Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance BLOCK S HOUSE 75 MOHAN GARDEN WEST DELHI DELHI 110059 | WEST DELHI | DELHI | 110059 | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance GRAM POST SATHIYAV MUBARAKPUR DISTRICT AZAMGARH | AZAMGARH | UTTAR PRADESH | 223221 | Admitted-Finance |
| 5 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹14,000
Closing Date
21 May 2020, 4:00 pmClosed
Superintending Engineer
ETC, Patharhiya Road, Mirzapur
Maintenance of 132/33 KV Sub-Station Robertsanj under ETD, Robertsganj.
2020_UPTCL_462254_1
04/2020-21/ETC/Mzp
Open Tender
Electrical Works
Fixed-rate
365 days
Robertsganj
As per tender specification
2 documents required · 2 mandatory
₹1,652
Executive Engineer, ETD
₹14,000
Yes
28 May 2020
25 Apr 2020
22 May 2020
25 Apr 2020
21 May 2020
25 Apr 2020
Amount
Annual Maintenance of 132/33 KV sub-station Robertsganj under ETD Robertsganj.
Routine checking and maintenance work of (1X40+1X63) MVA T/F including checking and maintenance of oil level in conservator, OLTC gear casing , divertor switching, breather, bushing, oil leakage, silica gel colour, AC supply, noise and vibrations etc. complete the job satisfactorily with all man and T&P ( Required consumable materials shall be provided by department.)
Routine checking and maintenance of 132 KV & 33 KV CTs and PTs including checking of oil level, oil leakage and filling of t/f oil upto required level, cleaning of dust on insulator, tightening of wiring on TB in junction box. Complete the job satisfactorily with all men and T&P (Consumable material shall be provided by department.)
Periodical checking and maintenance of capacitor bank by the way of visual examination of bank for fouling, leakage of capacitor unit, oil level and oil leakage, cleaning of insulators and bushings. complete the job satisfactorily with all man and T&P ( Required consumable materials shall be provided by department.)
Changing of Interrupter in 33 KV CB pole by conducting following works : i. Opening of existing Jumpers of damaged CB Pole interrupter. Ii. Dismantling of damged CB pole interrupter by opening of upper termainal plate of CB pole. Iii. Replacement of defective pole interrupter by new one,fixing of interconnecting rod and fixing of upper terminal plate and then checking the CB mechanism for proper operation. iv.Shifting of all scrap/damged part to store.
Replacement of defective/damaged CB pole by conducting following works: - i.Opening of Jumpers of defective/damaged pole by dismantling after detaching it from operating shaft of the CB. Ii.Shifting of the defective/damaged pole from switchyard to store and shifting of the new / good condition pole, from store to the site. iii.Erection of the good condition dismantled/new pole and get it connected with CB operating Shaft and then get jumpers connected to the pole. iv.Shifting of all scrap/damged part to store.
Daily reading and entry of Voltage rating & Specific Gravity of Battery Cell in battery register & Quarterly maintenance of battery sets of following specification & rating by way of cleaning, make up of distilled water, greasing & tightening of leads of Battery set. Complete the job satisfactorily in all respect by providing neccesary man power and T&P ( Consumable Materials shall be provided by department.)
110 V 200 AH Battery Set (55 cell)
General cutting & cleaning of grass in switchyard, around store building ,connecting roads by brroming and disposing of garbages as per required with all man ,materils and T&P provided by contractor.
Daily general cleaning and maintenance of control room, associated office, battery room, cleaning of washroom, wsah basin along with cleaning of associated toilets cover at sub-station with Acid, Phenyl/Harpic etc. including cost of men, material and T&P.
Cleaning of jungles including up-rooting of rank vegitation grass, bushes and scrapping of grass above 2 cms over ground level, collection of foreign materials, papers, plastics including cleaning of drainage, trench cover Complete the job satisfactorily using herbisides with all man and T&P .
First cutting between within 3 month of LOI/Agreement date
Second cutting after three month of First cutting
Third cutting after three month of second cutting
Fourth cutting after three month of third cutting
Tightening of nuts bolts, cleaning of insulators, and replacement of defective clamps and connecter of various equipment in all 132 &33 kv bays in 132/33 KV switchyard Complete the job satisfactorily with all man and T&P. ( Materials shall be provided by department.)
First job in the month of March-April (before summer season ) as per availability of shutdown
Second job in the month of September-October (before festive season ) as per availability of shutdown
Replacement of damaged Jaw/blades of 132KV & 33 KV isolators by the way of opening of defective jaw and blade its tightening after removing connected jumpers and its proper re-jumpering including lubricating of Jaw/Blade .Complete the job satisfactorily with all man and T&P . ( Materials shall be provided by department.)
132 KV side
33 KV side
Replacement of jumper from bus-bar to equipment
1 x Panther
2 x Panther
2 x Moose
Replacement of jumpers from equipments to equipments
1X Panther
2x Panther
2x Moose
Dismantling of following equipments by opening of nut and bolts, opening of jumpers, cable connections, earthing and shifting up to store/designated place in the yard as per direction of supervising engineer at 132kV sub-station Robertsganj.
145KV instrument transformer (CTs, PPTs, CVTs)
145KV post insulator
120KV lightning arrester
36 KV 3 phase VCB
36KV 1-Phase CT
36KV 1-Phase PT
30KV 1-phase LA
32/22/18KV post insulator
Erection of following equipment as per instruction manual of various equipments and technical specification including shifting of material/ equipment item store to erection site including all other associated work to complete the job satisfactory.at 132kV sub-station Mirzapur
145KV instrument transformer (CTs, PPTs, CVTs,)
145KV post insulator
120KV lightning arrester
36 KV 3 phase VCB
36KV 1-Phase CT
36KV 1-Phase PT
30KV 1-phase LA
32/22/18KV post insulator
Removal of complete sodium/LED light fitting assembly from poles/tower/ plateform building etc.
Upto 10 Meter
Fixing of sodium/LED light fitting assembly from poles/tower/ plateform building etc.
Upto 10 Meter
In junction/Marshalling box
Replacement of MCB
Replacement of fuse grip
Replacement of light junction box
Replacement of damaged Control/Power cable in original position including taking out damaged cable from cable trench and shifting to Store.
M/S MIEENAKSHI ENTERPRISES
M/S AJAI AND BROTHERS ENTERPRISES
M/S KSHITIJ ENTERPRISES
M/S SHANTI ENTERPRISES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .