Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.1 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹37.2 L+₹2.0 L (5.70%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹39.7 L+₹4.6 L (13.0%)Rejected-Finance 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | L3 | Rejected-Finance Other than L1 | |
| 4 | L4₹43.7 L+₹8.6 L (24.4%)Rejected-Finance 29 MODEL TOWN BEHIND GURUDWARA PATHANKOT | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L4 | Rejected-Finance Other than L1 |
Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
11 Feb 2020, 6:00 pmClosed
CWE Amritsar
CWE Amritsar Old Cantt Amritsar
REPAIR REPLACEMENT OF HT CABLE TRANSFORMER AND CONNECTED WORKS AT OLD AMRITSAR CANTT UNDER GE AMRITSAR
2020_MES_317122_1
CWE/ASR-74/2019-20
Open Tender
Civil Works
Item Rate
270 days
GE Amritsar
class D category b(ii)
7 documents required · 7 mandatory
₹500
GE Amritsar
₹98,000
27 Feb 2020
21 Jan 2020
13 Feb 2020
21 Jan 2020
11 Feb 2020
6 Feb 2020
Amount
Taking out existing HT pole any size / type after demolition of concrete foundation & coping including necessary excavation & earth work, dismantling MS clamps, nuts, bolts, earth wire, overhead lines conductor, insulators, gaurding cradles and other accessories complete all as specified and directed.
Dismantling of cross arms, fabricated from mild steel structural section of any type and size, bolts, nuts etc from existing position and keeping at site for repair / replacement all as directed.
Dismantling of existing stay assembly any type / size from its stay rod, cutting stay rods (above ground portion) dismantling MS clamps, nuts, bolts, stay bow, loop insulators, stay wire etc complete all as specified and directed.
Dismantling / taking out old ACSR conductor / GI earth wire, any size from poles / over head lines incl disconnection all as specified and directed.
Dismantling / taking out insulator of any size / type from existing electric HT lines all as specified and directed.
Supply and errecting in true vertical position steel tubular swaged poles 11 metre long complete with MS base plate, MS pole cap, bolts nuts & screws as specified type 410 SP-55 including painting of poles with black bitumenous paint throughout the length internally and outside upto planting depth and remaining portion with two coats of aluminium paint over a coat of red oxide primer, including painting of 05 Nos. bands / strips of 30 cm wide each with two coats of synthetic enamel paint (black & yellow) at a distance of 30 cm from plinth block upto 1500 mm height and marking / sign writing of pole number and feeders locations of pole with synthetic enamel paint (white) complete all as specified and directed. Note: Excavation & earth work and PCC fondation shall be measured and paid separately.
Supply and errecting in true vertical position Prestressed Concrete Poles 11 metre long 152mm X 152mm at top and 152mm x 260mm at bottom, class - 9 including painting of 05 Nos. bands / strips of 30 cm wide each with two coats of synthetic enamel paint (black & yellow) at a distance of 30 cm from plinth block upto 1500 mm height and marking / sign writing of pole number and feeders locations of pole with thick synthetic enamel paint (white) complete all as specified and directed. Note: Excavation & earth work and PCC fondation shall be measured and paid separately.
Material and labour for cement concrete 1:4:8, type D-2 (using 40mm graded stone aggrregate) as in foundation for poles, mass concrete including necessary form work complete all as specified.
Material and labour for cement concrete 1:3:6, type C-2 (using 40mm graded stone aggrregate) as in foundation for stays and coping of poles including necessary form work complete all as specified.
Supplying and fixing HT disc type porcelain vitreous white, brown or green insulator, size 145mm high and 255mm dia, ball and socket type with tension clamp for conductor, for working pressure 11000 volts complete all as specified and directed.
Supplying and fixing pin type porcelain vitreous white, brown or green insulator size 150mm high and 150mm dia, for working pressure 11000 volts grade including one galvanised mild steel spindle, two galvanised iron washers and one nut complete all as specified and directed.
Supply, fixing and testing Lightening Arrester non linear resistor type comforming to IS 3070 Part I, complete with all fittings, transmision class, discharge class-2, nominal discharge current 10KA & high discharge 65 KA assembly suitable for 11 KV including clamps, nuts, bolts & washers and connecting to earth with and including 4mm dia GI wire including taking down of old unservicable set complete all as specefied and directed.
Material & labour for mild steel cross arms, bracing, supports, clamps and back plate, fabricated from structural steel section including nuts, bolts and washers, welding, bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclusive of two coats of aluminium paint over a coat of red oxide primer complete all as specified and directed.
Supply, installation, commissioning and testing of switch Air break, Gang operated with 12 insulator switch Triple pole, mechanicaly operated, mounted on insulator and steel frame, for current rating 200 Amp operating Voltage 11 KV out door, vertical mounted type, complete with locking arrengement, assembly with fuse mount carrier and fuse element of required capacity and isolater suitable for 11 KV including necessary electric connection and 11 KV fuse (drop out type) of capacity as required at site and directed by Engr-in-Charge, with DO fuses assembly and one No. operating rod of 25 mm dia bore medium grade GI pipe of suitable length, worked out from ground level and handle complete with lock and two Nos keys incl flat iron clamp 50mm x 6mm MS channel of suitable size & length for fixing GOD including nut, bolt, washers including taking down existing unservicable set all as specified and directed.
Supply, laying, jointing and testing HT XLPE cable, cross section area 70 Sqmm, 3 core, 11000 V, screened, PVC 'E' grade insulated bedded, galvanised steel (heavy duty ) strip or wire armoured with alluminium conductor, pressure earthed system, conforming to IS 7098 (Part-1 ) 1977 and Part-II of 1985, laid in pipes / ducts / trenches, under floor and roads or fixed to wall etc including taking out old unsv cable, any type, complete all as specified and directed.
All as per Srl Item No 15.00 here-in-before but cross section area 95 Sqmm, 3 core.
All as per Srl Item No 15.00 here-in-before but cross section area 185 Sqmm, 3 core.
Material & labour for indoor type cable end terminatrion kit, heat shirnkable jointing material and accessary complete suitable for 11 KV HT XLPE underground cable size 50 to 95 Sqmm 3 core including testing after jointing complete all as specified and directed.
All as per Srl Item No 18.00 here-in-before but cable size 120 to 185 Sqmm 3 core.
All as per Srl Item No 18.00 here-in-before but cable size 240 to 300 Sqmm 3 core.
Material & labour outdoor type cable end terminatrion kit, heat shirnkable jointing material and accessaries complete suitable for 11 KV HT XLPE underground cable size 50 to 95 Sqmm 3 core including testing after jointing complete all as specified and directed.
All as per Srl Item No 21.00 here-in-before but cable size 120 to 185 Sqmm 3 core.
All as per Srl Item No 21.00 here-in-before but cable size 240 to 300 Sqmm 3 core.
Material & labour cable straight through joint box type suitable for 11 KV under ground XLPE screened PVC bedded GI Strip or wire armoured cable, size 50 to 95 Sqmm 3 core heat shrinkable, termination kit jointing material connected to electrical system with and including cable pieces of suitable size, length and the tap, vice type compelete all as specified and directed.
All as per Srl Item No 24.00 here-in-before but cable size 120 to 185 Sqmm 3 core.
All as per Srl Item No 24.00 here-in-before but cable size 240 to 300 Sqmm 3 core.
Material & labour for ACSR conductor, stringing and stretching on existing HT PCC / Steel tubular poles including binding and jointing the conductor with and including 14 SWG binding wire complete all as specified and directed.
Tightening / restringing existing loose / broken conductor ACSR, any type or size, LT / HT over head line including binding with suitable binding wire and jointing jumpers as required complete all as specified and directed.
Tightening and restringing existing loose / broken continuous GI wire 4 mm dia on existing HT over head lines including stringing all as required at site complete all as specified
Supply and fixing, in replacement of HT jumper of existing two / four pole structure of transformer etc includinng using 95 Sqmm single core aluminium cable conductor, including PG clamp nut, bolts, thimbles and washers etc as required at site complete all as specified and directed.
Material & labour stay assembly complete comprising of 7/3.15 galvanised stranded stay wire of required length, fixed to pole with and including FI clamps 50 x 6 mm, bolt, nuts washers, GI stay rod 20 mm dia and 1800 mm long, stay bow 400 x14mm, GI steel plate 300x300x6mm, loop insulator of size 90 x 140mm clearance hole 16mm including two coats of aluminium paint over a one coat of red oxide primer on exposed mild steel work all as shown in Electrical Plate No. 1 of SSR part - I 2009 on Page No 495 compelete all as specified and directed.
Supply and laying GI steel tubing, 80mm bore, light grade with all fittings, laid in trenches / under roads / along pole / wall for protection of Cable / GI wire / GI strip etc complete all as specified and directed.
All as per Srl Item No 32.00 here-in-before but bore of pipe 100mm.
Material & labour for preparation of old painted steel and iron surfaces and painting to steel tubular poles of any height 9/11/13 metre, any type (double swan / single swan) with two coats of synthetic enamel paint upto 1.5 m height above from ground level (in yellow and black strips of 30 cm wide each) and applying two coats of aluminium paint above 1.5 m height of poles incl painting on cross arms, bracing, clamps etc and writing pole number with black synthetic enamel paint complete all as specified and directed.
Material & labour for preparation of old painted steel and iron surfaces and painting to 4 pole structure PCC/Steel poles of any height 9/11/13 metre, any type (double swan / single swan) with two coats of synthetic enamel paint upto 1.5 m height above from ground level (in yellow and black strips of 30 cm wide each) and applying two coats of aluminium paint above 1.5 m height of poles and cross arms, bracing, clamps, chanels etc and writing pole number with black synthetic enamel paint complete all as specified and directed.
Material & labour for preparing old painted surface of distribution / power transformer outdoor / indoor / pole mounted of capacity 300 to 500 KVA by cleaning, removing the old paint by scratching with wire brush etc and applying with spray machine two coats of synthetic enamel paint of grey colour on external surfaces of the transformer and writing of letter HT / LT or HV / LV and SM / MES Nos including disconnecting and making electric connections complete all as specified and directed. Note: (i) The compressure / spray machine and other required necessary equipments shall be arranged by the contractor and quoted rates shall be inclusive of this aspect.
All as per Srl Item No 36.00 here-in-before but capacity 50 to 250 KVA.
All as per Srl Item No 36.00 here-in-before but capacity 4 MVA.
Material & labour for scrapping and removing of old paint, cleaning and preparation of surfaces of iron angle / chanel structure for 66 KV Grid at Old Cantt Amritsar and painting with 1st quality synthetic enameled aluminium paint two coats including cleaning / greasing insulators / LA / SF6 / CT / PT etc and checking loose connections complete all as specified and directed.
Material & labour for scrapping and removing of old paint, cleaning and preparation of surfaces of VCB for 66/11 KV Grid at Old Cantt Amritsar and painting with 1st quality synthetic enameled paint two coats with spray machine including checking loose connections complete all as specified and directed.
Excavation in trenches in soft/ loose soil not exceeding 1.50 m wide and not exceeding 1.50 m in depth for foundation of poles, stay, cable, pipes etc and getting out complete all as specified.
All as per Srl Item No 41.00 here-in-before but exceeding 1.5m and not exceeding in depth.
Returning, filling, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each complete all as specified.
Removal of surplus spoil to a distance not exc. 50m and depositing where directed at a level not exc. 1.5m above the starting point complete all as specified.
Material and labour for sand cushioning with a layer of fine sand 8 cm thick before laying the cable and 15 cm after laying the cable in trenches to cover under ground cable complete all as specified and directed. Note :-Punned down thickness of sand shall be considered for measurement)
Supply and laying un-reinforced precast concrete cable cover factory made, class HV, type I flat of size 300mm x 180mm x 40mm complete all as specified and directed.
Trimming of trees / branches from HT / LT poles clearing 2 metre horizontal on either side and 2 metre vertical distance from top of pole including removal of cut trees branches from site complete all as directed. Note:- Each Unit consisting of any number of wire/conductor shall be meaured as 'One Unit of Running Metre'.
Material & labour danger notice plate of 1.6 mm thick, mild steel sheet, 25 x 20 cm for HT poles, vitreous enamelled white with letters, figures and conventional skull and bones, in signal red colour, fixed with MS clamps, bolts and nuts of suitable size as approved complete all as directed at site.
Material & labour for cable / feeder indication plate, for HT/LT 25 x 20 cm, made of 2 mm thick mild steel sheet, applying with two coats of black pait over one coat of red oxide and writing, vitreous enamelled white with letters, fixed with MS clamps, bolts and nuts of suitable size as approved complete all as specified and directed.
Supply and fixing HT cable route indicator of cast iron not less than 100mm dia fixed through welding angle iron support of size 35 mm x 35 mm x 5 mm thick, 50 cm long including two coats of synthetic enamel paint over a coat of red oxide primer along HT trench including planting in ground with PCC (1:3:6) type C1 of size 30 cm x 30 cm x 60 cm complete all as specified and directed by Engineer-in-Charge.
Supply and fill up silica gel in different capacity of transformer breathers complete all as specified.
Material & labour for copper winding wire of any size/description suitable for step down power transformer of any capacity, including winding of coils (HT/LT) as per the manufacturers design & specification to obtain rated KVA complete all as specified.
Supplying and fixing aluminium strip 40x6mm, fixing with screws, including making holes for cable/thimbles as required complete all as specified.
Dehydration and filtering the transformer oil with dehydration machine to achieve dielectric strength of the oil to 40 KV at 2.5 mm gap complete all as specified and directed . Note:- Dehydration machine and other necessary equipments required shall be arranged by the contractor and quoted rates shall be inclusive of this aspect.
Supply and filling for topping up transformer oil in the transformer after dehydration with dehydration machine to achiene dielectric strength of oil to 40 KV at 2.5mm gap complete all as specified.
Opening up the top cover of the transformer by taking out the transformer oil in a separate container after disconnecting / taking out the HT/LT side electric connections from both the primary & secondary side of the transformer of any type / description (indoor / outdoor type ) installed on floor/pole for carrying out necessary repair / rewinding to HT/LT side or any other repair as required after shifting the transformer to contractor's work shop including taking out complete core assembly, Magger the winding for identifying the fault/defective winding, seggregating the defective winding portion/taking out, cleaning the laminated core rewinding with appropriate gauge winding wire of existing description for transformer of capacity 50 to 160 KVA including assembling & testing on completion & installation the same at the site all as specified and directed. Note : (i) Winding of coil and spares required as per repair shall be measured and paid separately under respective item. (ii) The transpotation charges and taking down/taking up of transformer are inclusive in the quoted rates. (iii) The cost for the dehydration of transformer oil if reqd shall be measured & paid separately. (iv) The cost of insulation material such as paper, cotton tape , latheroid sheet , casl sheet etc are inclusive in the quoted rate.
All as per Srl Item No 56.00 here-in-before but capacity 200 to 500 KVA.
Opening up the top cover of the transformer by taking out the transformer oil in a separate container after disconnecting/taking out the HT/LT side electric connections from both the primary & secondary side of the transformer of any type/ description ( indoor/outdoor type ) installed on four pole for carrying out necessary repair/replacement of HT/LT side bushes or any other repair as required for transformer of capacity 50 to 500 KVA including assembling & testing on completion complete all as specified and directed.
Servicing of transformer 66/11 KV incomer panel (Indoor) and taking out the defective / burnt out parts, replacment with new spare parts and assembling complete including testing all as specified and directed. Note:-The cost of the spare parts will be paid and measured and separately under the respective items
Servicing of 66 KV SF6 circuit breaker out door type including minor repair of parts, greasing, gas recharging etc complete testing all as specified and directed.
Servicing of GOD switch of any type, capacity including tightening of nuts, bolts, insulators, fitments of moveable parts, greasing, oiling etc complete testing all as specified and directed.
Servicing of Vaccum circuit breaker and taking out the defective /burnt out parts, replacment with new spare parts and assembling complete, oiling, greassing of complete vaccum circuit breaker and testing complete all as specified and directed at site . Note:-The cost of the spare parts shall be measured and paid separately under Srl Item Nos 74 to 84 here-in-after.
Material & labour for Air breather assy complete with fresh blue colour silcagel suitable for indoor/outdoor type transformer capacity 50 to 160 KVA complete all as specified.
All as per Srl Item No 63.00 here-in-before but capacity 200 to 500 KVA.
Material & labour for temperature gauge 0°C to 125 °C with transformer installed at site with all accessories complete all as specified and directed.
Supplying & fixing of LT side brass stud with nuts, bolts and washers for transformer of capacity 50 to 200 KVA complete all as specified and directed.
All as per Srl Item No here-in-before but capacity 250 to 500 KVA.
Supplying & fixing of HT side brass stud with nuts, bolts and washers for transformer of capacity 50 to 200 KVA complete all as specified and directed.
All as per Srl Item No 68.00 here-in-before but capacity 250 to 500 KVA.
Supply and fixing, in replacement, aluminium lugs for HT / LT cable including cutting of worn out aluminium cable terminal lugs from the cable, crimping of new aluminium cable core including necessary excavation and making good the surfaces complete all as specified and directed. Size of Cable:- 50 Sqmm to 95 Sqmm..
All as per Srl Item No 70.00 here-in-before but size of cable 120 Sqmm to 150 Sqmm..
All as per Srl Item No 70.00 here-in-before but size of cable 185 Sqmm to 240 Sqmm..
All as per Srl Item No 70.00 here-in-before but size of cable 300 Sqmm to 400 Sqmm..
Suppy only Closing coil suitable for 630 Amp 11000 Volts VCB as per sample complete all as specified and directed. Make: Kirloskar Model No. M-500
Suppy only Tripping coil suitable for 630 Amp 11000 Volts VCB as per sample complete all as specified and directed. Make: Kirloskar Model No M-500
Suppy only interupted base plate for 630 Amp VCB trolly as per manufacturer including connection complete all as specified and directed.
Suppy only insulator bush for 630 Amp VCB trolly as per manufacturer including connection complete all as specified and directed.
Suppy only Limit Switch 1 No 1 NC for 630 Amp VCB trolly as per manufacturer including connection complete all as specified and directed.
Suppy only drive insulator for 630 Amp VCB trolly as per manufacturer including connection complete all as specified and directed.
Suppy only bus bar/VCB insulator for 630 Amp VCB trolly as per manufacturer including connection complete all as specified and directed.
Suppy only mechanism part for 630 Amp VCB trolly as per manufacturer including connection complete all as specified and directed.
Suppy only Spring charging motor with gear assembly supply 230 volts AC suitable for 630 Amp 11000 Volts VCB as per sample complete all as specified and directed. Make :Kirloskar Model No M-500
Suppy only FRP Vaccum Bottle Support suitable for 630 Amp 11000 Volts VCB as per sample complete all as specified and directed. Make :Kirloskar Model No M-500
Suppy only Space heater suitable for 630 Amp 11000 Volts VCB as per sample complete all as specified and directed. Make of VCB :Kirloskar/Crompton Greaves/Seimens
Suppy and fixing O/C and E/F relay suitable for 630 Amp 11000 Volts VCB as per sample including provision for fixing in existing panel by cutting/welding work all as specified and directed Make :Alstom/Schneider/ L&T (Model No. MC61ANX4000)
Supply, fixing, connecting and testing, in replacement, Voltmeters 11 KV, flush type 96x96 mm digital type with LCD display, suitable for 110 DC / 240 Volt AC supply, including cutting / welding work complete all as specified and directed.
Supply, fixing, connecting and testing, in replacement, Amp meters for 0-200 Amp, flush type 96x96mm digital type with LCD display, suitable for 110 V DC / 240 V AC supply including cutting / welding work complete all as specified and directed.
Supply, fixing, connecting and testing, in replacement, Power factor meters flush type 96x96 mm digital type with LCD display, suitable for 110 V DC / /230 V AC supply, including cutting / welding work complete all as specified and directed.
Supply and fixed LED indicator lamp 24 V DC / 230 V AC as per sample complete all as specified and directed.
Supply, installation, connecting, and testing of 11 KV single phase indoor resin cast CT of ratio 300/150/5-5A suitable for VCB as per existing type and make including taking down old unserviceable CT all as specified and directed. Make : Instrans/CG/Schneider
All as per Srl Item No 92.00 here-in-before but CT ratio 100/50/5-5A
Material & labour for cable tray of mild steel sheet 2mm thick 30cm width x 5 cm height with manufactures holes for water drainage fixed in existing duct by angle, nut, bolts as per site requirement and cables covered with wire mesh superior quality for protection from any mechenical damages as per sample including binding / cutting / welding work and painting to be carried out using synthetic enamel paint two coats one coat of red oxide complete all as specified and directed.
Material & labour for cast iron cover plate, 10mm thick with handle, heavy duty, for covering duct/trench behind VCB, size as per site requirement and as directed including cutting of holes where required for passing of cables complete all as specified and directed.
Supplying, laying, jointing & testing 2.5 Sqmm 4 core PVC insulated, armoured electric cable with flexible stranded copper conductor, 1100 volts grade complete including taking down old unserviceable cable any type and size all as specified and directed.
All as per Srl Item No 96.00 here-in-before but 2.5 Sqmm 10 core.
Taking out and relaying existing HT cable of any size / type after repairing defects etc complete all as specified and directed. Note : Excavation, earth work, sand cushioning and protection cover, cable joints shall be measured and paid for separately under respective items.
Shifting of transformer of capacity 50 KVA to 500 KVA from one place to other place on two/four pole structure or PCC plateform in old Amritsar cantt area including HT/LT connection complete all as specified and directed at site by Engr-in-Charge. (Note : All T&P and M/C required for shifting of transformer to be provided by the contractor and rates included in quoted rate of this item)
Supply and fixing chain link fencing, size 50mm x 50mm, 4mm dia including line wire, fixed to standards, rails, straining bolts etc including provision of binding wire and taking down old unservicable fencing of any type complete all as specified and directed.
Material & labour for hard core of brocken stone / boulders, of gauge not exceeding 63 mm deposited, spread and leveled in layers not exc.15 cms thick, each layer watered and rammed to a true surfaces complete all as specified and directed.
Material and labour for brick work with sub class 'B' bricks, old size, straight or curved on plan exceeding 6 metre mean radius, built in cement mortar 1:4 complete all as specified.
Material and labour for 15mm thick cement plaster in CM (1:4) on fair faces of brick or concrete surfaces and finishing the surface even and smooth without using extra cement complete all as specified.
Material and labour for applying three coats of white wash on walls including preparation of surfaces complete all as specified.
Material and labour for earthing complete with copper earth electrode of size 20mm dia, 450mm long, burried directly in ground by boring hole (boring hole not less than 25 to 27 metre deep below ground level vertically to a depth not less than 2.25 meters below ground level with minimum dia 125mm) and copper electrode connected to copper wire 8mm by means of GI nuts, bolts and washers etc, including provision of earth strip protected by 32mm dia GI light grade protection pipe from ground level to test point including layers of common salt, charcoal dust and chemical as recommended and testing on completion complete all as specified. Note:- (i) All T&P required for boring hole and other connected work shall be arranged by the contractor and cost thereof shall be inclusive in the quoted unit rate. (ii) The cost of excavation & earth work shall be included in the quoted rates. (iii) On testing, after completion, if desired earth resistance is not obtained, the earthing will be redone at no extra cost and quoted rates shall be to include this aspect.
Material and labour for earthing complete with GI earth plate electrode 600mm x 600mm, 6mm thick, burried in ground vertically to a depth not less than 2.25 metre below ground level with top edge of the earth plate to a depth not lesss than 1.5 meter below the ground level, earth plate surrounded by 15cm thick layers of common salt and charcoal dust starting from ground below 15 cm of earth plate and up to 15 cm above the same, GI plate connected with galvanised iron earth lead wire of 4mm dia by means of GI nuts, bolts and washers, wire laid in 15mm dia light grade GI pipe as protection from top of the plate up to test point (cost of protection pipe up to 7.5 meters from earth electrode will be included in the rates quoted by the contractor) with following:- (a) Test point of GI strip of size 32mmx6mm. (b) Watering pipe of GI pipe light grade 20mm bore from top of the earth electrode up to MS funnel with wire mesh embeded in floor of PCC earth pit. (GI Funnel should properly tightned on GI watering pipe and embeded in PCC floor of earth pit with open top suitable for watering of earth pits) (c) PCC earth pit 30x30x30cm constructed in PCC 1:2:4 type B1 exposed surfaces smoothly finished with 15mm thick cement mortar 1:6 plaster including RCC pit cover 25mm thick with 2 Nos MS handles of 12mm dia suitable for carrying of pit cover (d) Angle iron frame made of 40x40x4 mm angle iron PCC pit for holding the pit cover. Note:- (i) The cost of excavation & earth work shall be included in the quoted rates. (ii) Earth lead beyond 7.5 m from electrode to earth terminal shall be measured separately (iii) On testing, after completion, if desired earth resistance is not obtained, the earthing will be redone at no extra cost and quoted rates shall be to include this aspect.
R D Bansal
Raman Electric Trading Co
kailu construction co
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .