| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.8 LAccepted-AOC | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹28.5 L+₹73,425 (2.64%)Rejected-Finance | L2 | Rejected-Finance LOWEST BIDDER OTHER THAN | |
| 3 | L3₹29.2 L+₹1.4 L (5.19%)Rejected-Finance | L3 | Rejected-Finance LOWEST BIDDER OTHER THAN | |
| 4 | L4₹30.4 L+₹2.6 L (9.34%)Rejected-Finance 53 HOUSING BOARD COLONY PHASE II UDHAMPUR 182101 J K | UDHAMPUR | UDHAMPUR | J K | 182101 | L4 | Rejected-Finance LOWEST BIDDER OTHER THAN | |
| 5 | L5₹30.5 L+₹2.8 L (9.97%)Rejected-Finance 6 RAILWAY STATION ROAD ONKAR INDUSTRIES GULAMALI PURA BAHRAICH UTTAR PRADESH 271801 | BAHRAICH | UTTAR PRADESH | 271801 | L5 | Rejected-Finance LOWEST BIDDER OTHER THAN |
Tender Value
₹29 L
EMD Value
₹58,000
Closing Date
30 Jun 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Sh A K Dubey IDSE SE CWE
Military Engineer Services, Commander Works Engineer, Udhampur, PO - Garhi, Udhampur-182121
ADDITION/ ALTERATIONS TO HT POWER SUPPLY SYSTEM AT VARIOUS POCKETS OF HQ NC UNDER GE (UTILITIES) UDHAMPUR
2022_MES_528450_1
CWE/U(U)-35/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
UDHAMPUR
AS PER TENDER
8 documents required · 8 mandatory
₹500
GE (UTILITIES) UDHAMPUR
₹58,000
26 Jul 2022
3 Jun 2022
2 Jul 2022
3 Jun 2022
30 Jun 2022
18 Jun 2022
Amount
Supply and ererction in vertical position Steel tublar swaged poles erected truly vertical or planted as strut complete with 6 mm thick mild steel base plate (300mmx300mm), welded to pole, B-118 finial taper cap,bolts,nuts & screws, poles made out of ERW MS tubing conforming to IS 2713 Part-II. Type 410-SP-55 (11 m long) including drilling of holes of required size for fixing of cross arms, painting the exposed surfacs of pole with two coats of aluminium paint over a coat of two coats of zinc chrome primer and two coats of black bitumenous paint internally & portion embedded in concrete, making five black & white bands at lower portion of pole each 300 mm wide alternatley, and marking pole No. with black paint at suitable height complete all as specified and directed. Note :- Excavation and earth work, PCC in foundation shall be measured and paid for separetely.
M&L for MS work cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections ( flat, angle, channel) including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one coat of red oxide primer, one under coat and one finishing coat of aluminium paint, complete all as specified and directed by Engr-in-Charge.
Supply and Fix lightning arrestors expulsion type complete with all fittings suitable for 11000 volts grade conforming to IS-3070 part-I, transmission class, discharge capacity 65 kilo Amps, complete all as specified and as directed by Engr-in-Charge.
Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 3.15mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to galvanized iron earth strip 20x3 mm size by means of bolts, nuts, check nuts and washers of galvanized standard iron or steel all as specified or indicated in electrical plate No 3 of MES Part-I, including testing on completion including the material and labour and taking out old unserviceable earthing of the following :- (a) Excavation and earth work for drilling hole for electrode in any type of soil. (b) PCC pit in cement concrete 1:2:4 type B-1. (c) Precast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 4 Kg/Sqm. (d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified.
Srl item No 04 Contd … (e) 15 mm nominal bore light grade GI protection pipe 7.5 mtr long for protection of earthing lead from mechanical injury or tempering. (f) Requisite quantity of common salt and charcoal. (g) Testing of earthing. Note : On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge.
Supply , lay and stringing of ACSR Conductor , Aluminium conductor reinforced with steel including various acessories like line connectors , line taps and compression joints wherever required including streching, tightining of poles insulator with winding wire of suitable size with insulator/streching of ACSR conductor complete all as specified and directed by Engr-in-Charge.
Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm, complete, all as specified and directed by Engineer-in-Charge.
Supply, laying, commissioning and testing in replacement XLPE insulated screended PVC bedded galvanised steel strip or wire armoured electric power (Heay duty) with aluminium condutor 11000 volts (earthed) grade cross sectional area 150 sqmm 3 core cable in trenches, jointing with proper lugs, cable gland complete all as specified and directed by Engr-in-Charge.
Description all as per Srl item No 8 above but size of cable 120 sqmm 3 core.
Description all as per Srl item No 8 above but size of cable 95 sqmm 3 core.
Excavation in trenches in any type of soil not exceeding 1.50 m wide and not exceeding 1.50 mtr in depth and getting out for pipe, cable pole, stay etc, complete all as specified and directed by engineer-in-Charge.
All as per Srl item No. 11 here in before but depth exc.1.5m and not exceeding 3.0m complete all as specified and directed by engineer-in-Charge.
Returning filling in (soil) including spreading leveling watering and well ramming in layers not exceeding 25cm thick, complete all as specified and directed by engineer-in-Charge.
Removal of excavated material (soil) to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed by engineer-in-Charge.
M&L plain cement concrete 1:3:6 type C-2 as in foundations filling and mass concrete using 40mm graded stone aggregate complete all as specified and directed by engineer-in-Charge.
M&L plain cement concrete 1:2:4 type B-2 using 40mm graded stone aggregate for coping of poles incl all necessary form work complete all as specified and directed by engineer-in-Charge.
S&F double walled corrugated (DWC) pipe of size 120 x 103 mm including snap fit coupler and any additional attachments suitable for DWC pipe , conforming to IS:14930 (Pt-II)/IS-16205 Pt-II for protection of HT/LT cable 120 & 150 sqmm in under ground complete all as specified & directed by Engineer-in-charge.
S&F double walled corrugated (DWC) pipe of size 90 x 76 mm including snap fit coupler and any additional attachments suitable for DWC pipe , conforming to IS:14930 (Pt-II)/IS-16205 Pt-II for protection of HT/LT cable 95 sqmm in under ground complete all as specified & directed by Engineer-in-charge.
Material and labour for road cutting for laying of HT/LT Cables / Pipes and making good the distrubued surfaces as equal to existing road finishes including refilling the excavated material, compacting , WBM and black top carpeting with biutemen & aggregate, complete all as specified & directed by Engineer-in-charge.
Material & labour for switch air break, gang operated triple pole, mechanically operated, mounted on insulators and steel frame with operating mechanism worked from ground level for current rating up to 400A for working pressure 11000 volts with drop out type fuses three No of 40 Amps capacity , complete all as specified & directed by Engineer-in-charge.
Suppy, installing, connecting, commissioning and testing of energy effficient transformer (level 3 of IS 1180) of capacity 250 KVA outdoor type powder coated, step down 11/0.433 KV, core type oil immersed, copper wound, natural oil cooled with external cooling tubes, having 3 phase 50 Hz, AC supply, DYN-11 design, off load tap changer on HT side to vary secondary voltage ±7.5% in steps of 2.5% as per IS 1180 (Pt-I to III) with all standerd accessories including HT and LT bushing LT box on LT side, including inbuilt protection and first filling of transformer oil (of die electric strength not less than 50 KV) upto required level in conservator tank with cover boxes, dial type thermometer, rollers, stop taps, breather with silica gel, conservator tank, oil level indicator, etc, complete all as specified and as directed by Engr-in-Charge. Note :(i) The transformer oil shall be fresh and approval certificate from manufacturer shall be obtained by contractor and furnished to GE. the copper shall be 99.97% purity and approval certificate from manufaturer shall be obtained by contractor and furnished to GE. (ii) Pre -commisioning, inspection of transformer shall be carried out by rep of Accepting offr and T&P for the inspection shall be arrange by contractor, cost of the T&P etc for testing shall deemed to be included in the unit rate.
Notes for Item 21 (Contd....) (iii) construction of platform for transformer 2.5m (wide)x 2.5m (long) & 2.0m (height) including moorum filling, earth work in brickwork any type of soil, brick work in CM (1:6) and PCC at top 10 cm thick (1:2:4) type B-1 and foundation with 1:4:8 type D-2, 25cm thick all as per drawing including plastering to exposed walls and white wash, providing MS channel on top of size 75x40x8mm of 1.5m length for rolling to transformer, including chain link fencing of wire mesh 150x100 size made out 4mm dia GI wire of height 1.5m fixed with the help of MS strip 25x6mm on and including MS angle iron 75x45x6mm thick 12 Nos post by the means of drilling holes at the distance of 30cm and fixed with the help of suitable nut, bolt and washer, the length of MS angle iron not less than 2.25m top of post bend to the shape of 60 degree including 03 Nos cuts for inserting barbed wire including 03 run of barbed wire and including provision of gate of size 1.5mx0.9m made out of MS angle iron 50x50x6mm and MS bar 12mm dia for meshing to the gate and locking arrangement complete all necessary for work, complete all as specified and as shown on drawing No. CEUZ/TD/1516/15 sheet 1/1. shall deemed to be included in the unit rate. (iv) Provision of 4 Nos rubber mats Synthetic 2mx1m at near the surfaces of Plinth/platform of transformer shall deemed to be included in the unit rate. (v) Necessary chain link fencing required around transformer shall deemed to be included in the unit rate.
Supply , installation, testing & commissioning of maintenance free earth electrode of size 100mm dia X 3000mm long with 17.2 mm Cu bonded MS Conductor pre cast or in situ cast in high purity electrically conductive granular material having ultra low resistive value of 0.001 ohm-m. electrode made of conductive earth enhancing material mixed with cement in ratio of 3:1 encase or backfill the voids surrounding the 17.2 mm Cu bonded MS Conductor or other metal components placed in augured bore hole of 100mm dia X 3000mm depth ,resulting in increase in the effective surface area of the earth electrode or grids to lower the resistance. Earth enhancing material should not leach chemicals into the adjacent soil or underground water channels and should be pH neutral range. Earth enhancing material should be permanently protect the encased metal components of the earthing systyem. Copper bonding on MS rod should be minimum 250 microns. all hardware like nuts , bolts and washers should be of stainless steel. electrode should withstand fault current up to 35ka for 1 sec. electrode top terminal should be sealed permanently packed with conductive concrete and Cu bonded MS/Copper strip taken out shall be terminated on to earth test point and equipped terminal. Test certificate of NABL laboratory shall be submitted by the contractor. Test link of size 500mmx 6mmx 200mm , RCC Pit cover including brazing of all the joints up to the test point shall be provided complete all as specified and directed by engineer-in-charge. Make of electrically conductive material : Marconite/ITPC Met-chem/ Kratonite or equivalent.
ARNABH ASSOCIATES
shivom builders
vijay kumar gupta and co
MOHAN LAL AND SONS
FANGALIA TRADERS
M/S Builders Indias
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .