requirement.
All as per item No. 13 here-in-before but 1400 mm sweep 33 watt plus/minus 10%
All as per item No.15 here-in-before including note but 230 mm sweep plastic body
Cabin fan plastic body energy efficient 400 mm sweep 240 volts, single phase, 50 c/s AC supply ISI marked fixed on wall with necessary fasteners, nuts, bolts and washers etc complete all as specified . NOTE- The cabin fan is to be fixed on wall with all necessary T&P and other accessories required shall be deemed to be included in the above item no extra payment will be admissiable on this account.
Supply and fixing LED light complete fitting surface/recessed mounted including batten and T-8 Retro LED polycarbonate 1 x 20 Watt, approx 4 feet long, environment friendly, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to tube fitting complete fitting with all accessories and following specification all as directed by Engr - in Charge:- (a) Lumen system efficacy of luminaries should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Max 10% (f) IP rating : IP -20 (g) CRCA pre coated housing with two coloured plastic end cap. (h) LED Driver of the make as of the luminaries. (J) LED driver should be complete with all protection viz open/short circuit protection, over voltage protection, all as per standard design of manufacture. (k) Surge protection minimum 2.5 KV (l) CCT : 6500K (m) CRI : More than 80 (n) Rated life time 50000 burning hrs (Average 10 to 12 hrs daily) equivalent in makes mentioned in Appendix 'B' here-in-after.
Supply and fixing LED light complete fitting surface/recessed mounted including batten and T-8 Retro LED polycarbonate 2 x 20 Watt, approx 4 feet long, environment friendly, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to tube fitting complete fitting with all accessories and following specification all as directed by Engr - in Charge:- (a) Lumen system efficacy of luminaries should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Max 10% (f) IP rating : IP -20 (g) CRCA pre coated housing with two coloured plastic end cap. (h) LED Driver of the make as of the luminaries. (J) LED driver should be complete with all protection viz open/short circuit protection, over voltage protection, all as per standard design of manufacture. (k) Surge protection minimum 2.5 KV (l) CCT : 6500K (m) CRI : More than 80 (n) Rated life time 50000 burning hrs (Average 10 to 12 hrs daily)
Supply and fixing flame proof LED light complete fitting surface/recessed mounted including batten and T-8 Retro LED polycarbonate 1 x 20 Watt, approx 4 feet long, environment friendly, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to tube fitting complete fitting with all accessories and following specification all as directed by Engr - in Charge:- (a) Lumen system efficacy of luminaries should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Max 10% (f) IP rating : IP -20 (g) CRCA pre coated housing with two coloured plastic end cap. (h) LED Driver of the make as of the luminaries. (J) LED driver should be complete with all protection viz open/short circuit protection, over voltage protection, all as per standard design of manufacture. (k) Surge protection minimum 2.5 KV (l) CCT : 6500K (m) CRI : More than 80 (n) Rated life time 50000 burning hrs (Average 10 to 12 hrs daily)
Supply and fixing LED mirror light fitting 1 x 5 Watt, including LED lamp extruded polycarbonate environment friendly, including electric with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to tube fitting complete fitting with all accessories and following specification all as directed by Engr - in Charge:- (a) Lumen system efficacy of luminaries should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to plus 45° (d) Power factor : Minimum 0.95 (e) THD : Max 10% (f) IP rating : IP -20 (g) CRCA pre coated housing with two coloured plastic end cap. (h) LED Driver of the make as of the luminaries. (j) LED driver should be complete with all protection viz open/short circuit protection, over voltage protection, all as per standard design of manufacture. (k) Surge protection minimum 2.5 KV (l) CCT : 6500K (m) CRI : More than 80 (n) Rated life time 50000 burning hrs (Average 10 to 12 hrs daily)
Supply and fixing COB LED light 1 X 70W complete fitting wall/roof mounted high bay beam suspended industrial including LED Lamp, aluminium dia cast heat sink for efficient heat dissipation with aluminium reflector including driver complete suitable body robust , origin resistant, superior finish without any cracks through holes environmental friendly including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to tube fitting complete fitting with all accessories and following specification all as directed by Engr - in Charge:- (a) Lumen system efficacy of luminaries should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Max 10% (f) IP rating : IP -65 (g) CRCA pre coated housing with two coloured plastic end cap. (h) LED Driver of the make as of the luminaries. (J) LED driver should be complete with all protection viz open/short circuit protection, over voltage protection, all as per standard design of manufacture. (k) Surge protection minimum 2.5 KV (l) CCT : 6500K (m) CRI : More than 80 (n) Rated life time 50000 burning hrs (Average 10 to 12 hrs daily)
Supply and fixing COB LED light 1 X 50 W complete fitting wall/roof mounted high bay beam suspended industrial including LED Lamp, aluminium dia cast heat sink for efficient heat dissipation with aluminium reflector including driver complete suitable body robust , origin resistant, superior finish without any cracks through holes environmental friendly including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to tube fitting complete fitting with all accessories and following specification all as directed by Engr - in Charge:- (a) Lumen system efficacy of luminaries should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Max 10% (f) IP rating : IP -65 (g) CRCA pre coated housing with two coloured plastic end cap. (h) LED Driver of the make as of the luminaries. (J) LED driver should be complete with all protection viz open/short circuit protection, over voltage protection, all as per standard design of manufacture. (k) Surge protection minimum 2.5 KV (l) CCT : 6500K (m) CRI : More than 80 (n) Rated life time 50000 burning hrs (Average 10 to 12 hrs daily)
Supply and fixing energy efficient LED street light fitting of 1 X 25 watt pressure die cast alumunium housing/body, heat resistant clear toughened glass, better optics for uniform distribution street/Roadway luminare, with driver, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to tube fitting complete fitting with all accessories and following specification all as directed by Engr - in Charge:- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max 10% (f) IP rating : IP -66 (g) IK rating : IK07 (h) CRCA pre coated housing with two coloured plastic end cap. (j) LED Driver of the make as of the luminaire. (k) LED driver should be complete with all protection viz open/short circuit protection, over voltage protection, all as per standard design of manufacture. (l) Surge protection minimum 10 KV (inbuilt + extended) (m) CCT : 5700K (m) CRI : Minimum 70 (n) Lens: High efficiency wide angle lens (o) BIS approved fixtures and driver (p) Rated life time 50000 burning hrs (Average 10 to 12 hrs daily)
Note for item No – 07, 08 & 18 to 24 (a) Contractor shall submit LM - 79 and LM - 80 reports obtain from manufactures . (b) Contractor shall to furnish a replacement warranty of 05 years for LED light fittings complete including lamps from the date of completion of CA. The product will be replaced including taking down and re-fixing new luminary free of cost in the following case :- (i) Manufacturing defects. (ii) Failure due to mechanical and electrical impact. (iii) Drop in luminary (or Lux at 1 mtr) below 90% of claimed values of lumens (or Lux at 1 mtr) of the LED luminaries. (c) All LED light/luminary must meet the provision laid down in IS - 16101 , 16102 Part -I/II ,16103 Part -I , 16104 ,16105 ,16106 , 16108/2012 and 15885 Part -II / Section 13. (d) Minor items required for completion of job are included in overall cost quoted by Contractor. Nothing extra shall be payable on this account.
RCBO, 63 Amp, 300mA, TPN, type confirming to IS, suitable 415 volts, AC supply, breaking capacity not less than 10 kA, , complete all as specified.
RCBO, 40 Amp, 300mA, TPN, type confirming to IS, suitable 415 volts, AC supply, breaking capacity not less than 10 kA, , complete all as specified.
RCBO, 20 Amp, 300mA, TPN, type confirming to IS, suitable 415 volts, AC supply, breaking capacity not less than 10 kA, , complete all as specified.
RCBO, 16 Amp, 300mA, TPN, type confirming to IS, suitable 415 volts, AC supply, breaking capacity not less than 10 kA, , complete all as specified.
MCB suitable for 240 volt AC supply, SP with over load and short circuit protection and rupturing capacity not less than 10 kA, 'C' curve type of rating 40 Amp complete all as specified.
Blanking plate of plastic and fixed in location (Suitable for distribution board)
Subtotal
Sch 'A' Sec - III (Part-I) (Internal Water Supply)
Lump sum price worked out by the Contractor for **Rs. ______________ “Internal Water Supply" as listed in Schedule ‘A’ Section - III(Part-I) Representing ** _______ % ____________ percent *Above / Below the lump sum price on col 5 inserted by the MES in Schedule ‘A’ Section III(Part-I).
Sch 'A' Sec - III (Part-II) (Internal Water Supply)
Angle valve, cast copper alloy, chromium plated, high pressure with quarter turn handle screwed ends for iron pipe or for unions and fixed suitable for 15 mm nominal bore iron pipe complete all as specified.
Sch 'A' Sec - IV, (Part-I) (Sewage Disposal Work)
Lump sum price worked out by the Contractor for **Rs. ______________ “Sewage Disposal Work" as listed in Schedule ‘A’ Section - IV (Part-I) Representing ** _______ % ____________ percent *Above / Below the lump sum price on col 5 inserted by the MES in Schedule ‘A’ Section IV (Part-I).
Sch 'A' Sec - IV, (Part-II) (Sewage Disposal Work)
DWCPE (SN8) confirming to IS-16098, 150 mm nominal bore complete laid in trenches and jointed including testing with and including necessary jointing material tees/ union/ socket etc complete as per manufacturers instructions. NOTES:- (i) Earth work shall be measured & paid for separately under respective items of Schedule 'A'/BoQ. (ii) The rate of necessary tees/ union/ socket/ other accessories of same material and size of pipe is included in this item and nothing shall be paid extra on this account.
Sch 'A' Sec - V, (Part-I) (Road Work)
Lump sum price worked out by the Contractor for **Rs. ______________ “Road Work" as listed in Schedule ‘A’ Section - V(Part-I), Representing ** _______ % ____________ percent *Above / Below the lump sum price on col 5 inserted by the MES in Schedule ‘A’ Section V(Part-I).
Sch 'A' Sec - V, (Part-II) (Road Work)
Thermo plastic road marking 2 mm thick painting (lines, dashes, arrow, letters etc on new road surfaces) with road safety spikeries glass beads including preparation of new road surfaces and applying paint by using special applicator machine with heating arrangement complete all as specified and as directed .
Delinator made out of acrylic material fitted with high intensity retro reflector in yellow, red colour fitted on CRCA pipe 40mm dia and 60cm long powder coated or stove enamelled white/black colour provided with steel wire mesh made up into cage for safety of reflector and embedding the same in PCC (1:2:4) type B-1 using 20mm graded stone aggregate size 300x300x450mm including necessary excavation & removal of spoil complete all as specified & directed by Engineer-in-charge.
Dual directional reflective cat eye of size 100mmx100mm of inpact resistance ABS plastic sstud having violet resistance color with plastic strip containing 31 mini retro reflective glass beads of colour white/red/yellow to each side and fixed with 12mm dia 120mm long zinc plated steel nails at the centre of cats eye of hammering comlete all as specified and directed by Engineer-incharge.
Rectangular sign Board Double legged informatory Eco boards of size 900mm x 600mm fixed on single frame. The board shall be of high intensity of required colour grade retro-reflective sheeting of AVERY DENNISOX made out of 2mm thick alco bond sheet to be covered with high intensity grade retro reflective sheeting, fixed to structural steel frame work of MS pipe of size 35x35mm square pipe with nut bolt/rivets ensuring safety against removal of planted, the lettering is computerized cut of high intensity grade white and black alternative bands of 25cm each with synthetic enamel paint and fixed through PCC block (1:3:6) of size 300mmx 300mmx 450mm complete all specified abd directed by Engr-in-Charge.
Tringular/Round sign Board of 600mm sides/dia single legged informatory Eco boards fixed on single frame. The board shall be of high intensity of required colour grade retro-reflective sheeting of AVERY DENNISOX made out of 2mm thick alco bond sheet to be covered with high intensity grade retro reflective sheeting, fixed to structural steel frame work of MS pipe of size 35x35mm square pipe with nut bolt/rivets ensuring safety against removal of planted, the lettering is computerized cut of high intensity grade white and black alternative bands of 25cm each with synthetic enamel paint and fixed through PCC block (1:3:6) of size 300mmx300mmx 450mm complete all specified abd directed by Engr-in-Charge.
Subtotal
Sch 'A' Sec - VI (Path and Culvert Work)
Lump sum price worked out by the Contractor for **Rs. ______________ “ Path and Culvert Work" as listed in Schedule ‘A’ Section - VI , Representing ** _______ % ____________ percent *Above / Below the lump sum price on col 5 inserted by the MES in Schedule ‘A’ Section VI).
Sch 'A' Sec - VII (AREA DRAINAGE WORKS)
Lump sum price worked out by the Contractor for **Rs. ______________ “AREA DRAINAGE WORKS" as listed in Schedule ‘A’ Section - VII , Representing ** _______ % ____________ percent *Above / Below the lump sum price on col 5 inserted by the MES in Schedule ‘A’ Section VII).
Sch 'A' Sec - VIII (SECURITY FENCING WORKS)
Lump sum price worked out by the Contractor for **Rs. ______________ “SECURITY FENCING WORKS" as listed in Schedule ‘A’ Section - VIII , Representing ** _______ % ____________ percent *Above / Below the lump sum price on col 5 inserted by the MES in Schedule ‘A’ Section VIII).
Sch 'A' Sec -IX (COMPOUND WALL & STEEL GATES WORKS)
Lump sum price worked out by the Contractor for **Rs. ______________ “COMPOUND WALL & STEEL GATES WORKS" as listed in Schedule ‘A’ Section - IX , Representing ** _______ % ____________ percent *Above / Below the lump sum price on col 5 inserted by the MES in Schedule ‘A’ Section IX).
Sch 'A' Sec - X (Part-I), (External Water Supply works)
Lump sum price worked out by the Contractor for **Rs. ______________ “External Water Supply Works” as listed in Schedule ‘A’ Section - X (Part-I)Representing ** _______ % ____________ percent *Above / Below the lump sum price on col 5 inserted by the MES in Schedule ‘A’ Sec - X (Part-I) .
Sch 'A' Sec - X (Part-II), (External Water Supply works)
Ductile Iron pressure pipe 200 mm bore with socket and spigot end, Class K-9, conforming to IS: 8329/2000 - blast furnace slag cement with portland cement properties suitable for push-on-jointing (Rubber gasket) with inside cement mortar lining with internal metallic zinc coating and external Black Bitumen coating, duly ISI marked and DI fittings complete all as specified and as directed by Engr-in-charge. Note:- DI specials/fittings & joints and rubber gasket shall be measured and paid seperately.
All as per item No. 61 here-in-before but 150 mm bore
All as per item No. 61 here-in-before but 100 mm bore
Ductile iron fitting such as bends (any type, radius and angle) tappers any type, (straight, bend, increasing, decreasing or double socket etc) tee pieces single branch ‘Y’ junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs etc. of size upto 200 mm dia complete all as specified and directed.
Note for Item No 61 to 64 : Make of pipe and fittings should be same. Alternatively fittings should be of make recommended by pipe manufacturer
Supply, installation, commissioning and testing of centrifugal pump set, electric motor driven, discharge capacity not less than 8 LPS at 40 mtr head, suitable for pumping clear water, comprising of the following specification :- (i) Pump, centrifugal type, horizontal, split casing, 1440 rpm, discharge not less than 8 LPS at 40 mtr head having bronze impeller and stainless steel shaft, single stage directly coupled with electric motor through flexible tyre coupling with coupling guard. (ii) Squirrel cage indication motor, TEFC, 3 Phase 415±10 Volts 50 C/S, AC supply not less than 15 HP, 1500 rpm directly coupled to centrifugal pump set including all electrical connection, PVC insulated unsheathed single core 6 sqmm size multistranded pvc insulated copper cables upto electric panel six runs in PVC conduit. (iii) Common base foundation of ICMC - 100 suitable for installation of above pump set duly drilled holes and painted with two coats synthetic enameled paint over a coat of red oxide primer. (iv) PCC foundation in CM 1.3.6 type C2 using 40 mm graded aggregate, 30 cm above GL and 15 cm below GL and as per size of common base foundation/ standard engg practice. (v) Bourdons type pressure gauge 3" dia dial type SS body with check valve. (vi) rate of suitable size of suction pipe matching with pumps and addition/alteration of suction and delivery side of pipe including nuts, bolts, washers, rubber gasket etc shall be deemed to be included in the rate quoted” (vii) Pre-commissioning of pump sets shall be carried out by the rep of accepting officer. Nothing extra shall be payble on the account.
Cast Iron Sluice valve flanged Type, class PN-1.0, 150 mm bore ISI marked conforming to IS- 14846-2000 complete with stainless steel spindle flanged both ends drilled CI gate with brass ring and iron wheel handle suitable for CI/DI pipe line including gasket joint, nut, bolts (high tensile) and washers etc complete all as specified.
All as per item No. 67 here-in-before but 200 mm bore
All as per item No. 67 here-in-before but 350 mm bore
All as per item No. 67 here-in-before but 80 mm bore
Cast iron body foot valve for 100 mm dia pipe ISI mark confirming to IS 4038 with neoprene rubber gasket joint, nut bolts (high tensile), washers etc complete all as specified
Supply, installation, commissioning and testing of Silent Diesel Engine driven Generating set, capacity 20 KVA, outdoor type, 415 volts, 3 phase 4 wire, 1500 RPM, liquid cooled engine as per IS:10001/ 10002 and brushless Alternator as per IS:13364 complete with foundation (as per OEM design), electronic type governer, PF 0.8, control panel with Microprocessor controller with necessary meter and sound proof canopy as per CPCB norms and maintenance free battery as per IS: 14257, inbuilt battery charger (when no run) and suitable size 3.5 core XLPE armoured electric cable from DG set to changeover of electric panel of pump set and connection complete.
Item No. 72 contd/- (a) Diesel engine: Diesel engine 4 stroke water cooled electric start of suitable BHP at 1500 RPM suitable for above output of alternator at 47°C, 50% RH and conforming to BS 5514, BS 649, IS 10000 capable of taking 10 % over loading for one hour after 12 hour of continuous operation. The engine will be fitted complete with all the required accessories. (b) Engine mounted instrument panel fitted with and having digital display for following:- (i) Start top switch with key. (ii) Water temperature indication. (iii)Lubrication oil temperature indication. (iv) Battery charging indication. (v) RPM indication (vi) Over speed indication. (vii) Low lubrication oil trip indication (viii) Engine hour indication. (c) Alternator- synchronous alternator rated at 20 KVA, 415 Volts at 1500 RPM 3 Phase 50 Hz, AC supply with 0.8 lagging power factor at 47°C, 50 % RH. The alternator shall be having SPDP enclosure, brushless, continuous duty, self excitation and self regulated through AVR confirming to IS - 4722/BS 2613 suitable for tropical conditions and with class F/H insulations.
Item No. 72 contd/- (d) Base frame and foundation. Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendation of manufacturer. (e) Fuel Tank. In built fuel tank for 12 hours fuel capacity, fabricated out of 3 mm thick MS sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class C pipe of suitable dia complete with valves. Level indication and accessories as required as per specification. (f) Exhaust system Dry exhaust manfold with hospital exhaust silencer and catalytic converter (g) Starting system. 12 V/24 V starting system comprising of starter motors, Voltage regular and arrangement for initial excitation complete with suitable Nos of maintenance free batteries as per manufacturer design
Construction of brick masonary valve pit chamber size 110 X110 X90 cm (internal dimension) using sub class 'B' bricks complete including excavation & earth work, PCC 1:4:8 type D-2 using 40 mm graded stone aggregate in foundation, coping on top in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate, inner plaster 15 mm thick in cm 1:4 MS sheet cover 3 mm thick mounted on angle iron frame of size 40 x 40 x6 mm with locking arrangement duly painted with two coats of synthetic enamel paint over a coat of primer red oxide complete all as specified and directed.
All as per item No. 76 here-in-before but valve pit chamber of size 150 X150 X110
Supply, installing, commissioning and testing of factory made Indoor type LT cubical panel board suitable for operation on 415 Volts, 3 phase, 4 wire, 50Hz supply system including bus bar chamber in center (vertically) and cable allay either side, shell shall be made out of 2.0 mm thick CRCA sheet duly powder coated siemens gray shade and completely weather, vermin & dust proof, adequate air ventilation at sides & back with hinges and locking arrangements half nob type without key type suitable to accommodate the following mentioned fittings and compartmentalized for each control gear including front openable single door including provision for taking out incoming and outgoing cables duly marked with riveted letter plates of appropriate size for each feeder/block cable, danger board, detachable plate at bottom for cable entry etc. and MC 100 pedestal for grouting in floor with suitable nut, bolts, washers etc. including foundation and comprising the following :-
Cutting existing CI/DI pipe line of 350 mm and inserting DI fittings, collar / tail piece, Tee reducer flanged type including any addition/ alteration required for connection and including required earth work, excavation, returning filling, spreading/ leveling complete all as specified and directed by Engr-in-charge. Note: Rate includes the DI Tee fittings and any other material required for connection
Subtotal
Sch 'A' Sec - XI (Part-I), (External Electric Supply Works)
Lump sum price worked out by the Contractor for **Rs. ______________ “External Water Supply Works” as listed in Schedule ‘A’ Section - XI (Part-I)Representing ** _______ % ____________ percent *Above / Below the lump sum price on col 5 inserted by the MES in Schedule ‘A’ Sec - XI (Part-I) .
Sch 'A' Sec - XI (Part-II), (External Electric Supply Works)
Sand cushioning using clean local tibba fine sand for underground cable 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of cable complete all as specified. Note:- Punned thickness shall be considered for payment purpose.
Supply of HT 12 KV, 3 Phase 50 Hz, Totally metal clad withdraw able type Vacuum Circuit Breaker panel with Copper bus bar of suitable rating, horizontal isolation type VCB of capacity minimum 630 Amps rated current, as per IEC 62271-100-200. The offered panels shall be tested for IAC level of 25 kA, For better performance: (i) mechanical life – 30,000, (ii) Rated Current -10,000 & (iii) Rated Short Circuit operations – 100. Panel and VCB parameters are as below: (i) Rated Voltage level/PF with stand voltage/impulse level: 12 KV/28 KV/75 kVp. (ii) Continuous current rating : minimum 630 A (iii) Short circuit with stand current: minimum 25 KA (iv) One No, minimum 630 Amps horizontal draw out type vacuum circuit breaker in 12 KV metal clad floor clad floor mounting panel complete with following:-
Item No. 86 Contd/- (a) manually & motor operated (230 V, AC, 50 Hz) spring charged type, manually and electrically open (electrical - 24 VDC) operation type, incorporating mechanical as well as electrical ON/OFF indication “OFF” push button, test/service position limit switches, with minimum 6 No + 6NC breaker auxiliary contacts in service position. (b) Epoxy cast wound current transformer (CT), 12 KV of ratio 200-100/5+5A, 5P 10/1.0, 15 VA burden with metering and protection core including necessary control wiring. (A) Protection arrangements for the breaker shall comprise of the following: (i) E/F, O/C. TCS with IEC 103 protocol for communication – numerical Type Schneider (Easergy) (ii) Master Trip Relay, (iii) Aux, Transformer protection relay. All relays shall belong to a common platform and shall be of single make with Electromechanical Relays.
40mm dia (size suitable for fitted Flood/ street light fitting) 1.5 metre long GI pipe light grade bracket for fixing of light fitting made to shape at including MS clamps (FI Plate 25X6mm as per site requirement) 02 Nos and nut and bolts complete will welding of drilling as required at site complete all as specified and directed
Cable junction box of size not less than 300x200x105 mm, made out of high quality thermo plstic polystyrene, weather proof, dust jet water proof, chemical, acid corrison, impact, insulated & shock proof IP66/67 for outdoor installation with internally embedded gasket (PUR) including the box fitted with connector 8 way 40 amps 01 No including Emlex stud type TB 4Nos incoming/ outcoming cable at controlled with MCB SP 6 Amps 01 No & enclosed along pole with MS flat iron clamp of suitable size and including MCB to street light terminals with PVC sheathed cable of copper wire, PVC insulated of size 1.5 sqmm 3 core etc complete all as specified and directed.
Supply and fixing energy efficient LED street light fitting of 1 X 45 watt pressure die cast aluminum housing/body, heat resistant clear toughened glass, better optics for uniform distribution street/Roadway luminary, with driver, including electric connection with using 1100 volt grade, FRLS PVC insulated stranded Aluminium conductor cable PVC sheathed 2.5 sqmm flat or circulator twin core cable including 20mm dia PVC rigid conduit (heavy duty) ISI marked fixed alongwith pole including all fixing arrangments i.e pvc clamp, raw plug, screw terminal etc, specification all as directed by Engr - in Charge:- (a) Lumen system efficacy of luminaries should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max 10% (f) IP rating : IP -66 (g) IK rating : IK07 (h) CRCA pre coated housing with two coloured plastic end cap. (j) LED Driver of the make as of the luminary. (k) LED driver should be complete with all protection viz open/short circuit protection, over voltage protection, all as per standard design of manufacture. (l) Surge protection minimum 10 KV (inbuilt + extended) (m) CCT : 5700K (m) CRI : Minimum 70 (n) Lens: High efficiency wide angle lens (o) BIS approved fixtures and driver (p) Rated life time 50000 burning hrs (Average 10 to 12 hrs daily)
Note For Item No 91 : (a) Contractor shall submit LM - 79 and LM - 80 reports obtain from manufactures (b) Contractor has to furnish a replacement warranty of 05 years for LED light fittings complete including lamps from the date of completion of CA. The product will be replaced including taking down and re-fixing new luminary free of cost in the following case :- (i) Manfacturing defects. (ii) Failure due to mechanical and electrical impact. (iii) Drop in lumen (or lux at 1 m) below 90% of clamied values of lumen(or lux at 1 m) of the LED /Luminaries. (c) All LED light/luminare must meet the provision laid down in IS - 16101, 16102 Part -I/II,16103 Part -I, 16104,16105,16106,16108/2012 and 15885 Part -II / Section 13. (d) Minor items required for completion of job are included in overall cost quoted by Contractor. Nothing extra shall be payable on this account
Supply, installing, commissioning and testing LT panel board (Outdoor type) cubical type made out of CRCA sheet 3.15 mm thick dust and vermin proof and angle iron of size 50mm x 50mm x 6mm, pedestal frame grouted in PCC (1:2:4) type B-1 20mm graded crushed stone aggregates, thimbles , cable entry boxes with cable glands of cast copper alloys . Panel should covered from all sides with front and back lock able door and hinges complete with aluminium bus bar of capacity 400 Amps, FP, Three phase,04 wire(in separate chamber) including painting with two coats of epoxy powder coating paint over a coat of red oxide primer and consisting of the following :-
Supply, installation, commissioning and testing of LT panel board (Outdoor type) cubical type made out of CRCA sheet 3.15 mm thick dust and vermin proof and angle iron of size 50mm x 50mm x 6mm, pedestal frame grouted in PCC (1:2:4) type B-1 20mm graded crushed stone aggregates, thimbles , cable entry boxes with cable glands of cast copper alloys . Panel should covered from all sides with front and back lock able door and hinges complete with aluminium bus bar of capacity 150 Amps, FP, Three phase,04 wire(in separate chamber) including painting with two coats of epoxy powder coating paint over a coat of red oxide primer and consisting of the following :-
Sheet metal enclosure TPN DB concealed with wall having facility to fix MCB TPN as incomer and MCBs in outgoing, TP vertical type 4 way of double door, complete fitted with bus bars, neutral links, G frame including S&F 4 pole MCB 16 Amp capacity, 50 Hz, 10 KA Breaking capacity, blanking plates including making good disturbed surfaces complete all as specified and directed.
Subtotal
Sch 'A' Sec - XII (Part-I), (SUMMER COOLING APPLIANCES WORKS)
Lump sum price worked out by the Contractor for **Rs. ______________ “SUMMER COOLING APPLIANCES WORKS” as listed in Schedule ‘A’ Section - XII (Part-I)Representing ** _______ % ____________ percent *Above / Below the lump sum price on col 5 inserted by the MES in Schedule ‘A’ Sec - XII (Part-I) .
Sch 'A' Sec - XII (Part-II), (SUMMER COOLING APPLIANCES WORKS)
Supply, install , commissioning of Frost free single door refrigerator electric driven single phase 230 volts, AC 50 Hz,of capacity minimum 350 litre with BEE approved, 5 star rating with inbuilt stablizer complete including electric connection through buck/ boost transformer complete all as specified.
Supply, install , commissioning of Water cooler fully stainless steel, electric driven single phase having storage capacity 60 litre and nominal cooling capacity 120 litre per hour mounted on locatiion as directed complete including connecting and making electric connection complete
Supply, install , commissioning of Water cooler fully stainless steel, electric driven single phase having storage capacity 40 litre and nominal cooling capacity 80 litre per hour mounted on locatiion as directed complete including connecting and making electric connection complete.
Supply, install , commissioning of Evaporative air cooler in steel body(Desert cooler) made out of hot dip galvanised steel thickness 1 mm body and 2 mm (removable sides and back panels) single phase 230 volts of fan size 450 mm sweep with submersible pump of suitable size (maximum power consumption 250 watts) having normal air flow 4000 cum per hr including 15mm bore float valves,high pressure, with polythene float and fly nut, including 15mm bore Stop valve, cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends ,nuts,washers, PVC connections of 15mm bore , leakage proof joints and all the necessary arrangmemnts to take water from GI Pipe medium grade 15mm bore to air cooler.
Subtotal
Sch 'A' Sec - XIII (Part-I), (HOT WATER SUPPLY WORKS)
Lump sum price worked out by the Contractor for **Rs. ______________ “Hot Water Supply Works” as listed in Schedule ‘A’ Section - XIII (Part-I)Representing ** _______ % ____________ percent *Above / Below the lump sum price on col 5 inserted by the MES in Schedule ‘A’ Sec - XIII (Part-I) .
Sch 'A' Sec - XIII (Part-II), (HOT WATER SUPPLY)
Electric operated single phase Water storage heater (geyser), vertical type of capacity 25 liter, five star rating, with 2 KW heating element complete having vitreous enamel coated tank, single weld line tank made of ultra thick superior cold rolled steel, inlet & outlet provision, safety device and fixing the with provision of suitable size fastener, bolts & washers and making connections with & including 15 Amp plug top having indicating light AC 230 V including writing MES No. etc. as directed complete all as specified.
Staging for cold storage tank ( Cap 500 litre) for hot water supply with 55 x 55 x 10 mm rolled steel angle with a height of not less than 1.8 mtr height as legs and 1.2 mtr x 1.2 mtr fr base frame with plate thickness 6 mm for PVC storage tank and cross arms, fixed in PCC foundation 1:2:4 type B-1 with size 300 x 300 x 300 mm with floor and adequate support for PVC storage tank for wind velocity including two coats of synthetic enamel paint after one coat of red oxide primer all as specified.
Subtotal
Sch 'A' Sec - XIV, (Site clearance, Earth Work and Development of land works)
Lump sum price worked out by the Contractor for **Rs. ______________ “Site clearance, Earth Work and Development of land works" as listed in Schedule ‘A’ Section - XIV Representing ** _______ % ____________ percent *Above / Below the lump sum price on col 5 inserted by the MES in Schedule ‘A’ Section XIV.
ENGINEER CONSTRUCTION PVT. LTD.
VIJAY JINDAL BUILDERS PVT LTD
M/s Jatindra Construction Company
A S CONSTRUCTION COMPANY
ASHISH JINDAL BUILDERS PVT. LTD.
Sood Enterprises
M/s Kataria Construction Company
M/s Khanna Enterprises
Saru Enterprises Pvt Ltd
Rabina Enterprises Pvt Ltd
Pawansut Infra Projects Pvt. Ltd.
SOM BUILDERS
Shekhar Enterprises
M/s. Shiva Engineers
stage.html
html • 0.08 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.