Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.0 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹44.9 L+₹1.7 L (4.04%)Rejected-Finance | L2 | Rejected-Finance No Lowest | |
| 3 | L3₹45.2 L+₹2.0 L (4.69%)Rejected-Finance 101 1ST FLOOR JASOL RESIDENCY 14TH CROSS KANAKANAGAR R T NAGAR POST BANGALORE 560032 | BANGALORE | BANGALORE | KARNATAKA | 560032 | L3 | Rejected-Finance No Lowest | |
| 4 | L4₹45.5 L+₹2.3 L (5.36%)Rejected-Finance NO 131 5TH CROSS PASCHIM COUNTY MEDARAHALLI CHIKKABANAVRA POST BANGALORE 560 090 | BENGALURU URBAN | KARNATAKA | 560090 | L4 | Rejected-Finance No Lowest | |
| 5 | L5₹45.8 L+₹2.6 L (6.04%)Rejected-Finance | L5 | Rejected-Finance No Lowest |
Tender Value
Refer Docs
EMD Value
₹80,000
Closing Date
7 Nov 2022, 6:00 pmClosed
GE North Bangalore
GARRISON ENGINEER NORTH BANGALORE T 64 MEANEE LINES MEG AND CENTRE BANGALORE 560042
REPAIRS REPLACEMENT OF INTERNAL WIRING FANS AND OTER E M MISC WORKS IN OTM ACCN AT MEG CENTRE CONVERSION OF OLD HPSV LIGHT FITTING TO LED LIGHT FITTINGS REPLACEMENT OF EXISTING RCC POLES PAINTING POLES AT MEG CENTRE BANGALORE
2022_MES_558044_1
8344
Open Tender
Electrical and Maintenance Works
Item Rate
45 days
BLORE
Class D Category b(i)
7 documents required · 7 mandatory
₹500
GARRISON ENGINEER NORTH BANGALORE
₹80,000
Yes
14 Nov 2022
17 Oct 2022
9 Nov 2022
17 Oct 2022
7 Nov 2022
24 Oct 2022
17 Oct 2022 - 24 Oct 2022
Amount
(INTERNAL ELECTRIFICATION WORKS - E/M PORTION)
Taking down carefully aluminium/ copper wiring/power point wiring (light, fan, call bell socket or power circuits), without taking out switches, sockets, regulators, light fittings, etc., complete and making good the disturbed surface of walls, ceiling etc including painting with same colour of the back ground complete all as specified and as directed by Engineer-in-Charge.
Material and labour for Concealed Point Wiring complete with 1.5 Sq mm single core PVC insulated unsheathed cable 1100 volts grade multi stranded with FRLS copper conductor conforming to IS 694 drawn through and including non-metallic rigid PVC conduit medium grade ISI marked including accessories concealed in walls including MS terminal boxesfabricated with 1.6 mm thick MS sheet, covering with laminated sheet top cover 3 mm thick fixed with cadmium plated iron screws for housing the switches, switch socket outlets, fan regulators etc., including provision of 1.5 Sq mm PVC insulated single core multi stranded copper conductor cable as earth continuity conductor and connecting to common earth dolly, all as specified and as directed for One light point controlled by one switch / One fan point controlled by one switch/regulator.
All as per Serial Item No 2 here-in-above, but for one light point controlled by 2 way switch
All as per Serial Item No 2 here-in-above, but for one 3 pin socket outlet 5 Amps on independent board.
All as per Serial Item No 2 here-in-above, but for one 3 pin socket outlet 5 Amps on Same Board. Notes for serial item Nos 2 to 11 :- (i) Earth wire for points in the same circuit can be looped from point to point, (ii) Earth wire shall be taken inside the conduit, (iii) Cost of terminal box shall deemed to be included in the item rate quoted for point wiring, (iv) Cost of cable from DB to any switch/ socket board to be included in point wiring. (v) Cutting chases, grooving, etc., as required for taking down / providing concealed wiring shall be measured and paid for separately under respective item.
Material and labour for Point Wiring complete with 1.5 Sq mm single core PVC insulated unsheathed cable 1100 volts grade multi stranded with FRLS copper conductor conforming to IS 694 drawn through and including PVC Casing & Capping ISI marked including accessories surface type wiring including 1.6 mm thick MS sunken boxes concealed on walls including laminated sheet top cover 3 mm thick fixed with cadmium plated iron screws for housing the switches, switch socket outlets, fan regulators etc., including provision of 1.5 Sq mm PVC insulated single core multi stranded copper conductor cable as earth continuity conductor and connecting to common earth dolly, all as specified and as directed for One light point controlled by one switch / One fan point controlled by one switch/regulator.
All as per Serial Item No 6 here-in-above, but for one light point controlled by 2 way switch
All as per Serial Item No 6 here-in-above, but for one 3 pin socket outlet 5 Amps on independent board.
All as per Serial Item No 6 here-in-above, but for one 3 pin socket outlet 5 Amps on Same Board.
Material and labour for Concealed Point Wiring complete with 2.5 Sq mm single core PVC insulated unsheathed cable 1100 volts grade multi stranded with FRLS copper conductor conforming to IS 694 drawn through and including non-metallic rigid PVC conduit medium grade ISI marked including accessories concealed in walls including MS terminal boxes / modular boxes fabricated with 1.6 mm thick MS sheet, covering with laminated sheet top cover 3 mm thick fixed with cadmium plated iron screws for housing the switches, switch socket outlets, fan regulators etc., including provision of 2.5 Sq mm PVC insulated single core multi stranded copper conductor cable as earth continuity conductor and connecting to common earth dolly, all as specified and as directed for power socket point of 15 Amps
Material and labour for Point Wiring complete with 2.5 Sq mm single core PVC insulated unsheathed cable 1100 volts grade multi stranded with FRLS copper conductor conforming to IS 694 drawn through and including PVC Casing & Capping ISI marked including accessories surface type wiring including 1.6 mm thick MS sunken boxes concealed on walls including laminated sheet top cover 3 mm thick fixed with cadmium plated iron screws for housing the switches, switch socket outlets, fan regulators etc., including provision of 2.5 Sq mm PVC insulated single core multi stranded copper conductor cable as earth continuity conductor and connecting to common earth dolly, all as specified and as directed for power socket point of 15 Amps.
Taking down unserviceable sub main wiring, providing material and labour for, Sub main wiring using FRLS grade PVC insulated unsheathed, 1100 volts grade, multi stranded copper conductor cable, 2 runs of single core of size 4 Sq mm and one run of earth continuity conductor of size 4 Sq mm to be drawn through and including PVC casing & capping complete all as specified and as directed. NOTE: - Two runs of 4 sq.mm cable, one run of 4 sq mm earth wire and PVC casing and capping shall be measured as one length.
Taking down unserviceable sub main wiring, providing material and labour for, Sub main wiring using FRLS grade PVC insulated unsheathed, 1100 volts grade, multi stranded copper conductor cable, 2 runs of single core of size 6 Sq mm and one run of earth continuity conductor of size 6 Sq mm to be drawn through and including PVC casing and capping complete all as specified and as directed. NOTE: - Two runs of 6 sq.mm cable, one run of 6 sq mm earth wire and PVC casing and capping shall be measured as one length.
Taking down unserviceable sub main wiring, providing material and labour for, Sub main wiring using FRLS grade PVC insulated unsheathed, 1100 volts grade, multi stranded copper conductor cable, 4 runs of single core of size 16 Sq mm and 2 runS of earth continuity conductor of size 16 Sq mm to be drawn through and including PVC casing and capping complete all as specified and as directed. NOTE: - Four runs of 16 sq.mm cable, 2 runS of 16 sq mm earth wire and PVC casing and capping shall be measured as one length.
Supply and fix in repairs, piano Switch, flush type, One way, SP, 5 Amps, 240 Volts all as specified and as directed.
Supply and fix in repairs, piano Switch, flush type, two way, SP, 5 Amps, 240 Volts all as specified and as directed.
Supply and fix in repairs, switch socket combination 5 pin, 2 in 1, 5 Amps, flush type, 240 Volts all as specified and as directed.
Supply and fix in repairs, switch socket combination 3 pin, 2 in 1, 5 & 15 Amps, flush type, 240 Volts all as specified and as directed.
Supply and fix in repairs, flush type socket outlet, 2 in 1, 3 pin 5 Amps, 240 V, complete all as specified and directed.
Supply and fix in repairs, fan Regulator, 120 W, electronic stepped type, 230 Volts, complete all as specified and as directed.
Supply and fix in repairs, Ceiling rose surface type, Bakelite, 65 x 50 mm ISI marked with three terminals all as specified and as directed.
Supply and fix in repairs, MCB SP, 240 volts, 6 to 32 Amps, 50 Hz, 10 KA breaking capacity, 'C' Series, using copper lugs for terminations, complete all as specified and as directed.
Supply and fix in repairs, MCB SPN, 240 volts, 32 to 40 Amps, 50 Hz, 10 KA breaking capacity, 'C' Series, using copper lugs for terminations, complete all as specified and as directed.
Supply and fix in repairs, MCB TPN, 415 volts, 63A Amps, 50 Hz, 10 KA breaking capacity, 'C' Series, using copper lugs for terminations, complete all as specified and as directed.
Supply and fix in repairs, MCB TPN, 415 volts, 100 Amps, 50 Hz, 10 KA breaking capacity, 'C' Series, using copper lugs for terminations, complete all as specified and as directed.
Taking down unserviceable sheet metal enclosure/ DB, supply and fix, MCB DB TPN 4 way (Horizontal), double door with Sheet metal enclosure, flush mounted, prewired, 415 V, AC, 50 Hz, Factory made, powder coated, IP-42 protection conforming to IS-13032 universal mounting with 200 Amps rated copper bus bar, neutral link, earth link, earthing studs, detachable gland plates with knockouts on both sides, etc complete all as specified and as directed. Notes : i) All unused modules shall be provided with blanking plate for which the cost is deemed to be included in the cost of MCB DBs. ii) MCB/ Isolators will be measured and paid separately as supply and fix under respective items.
All as per Serial Item No 26 here-in-above, but SPN 8 ways, 240 V AC, 50 Hz.
Taking out old unserviceable MCCB, Supply and fix, MCCB, 4 pole, 415 volts, 200 amps, 36 kA breaking capacity, adjustable type complete all as specified and as directed.
Taking out old unserviceable MCCB, Supply and fix, MCCB, 4 pole, 415 volts, 100 amps, 16 kA breaking capacity, adjustable type complete all as specified and as directed.
Supply and fixing in repairs, wall mounted LED batten, suitable for indoor applications, energy efficient, 20 Watt, 4 feet long, extruded aluminium housing and integrated LED channel with high lumen output of 2000 lumens and diffuser should be High translucent serrated milky white, environmental friendly, energy efficient LED, with accessories, IP 20 protection Class I, system electrical efficiency > 85%, system efficacy > =100 lm/W, operating voltage between 140 - 270 V, AC, 50 Hz, TDH <20%, power factor ≥ 0.90, surge protection 2.5 kV, colour temperature 5700 K, CRI > 80 & integrated electronic driver 20 W fitting prewired and connecting with 3 Core, 1 sq mm sheathed copperflexible cable complete all as directed by Engineer – in – charge. Cat Part No. BCLAB 20 WH LED P of Bajaj or technocommercial equivalent makes.
Supply and fixing in repairs, wall mounted LED batten, suitable for indoor applications, energy efficient, 10 Watt, 2 feet long, polycarbonate housing and integrated LED channel with high lumen output of 2000 lumens and diffuser should be High translucent serrated milky white, environmental friendly, energy efficient LED, with accessories, IP 20 protection Class I, system electrical efficiency > 85%, system efficacy > =100 lm/W, operating voltage between 140 - 270 V, AC, 50 Hz, TDH <20%, power factor ≥ 0.90, surge protection 2.5 kV, colour temperature 5700 K, CRI > 80 & integrated electronic driver 20 W fitting prewired and connecting with 3 Core, 1 sq mm sheathed copper flexible cable complete in all respects all a directed by Engineer-in-charge. Cat Part No BCLSB 10 WH of Bajaj or techno commercially equivalent makes specified here-in-after complete all as specified.
Supply and fixing in repairs, LED ceiling mounted, suitable for Gypsum board / grid type false ceiling, recessed full lit luminaire with glare free uniform illumination 36 W 2 feet x 2 feet (>100 Lumen / Watt), CRCA body, suitable for ceiling, with LED seamless front frame with flat white high transmission acrylic cover,operating voltage between 140 - 270 V, AC, 50 Hz, PF >= 0.95, THD<10%, CCT 5700K, CRI >= 80 and Driver Should be Constant Current LED Driver with 2.5 KV Surge, Driver Efficiency >85%, Driver having High Voltage, Short Circuit Protection and Driver Should be with BIS Certified with R number, integral drivers, prewired and connecting with 3 Core 1 sq mm sheathed copper flexible cable complete all as directed by Engineer – in – charge. Cat Part No. BCLSB 10 WH of Bajaj or technocommercial equivalent makes.
Supply and fixing in repairs, LED light fitting aluminium extruded suspended type, suitable for indoor application, 40 W with suspension chain / rod, jointing kit, (>100 Lumen / Watt), operating voltage between 140 - 270 V, AC, 50 Hz, PF >= 0.95, THD<10%, CCT 5700K, CRI >= 80 and Driver Should be Constant Current LED Driver with 2.5 KV Surge, Driver Efficiency >85%, Driver having High Voltage, Short Circuit Protection and Driver Should be with BIS Certified with R number, integral drivers, prewired and connecting with 3 Core 1 sq mm sheathed copper flexible cable complete all as directed by Engineer – in – charge Cat Part No. BPCS 40 W LED 4FLW of Bajaj or technocommercial equivalent makes.
Supply and fix in repairs, bulkhead LED luminaries 10W energy efficient solution for upgrading conventional light fittings, with IP 65 protection Make: Bajaj Cat No. BIBWP10WLED or technocommercial equivalent makes.
Supply and fix in repairs, lamp holder, pin type, PVC /polycarbonate made, complete all as specified and as directed by Engineer-in-charge.
Taking down existing security light fitting, Supply and fix 30 W, LED security light fittings with lamp 30 W with high lumen output, environmental friendly, energy efficient LED, with prismatic polycarbonate diffuser with pressure die cast housing with toughened glass and high power LEDs with secondary optics, with lamps and accessories, IP 66 protection, system electrical efficiency > 85%, system efficacy > 110 IP/W, 10 KV SPD, operating voltage between 140 - 270 V, AC, 50 Hz, TDH, 10%, power factor ≥ 0.95, surge protection 2.5 kV, colour temperature 5700 K, CRI > 80, integral drivers, connecting to loop boxes electrically, light fitting conforming to Cat No ENXT P 30L WHSY PC SD of Bajaj or techno commercially equivalent approved model complete with all accessories complete all specified and as directed.
Taking down existing brackets, providing Material and labour, for bracket made of Galvanized iron pipe 25 mm dia, medium grade, bent to shape not less than 1.5 metre with 2 Nos of MS clamps fabricated out of MS Flats of size 25 x 6 mm, bolts , nuts & washers of suitable size for fixing street light fittings, including 2 coats of aluminium paint complete all as specified and as directed.
Supply and fix in repairs, sheet metal enclosure, SPN, with metal plug and socket, 20 Amps, 240 Volts with one number MCB SP of 20 Amps, complete all as specified and as directed.
Cutting chases, pinning in. making good to facings where required and pointing in cement mortar 1:3 to ends or edges of landings, steps, cills, sunshades, shelves, lintels, etc.; and cutting chases for concealed water tubing or concealed conduit wiring, etc., and making good, cutting not exceeding 10 cm girth, all as specified and as directed.
Disconnecting electric connection / lines, Taking down ceiling fan of 1200mm/1400mm sweep / wall mounted fan 300/450 mm sweep from position, preparing the surfaces, cleaning all dust, filling cavities with filler, spray painting with one coat of synthetic enamel paint, writing MES No, replacing the split pin, rubber pulley, etc., and re-fixing the same complete all as specified and as directed.
Dismantling / opening ceiling fan of 1200 mm sweep of any make and type, removing old defective winding carefully, cleaning the inner parts and rewinding with super enamelled copper conductor of same gauge, maintain good insulation, varnishing, drying and reassembling / re-fixing in its position complete all as specified and as directed.
Dismantling / opening ceiling fan of 1400 mm sweep of any make and type, removing old defective winding carefully, cleaning the inner parts and rewinding with super enamelled copper conductor of same gauge, maintain good insulation, varnishing, drying and reassembling / re-fixing in its position complete all as specified and as directed.
Dismantling /opening wall mounted fan of 300 mm sweep of any make and type, removing old defective winding carefully, cleaning the inner parts and rewinding with the same gauge super enamelled copper conductor of good insulation, varnishing, drying and re-assembling complete all as specified and as directed.
Dismantling /opening the exhaust fan of 300 mm sweep of any make and type, removing the old defective winding carefully, cleaning the inner parts and rewinding with the same gauge supper enamelled copper conductor of good insulation, varnishing, drying and reassembling complete all as specified and as directed.
Dismantling /opening the exhaust fan of 450 mm sweep of any make and type, removing the old defective winding carefully, cleaning the inner parts and rewinding with the same gauge supper enamelled copper conductor of good insulation, varnishing, drying and reassembling complete all as specified and as directed.
Taking down exhaust fans 300mm / 450mm sweep from position by duly disconnecting electric lines, preparing the surfaces, filling cavities with filler, after cleaning all dust, spray painting with one finishing coat of synthetic enamel paint including writing MES NO and replacing the split pin, rubber pully etc., including refixing and connecting the same complete all as specified and as directed. Notes for Sl Item Nos 42 to 48:- Spare parts required for making functional will be measured and paid for separately.
Supply only ball bearing of various sizes / makes as suitable for ceiling fans / wall mounted / exhaust fans including greasing complete as directed.
Supply only gun metal bus of any size / make suitable for fixing to ceiling fans all as directed.
Supply only 2.5 mfd capacitors suitable for ceiling / exhaust fan / wall mounted fans all as directed.
Supply only 4 mfd capacitors suitable for ceiling / exhaust fan / wall mounted fans all as directed.
M&L PVC flexible cable twin twisted core of 23/0.0076 size multi stranded copper conductor suitable for connecting ceiling fans / exhaust /wall mounted etc.including taking down old unserviceable conductor complete all as specified and as directed.
Supply & fix rubber bush with MS bolts, nuts, washer with 'U' clamps for ceiling fan including taking down old unserviceable clamps complete all as specified and as directed.
Supply & fix plastic cup with screw suitable for ceiling fans including taking down old unserviceable plastic cup complete all as specified and as directed.
S & F PVS Fresh air fan of 250/300 mm sweep 1200/1400 RPM with louver. Make : CG / Usha / Orient / Phillips / Bajaj.
Supply and fixing ceiling fan, 230V, SP 1200 mm Sweep with BEE 3 Star rating with all accessories and fixing the fan from ceiling rose with and including 3 core flexible copper wire 24/0.20 sqmm etc all as specified and as directed. Make : Bajaj SABSE TEZZ EE 03. Model No 251120 and equvalent on Havells/CG/ USHA.
Demolishing of existing earth pits, and providing Material and labour for, earthing complete with Galvanized Iron earth plate electrode 600 mm x 600 mm x 6 mm buried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to galvanized earth lead wire of 4 mm dia by means of bolts, nuts, check nuts and washers, earth wire protected by galvanized steel pipe 15 mm bore (light grade) connected to machinery/ equipment all as shown in electrical plate No. 3 of SSR-2009 Part I and including necessary excavation and earth work in any type of soil, 40 mm bore light grade GI pipe for watering funnel wire mesh, PCC chamber in CC (1:3:6), type C1 , 40 mm tick RCC pre-cast manhole cover slab 1:2:4 type B1, reinforced with 8 mm dia MS round bars @ 100 mm c/c both ways for cover and MS frame etc., complete all as specified and as directed NOTE :- Earth pit shall be constructed at least 0.5 metre away from each earth chamber.
Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for laying of cable / erection of pole, etc. not exceeding 10 sq m on plan and getting out in hard / dense soil complete all as speicified.
Excavating in trenches, not exceeding 1.5 m wide and depth exceeding 1.5 m and not exceeding 3 m; for foundation, etc. not exceeding 10 sq m on plan and getting out in hard / dense soil complete all as speicified.
Returning, filling in soils, including spreading, levelling, watering and well ramming in layers not exc 25 cm complete all as specified.
Removing excavated surplus soils not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified.
Riddled earth cushioning in layers for cable protection, watering well ramming in layers complete all as specified. Note : Punned thickness only will be measured for payment.
Supply and laying Sub Class 'B' bricks of size 230 mm x 115 mm x 75 mm, for cable protection, complete all as specified.
Taking down burned XLPE cables, Supply and laying 1100 V graded, armoured heavy duty XLPE insulated aluminium conductor cable, screened PVC bedded cable of cross-sectional area 2 Core 10 Sq mm with lugs all as specified. Notes:- i) Eartwork, sand cushioning & and cable protection works where required will be measured and paid for separately.
All as per Serial Item No 65 here-in-above, but aluminium conductor cable of cross-sectional area 4 Core 10 Sq mm with lugs all as specified.
All as per Serial Item No 65 here-in-above, but aluminium conductor cable of cross-sectional area 4 Core 16 Sq mm with lugs all as specified.
Material and labour for galvanised iron light grade pipe 40 mm dia as cable protection works, laid in trenches / on walls / poles / roads, including taking out old unserviceable pipe complete all as specified and as directed.
Material and labour for galvanised iron light grade pipe 50 mm dia as cable protection works, laid in trenches / on walls / poles / roads , including taking out old unserviceable pipe complete all as specified and as directed
Dismantling of unservicieable RCC poles, including demolition of PCC bed and coping, Supply and erecting steel tubular swaged poles 9 m long, type 410 SP 31 (ISI Marked), with cast iron base plate, finial taper plugs, bolts, nuts, etc,, all as specified. Notes : Excavation & earthwork, foundation concrete and coping will be measured and paid separately.
Material and labour for, plain cement concrete 1:4:8 type D2 (using 40 mm graded stone aggregate) laid as in foundations and similar works, including necessary formwork, complete all as specified.
Material and labour, Plain Cement Concrete (1:3:6), type C1, using 20 mm graded stone aggregates for coping of poles / mass concreting / plinth blocks of poles etc., including necessary form work and finishing the exposed surfaces even and smooth without using extra cement complete all as specified and directed.
Preparation of old painted surfaces of steel pole / PCC pole including bracket of any height, applying zebra marking painting with two coats of synthetic enamel paint of approved make from ground level & upto 0.9 metre height (3 strips of black, 3 strips of yellow, each of 15 cm width) and remaining length with two coats of aluminium paint, painting pole terminal box, 2 coats of cement based paint on coping etc., writing pole numbers on each pole to match with existing one, complete all as specified and directed .
Taking down unserviceable time line distribution board and supply and fix time line distribution board 32 A, 3 Pole, 230 V, analog time switch including accessories, relay contractors, timer etc., all as per Indoasian Cat Part No TL032AB0 or of techno commercial equivalent makes approved here-in-after.
Taking down existing brackets from street lights / walls, providing Material and labour, for brackets made of Galvanized iron pipe 40 mm dia, light grade, bend to shape not less than 1.5 mtr with 2 Nos of MS clamps fabricated out of MS Flats of size 25 x 3 mm, bolts, nuts of suitable size for fixing street light fittings complete all as directed.
Taking down old unserviceable junction boxes, Supply and fix, FRP body, junction boxes (IP 65 protection), of size not less than 300 mm x 200 mm x 80 mm (out door type), fitted on poles with suitable size clamps made out of MS flat iron of size 20 x 5 mm GI nuts, bolts and washers complete with 4 way 32 Amps (heavy duty) connector - 2 Nos, including provision of cable glands of suitable size, including MCB SP 6 amps - 01 No, complete all as specified and directed.
Taking down existing street light fitting, Supply and fix 60 W, LED street light fittings with lamp, 60 W, IP 66 protection, with high lumen output, environmental friendly, energy efficient LED, pressure die cast ousing alongwith prismatic polycarbonate modular secondary lens optics with accessories, impact resistance of IK 08, system electrical efficiency > 85%, system efficacy > 100 lm/W, operating voltage between 140 - 270 V, AC, 50 Hz, TDH, 10%, power factor ≥ 0.95, 4 kV inbuilt and 10 kV external surge protection, colour temperature 5700 K, CRI > 80, intergral drivers, top opening dirver cover for easy maintenance fittings as per Cat No ENXT P 72 L WH CR PC SD of make Bajaj or techno commercially equivalent makes. Note: - Electric cable if required for replacing defectivecable from looping box to fitting will be measured and paid separately under respective item.
Taking down existing street light fitting, Supply and fix 90 W, LED street light fittings with lamp, IP 66 protection, with high lumen output, environmental friendly, energy efficient LED, pressure die cast housing and tougened glass with accessories, impact resistance of IK 07, system electrical efficiency > 85%, system efficacy > 100 lm/W, operating voltage between 140 - 270 V, AC, 50 Hz, TDH, 10%, power factor ≥ 0.95, 5 kV inbuilt and 10 kV external surge protection, colour temperature 5700 K, CRI > 80, intergral drivers, top opening dirver cover for easy maintenance fittings as per Cat No BRTFG 90W LED CR of make Bajaj or techno commercially equivalent makes. Note: - Electric cable if required for replacing defectivecable from looping box to fitting will be measured and paid separately under respective item.
Taking down unserviceable wiring, providing material and labour for, wiring with PVC insulated unsheathed, 1100 volts grade, multi stranded copper conductor cable, 2 runs of single core of size 2.5 Sq mm and one run of earth continuity conductor of size 2.5 Sq mm to be drawn through and including PVC rigind conduit of 20 mm dia fixed on pole, complete all as specified and as directed. NOTE: - Two runs of 2.5 sq.mm cable, one run of 2.5 sq mm earth wire and PVC conduit shall be measured as one length.
Dismantling and taking down LED street light fitting of any make from poles, removing and replacing the burnt out LED drivers of 25 to 60 W, making the light fitting functional and refixing in same or different location all as directed.
Dismantling and taking down LED street light fitting of any make from poles, removing and replacing the burnt out LED drivers of 90 W, making the light fitting functional and refixing in same or different location all as directed.
Dismantling and taking down flood light fitting from high mast pole and removing and replacing the burnt out or unserviceable LED driver of any make from poles 150 W to 200 W, making the light fitting functional and refixing in same or different location all as directed.
Taking down existing flood light fitting, Supply and fix 150 W, LED flood light fittings (outdoor type) with lamp, IP 66 protection and impact resistance of IK 07, with high lumen output, environmental friendly, energy efficient LED, ultra sleek, light weight and with secondary optics made of pressure die cast housing, electrical efficiency > 85%, system efficacy > 100 lm/W, operating voltage between 140 - 270 V, AC, 50 Hz, TDH, 10%, power factor ≥ 0.95, 4 kV inbuilt and 10 kV external surge protection, colour temperature 5700 K, CRI > 80, intergral drivers, IP 65 protection fittings as per Cat No BJFL 150W LED I of make Bajaj or techno commercially equivalent makes specified here-in-after complete all as specified. Note: - Electric cable if required for replacing defectivecable from looping box to fitting will be measured and paid separately under respective item.
Boring of holes in roads, pavements, hardstanding by trenchless technology using ultra sound technique including provision of HDPE pipe of 63 mm dia (with working pressure of 0.4 mpa)
Excavation in trenches by cutting or road crossing / PCC hardstanding for laying of pipe / cable including making good the cut surface by filling wit PCC 1:3:6 type C2 (using 40 mm graded stone aggregate) / bitumen to match to original finish all as directed.
mahadevi Enterprises
Vasavi Electricals
Aditya Associates
YUVARAJ ELECTRIC AND CO
K T ASSOCIATES
KAALIKA ELEVATORS
Auromirra Enterprises
Swarna Constructions
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .