| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹45.1 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹49.9 L+₹55,320 (1.12%)Rejected-Finance | L2 | Rejected-Finance Not lowest | |
| 3 | L3₹53.1 L+₹3.7 L (7.54%)Rejected-Finance NO 18 8 254 26 RAKSHAPURAM SAIDABAD POST HYDERABAD 500 005 | HYDERABAD | HYDERABAD | TELANGANA | 500005 | L3 | Rejected-Finance Not lowest | |
| 4 | Rejected-Technical 8 51 PLOT NO 6 LIC COLONY SUJATA NAGAR PENDURTHY MANDAL VISAKHAPATNAM 530042 AP | 530042 | - | Rejected-Technical Not enlisted in particular category | |
| 5 | Rejected-Technical | - | Rejected-Technical Not enlisted in particular category |
Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
10 Aug 2022, 6:00 pmClosed
GE I R and D Kanchanbagh
GE I R and D Kanchanbagh Kanchanbagh Post Hyderabad 500058
REPAIR/REPLACEMENT OF UNSV 33KV/11 KV MRS, 11KV HT INSTALLATIONS, 11KV OH LINES AND UG CABLES, HT VCBs/SF6s BREAKERS, MAINT OF POWER/ DISTRIBUTION TRANSFORMERS, LT/HT SWITCHGEAR AND PANELS AND ITS CONNECTED ACCESSORIES AT DLRL KANCHANBAGH HYDERABAD
2022_MES_538062_1
GE I KBAGH TOKEN 16 OF 2022 2023
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Hyderabad
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE I R and D Kanchanbagh
₹98,000
Yes
8 Sept 2022
14 Jul 2022
12 Aug 2022
14 Jul 2022
10 Aug 2022
28 Jul 2022
15 Jul 2022 - 22 Jul 2022
Amount
Testing and setting the relays of incoming VCB's/SF6s of 33 KV by primary injection method of any make/model mechanical parts, cleaning inside & outside with CRC-26 spray including replacing the unserviceable minor parts like springs, gear, nuts, bolts and washers, internal wiring if necessary and lubricating all the complete to the entire satisfaction of Engr-in-charge.
Disconnecting and removing the unserviceable 33 KV burnt out six bolt clamps and supply and fixing new six bolt type Aluminium clamps suitable for panther aluminium jumpers / pipes including nuts, bolts, washers and testing complete all as specified and directed.
Dehydration and filtration of 2.5 MVA transformer 33/11 KVA, HT OCB oil indoor/outdoor/ isolation type at different location and different size of transformer from 63 KVA to 1000 KVA or any capacity Transformer on DLRL location with centrifuging machine, manually operated and achieve BDV 60 KV including carrying out oil testing before and after the dehydration process for each OCB complete all as directed. Note : Required oil for top up will be measured and paid separately under relevant item of schedule
Supply only topping up of Transformer/OCB oil as per IS :335, break down voltage not less than 60 KV all as specified and directed. Make :- Power Oil/Electrol
Supplying, installation, commissioning and testing in replacement of 33 KV Current Transformer (CT`s), indoor type, resin cast epoxy type, of 13.1 KA/Sec having ratio 40/5-5 Amps having Core1: Class 5P10, 10VA for protection , Core2: Class 0.5, 10VA for metering including associated wiring complete all as specified and directed
Supplying, installation, commissioning and testing in replacement of 11 KV Current Transformer (CT`s), indoor type, resin cast epoxy type, of 13.1 KA/Sec having ratio 150-75/5-5-1A Amps having Core1: Class 5P10, 10VA for protection , Core2: Class 0.5, 10VA for metering including associated wiring complete all as specified and directed
M&L for maintenance servicing, copper Bus Bar 10x70mm with HT tape as per required design 7 dimensions with NUT BOLTS including fixing charges all as directed.
Supply, laying, testing and commissioning in trenches/ ducts, fixed on walls/panels of LTUG cable, 1100 volts grade, PVC insulated, PVC unsheathed armoured with aluminum conductor cable complete including lugs of requied sizes for the following nominal cross sectional areas of cables including taking down old unserviceable cable complete all as directed:- Make: HAVELL'S/UNIVERSAL/CCI/GLOSTER/KEI/ POLYCAB/ KEC INTERNATIONAL (RPG)
4 core x 10 Sqmm
4 core x 16 Sqmm
4 core x 25 Sqmm
4 core x 35 Sqmm
3.5 core x 50 Sqmm
3.5 core x 70Sqmm
3.5 core x 95 Sqmm
3.5 core x 120 Sqmm
M&L for Servicing & Repairs to Air-break switch (isolator) off load, rotating type, 33 KV, 800 Amps to 1250 Amps capacity, with proper alignment of isolator rotating blades, with fixed contact jaws, arcing horns, applying petroleum jelly to moving mechanism, cleaning and lubricating to isolator gear box assembly, tightening all nuts, bolts and clamps of jumpers etc, repairing to isolator gear box assembly and making in proper serviceable condition for smooth functioning, testing and commissioning on load complete all as specified and directed.
S&F in replacement of LED indication lamp for breaker ON/OFF/TRIP/Breaker Spring Charged/R-Y-B etc for 11/33 KV (110V/30V DC supply) control panel including associated wiring, if reqd, complete all as specified and directed.
Supply, Lay cable in repairs 1100 volts with PVC insulated and steel armoured with multi stranded copper conductor of the sizes 16 core 2.5 Sq mm.
M & L for cutting and removing grass, vegetation bushes etc from surrounding HT installation as bushes grows during a period of contract and removing all rubbish to a distance not exceeding 50 m as directed.
M&L for Repairs/maintenance of 11KV HT VCB/OCB/SF6 breakers Panel including bus coupler of any type, size and capacity complete including the following :- Taking out 11KV HT VCB/OCB/SF6 breakers of 400/630/800 Amps rating trolley from HT Panel after switching off electric supply, checking of mechanical/motorised system for proper functioning of upward/downward movement of HT VCB trolley including opening the VCB & checking the quality of insulating. Cleaning & servicing the fixed/moving contact & blowing out dust from bus bar chamber, spout gear mechanism and applying the proper lubrication/greasing and cleaning/servicing the entire motorised mechanism of VCB including all spare parts required at site, reassembling the VCB connection, testing, commissioning and putting on load to the entire satisfaction of Engr-in-charge.
Earthing complete with copper plate electrode 600x 600 x 3.00 mm thick buried directly in ground vertically to a depth not less than 2.25 mtr deep below normal ground level with top edge of earth plate, not less than 1.5 mtr below normal ground level connected to copper strip earth lead of size 20 x 3 mm by means of bolts, nuts/check nuts and washers etc of galvanised iron, protected by galvanised iron pipe light grade 50 mm dia and connected to main switch/control board including necessary excavation earth work in any type of soil and PCC 1:3:6 type C1 for earth chamber, 40 mm thick RCC cover slab 1:2:4 type B1 with 6 mm dia TMT Bars at 140 mm cc both ways, watering pipe 20 mm dia light grade GI, funnel, wire mesh, lugs, charcoal and salt etc complete all as shown in Electrical plate No. 3 SSR Part I and testing complete including removing unserviceable any type of items all as specified and directed. Note : Copper strip and GI pipe 50 mm dia beyond 7.5 metres per earth will be measured and paid separately.
M&L Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated location for loop earthing etc. as required of size 32x6mm GI strip complete all as specified and directed.
Supply & Fix Gasket inreplacement for upto 2.5 MVA transformer (SRC RC 70C Grade) with including all required T&P for drain out and refilling trainsformer oil after proper filteration,comminissioning and testing complete complete all as directed.
All as per item No. 18 above Gasket replacement upto 800 KVA transformer (SRC RC 70C Grade).
Supply installing testing and commissioning in replacement the relay module Micom P111 making necessary cutting in the existing panel and necessary control wiring FRLS of size not less than 2.5Sqmm and providing Ferules for identification and necessary spares for fixing complete to the entire satisfaction of the Engr-in-Charge.
Testing and re-setting and calibration of protection relay of 11 KV RMU/VCBs/SF6 breaker (indoor/outdoor) for incoming and out going feeders with control panel and control cable differential relay once in a month through authorised service engineer, Checking of instruments function and taking corrective action for improvement if found improper, functioning complete all as specified and directed.
M&L for XLPE Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm.
M&L for XLPE Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm.
M&L for XLPE cable jointing kit for 11 KV (earthed) for outdoor termination heat shrink type joint complete with jointing material & accessories suitable for 240 to 300 sqmm, 3 core armoured aluminium conduct including taking down old unserviceable jointing kit complete all as directed.
M&L for XLPE cable jointing kit for 11 KV (earthed) for indoor termination heat shrink type joint complete with jointing material & accessories suitable for 120 to 185 sqmm, 3 core armoured aluminium conduct including taking down old unserviceable jointing kit complete all as directed.
M&L for XLPE cable jointing kit for 11 KV (earthed) for indoor termination heat shrink type joint complete with jointing material & accessories suitable for 50 to 95 sqmm, 3 core armoured aluminium conduct including taking down old unserviceable jointing kit complete all as directed.
Supply, fix, testing and commissioning of Air break gang operated switch, triple pole mechanically operated out door type with all fittings/accessories mounted on and including 11 KV HT polymeric insulators and steel channel frame, GI operating rod 25 mm dia of suitable length with operating mechanism worked from ground level vertically operated including locking arrangement for operating handle with and including 7 levers Navtal lock complete suitable for current rating of 400 Amps HT 11 KV working pressure all as specified and directed.
Supplying and laying un-reinforced precast concrete cable cover, class HVP, type 1 with peak, size 250mm x 150mm x 40mm lete all as directed.
M&L Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive on one primer coat, one under coat and one finishing coat of paint all as directed.
Supply, Install and erect steel tubular swaged pole type 410 SP-31 of 9.0 mtrs long complete with cast iron base plate finial taper plug, pole cap, bolts, nuts and washers pole made out of MS tubing confirming to IS-2713 Part-II, including drilling of holes painting with two coats of bituminous paint internally and externally embedded portion in ground/concrete and painting to exposed surfaces with two coats aluminium paint and one coat of red oxide primer complete all as specified and directed. Note :- Excavation/Earth work in any type of soil/ strata PCC foundation, coping of poles, cross arms, clamps shall be measured and paid separately. Make :- M/s Bombay Tubes/ M/s Jindal Steel Products/ M/s India Tubes Co/ M/s Bharat poles/ National Tubing.
Material and Labour for PCC 1:3:6 type C2 wiring 40 mm stone aggregate for foundation of poles/transformer bed/cable duct foundation/panel base/ chain link supports etc including necessary form work etc complete all as specified and directed.
Material and Labour for PCC 1:2:4 type B1 wiring 20 mm graded stone aggregate for coping of pole including necessary form work etc complete all as specified and directed.
Material and Labour for Brick work with fly ash bricks sub-class 'B' bricks straight or curved on plan exc 6m mean radious in CM (1:6) complete all as specified and directed.
Material & Labour for 10mm thick rendering in cement motar (1:6) mixed on brick or concrete surfaces finished even & smooth w/o using extra cement complete all as specified and directed.
Material & labour 3M 1602-R electriccal insulating sealer to bushings, insulators, current transformer, potentional transformers & cable Kits complete all as specified and as directed.
M&L for spreading the 20mm coarse aggregate in various sub stations and other locations complete all as directed.
M&L for spreading the 40mm coarse aggregate in various sub stations/Structure premises and other locations complete all as directed.
M&L for Isolate, disconnect, dismantle the burnt out lugs from main switches/ MCCB and crimping with new lugs as per existing one including fixing, insulation, termination to main switch/MCCB for the following sizes of cables complete all as directed.
35 sqmm to 50 sqmm
70 sqmm to 95 sqmm
120 sqmm to 240 sqmm
240 sqmm to 300 sqmm
M&L for Preparation of old painted inner/outer surfaces of indoor/out door HT/LT panels, spray painting the same with two coat of synthetic enamel paint(RAC 7032) simens grey to achive smooth finish including writing of SM/MES No complete all as directed.
Supply and fix in repairs of Alarm annucator 12 window of model MBAS-0600 suitable for 33/11KV HT breaker complete all specified and directed.
S&F cable jointing kit for straight through joint (epoxy) for 1.1 KV grade XLPE, PVC insulated and sheathed aluminium conductor under ground cable including thimbles, nuts & bolts, washers etc and testing after jointing complete, all as directed for the following sizes. Make: M-seal/Raychem/Transeal/Denson
6 sqmm to 16 sqmm 4 core
25 sqmm to 50 sqmm 3.5 core
70 sqmm to 120 sqmm 3.5 core
Material and labour painting of HT two pole structure 11 KV complete by scrapping the existing old paint and making the surfaces smooth including cross arms bracings complete and applying two coats of synthetic aluminium paint complete all as specified and directed.
All as per Item No: 41above but four/Six pole structure Make of Paint for item No. 41 & 42 : Asian/Nerolac/Berger
Labour for cutting the bushes and plants grown near the substation/ structures premises using necessary tools and plants and removing the plants from the root level at any depth and cleaning the premises completely and making good the site suitable for spreading the stone aggregate including disposing all the waste to a distance not exc 50M from the site all as directed by the Engr-in-Charge.
M&L for Pin type, porcelain, vitreous, white,brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 50mm height, 65/100mm dia for 550 volts grade complete all as directed.
M&L in replacement of Shackle Type insulator 1100V 100mm height 115 mm dia same as per existing complete.
Cutting of trees and tree branches of girth up to 20cm and to a radius of 3M all around LT/HT OH line complete all as directed. Note: The distance between two adjacent poles will be considered as one span.
M&L 11KV grade pin type, composite polymeric insulator of clevis/Tounge/socket or ball type spindle including nuts and bolts of size type as specified by the manufacturer conforming IS- 61109 including all galvanised steel disc fittings as required at site and removing of unserviceable insulators complete all as specified and directed. Make :- Jaipuria/Rashtriya Electrical/Denson or make approved in the state Electricity board
M&L 11KV grade suspension type, composite polymeric insulator of clevis/Tounge/socket or ball type spindle including nuts and bolts of size type as specified by the manufacturer conforming IS- 61109 including all galvanised steel disc fittings as required at site and removing of unserviceable insulators complete all as specified and directed. Make :- Jaipuria/Rashtriya Electrical/Denson or make approved in the state Electricity board
M&L in replacement horn gap fuse assembly mounted on porcelan insulator and steel frame, D or Channel type for HT 11 KV, 400Amps rated current including base frame made with 'C' channel cross arms of suitable size shall be robust enough to sustain the various stresses encountered during all operational conditions of the cutout and necessary reconnecting all the wires/cables etc including removing the unserviceable drop out fuse assembly complete all as specified. Note: Fuse assembly for three phases will be considered as one Set.
M&L in replacement of Lightning arrester expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo Amp connecting to the earth strip including necessary fixing spares as required at site all as specified and directed. Note: A set of three lightening arresters will be considered as one set .
Repairs to AB switch (GOD) including replacement of male and female contacts, bolts & nuts and cleaning the carbon/ dust deposited on the switch contact surfaces and applying mineral jelly, oil grease to the moving/rotating parts etc after cleaning, removing carbon deposits including testing and commissioning the same for operation complete all as directed by Engr-in-charge. Note: The repairs to three poles of AB switch will be measured as on job.
Labour only for removing the binding of ACSR conductor of HT 3 phase 4 wire over head line from insulator, removing the jumper, connector, service wire, UG cable and restringing the existing ACSR conductor of any size, length, span upto desired sag and fixing the same ACSR conductor on insulator by proper binding, jumper connection etc complete all as specified and directed.
M&L in replacement the tinned copper fuse wire single pole of 11000 volts grade of rating 25Amps and up to 50Amps.
M&L in replacement the tinned copper fuse wire single pole of 11000 volts grade of rating 50 Amps up to 100Amps.
S&F rust free Acrylic Danger notice plate duly marked voltage danger and conventional skull and bones in signal red colour written in one local language and english with retro reflective stickering and fixing with GI/MS. clamps, bolts and nuts of approved size, for LT 440volts all as specified.
All as per item No. 55 above but for HT 11000 volts.
M&L for EPR high voltage adhesive insulating tape in replacement for cable insulation of dielectric strength 38.3Kv/min fr indoor cable insulation all as specified. Make: Transeal/ Denson/ Rachem.
Material and labour for locating UG cable fault through high voltage UG cable testing van through TSSPDCL or any authorised service provider in HT cables of any size or distance complete all as specified and directed to the entire satisfaction of Engr-in-Charge.
Material and labour for tracing the cable route using ultra sonic cable route locator of any HT/LT UG cables complete all as specified and directed.
Supply and fixing rectangular RCC cable route indicator of size not less than 1m long with curved on top surface duly marking with size of cable, location including painting with two coats of synthetic enamel paint on surface directed.
Supply and fix in repair of Impluse Emergency First aid kit box with basic medicine like Band Aid strips of min 20 Nos, Anteseptic cream, Cotton, Surgical tape 1 inch, non sterial gauge swabs, Hydrogen peroxide bottle, medical spirit bottle complete all as specified and directed.
M&L for fabricating feeder distribution layout board on ACP sheet of thickness 3mm and size as required at site designing the layout as per the sketch provided by the Engr-in-charge using ecosolvent print including lamination and fixing to the wall/50mm steel pipe using necessary fixing nuts, bolts and spares as required at site. The job includes removing of old layout board from its position complete all as specified and directed.
Disconnectiong and taking down the unserviceable gang operationed device unit of 33 KV complete from the structure for repairing including replacement Male contacts/movingg contact blads (set of 3) Female contacts/fixed contacts (set of 3) Tinned copper flexible jumpers and applying mineral jelly oil grease after proper removal of carbon deposit and refixing of switch AB gang operated triple pole mechanically operated mounted on isolator and steel frame with operating mechanism worked from ground level from current rating upto 800 A,33 KV grade horizontal/vertical type complete all as directed all as directed by Engineering-in- charge.
Supply and fix in repairs pad 4 hole/6 hole clamps,pipe clamps suitable size for 33KV jumper in structure.
Material and Labour for cutting existing BT road/PCC of size 45cm x 60cm for taking out/laying of underground cable and including necessary earth work and refilling the same in layers well ramming including watering as required and matching with the existing surface with 200mm thick PCC 1:2:4 type B1 and curing the same with wet gunny bags and removing debris to a distance not less than 50m complete all as specified and directed.
Supply and lay GI tubing 100mm dia, light grade for cable protection at road crossing/on poles and tubing sealed at bith ends after laying the cables including taking out old GI tubing complete all as directed.
All as per iem No 66 here-in-before but 80mm dia Make for item Nos.66 & 67: ZENITH/ TATA/ JINDAL/SWASTIC
S&F in repairs MCCB 200 Amps, 4 pole 50 HZ 35 KA thermal magnetic, adjustable S/c, O/c settings Icu= 100% complete all as directed.
S&F in repairs MCCB 100 Amps, 4 pole 50 HZ, 4 pole 50 HZ 16 KA thermal magnetic, adjustable S/c, O/c settings Icu= 100% complete all as directed.
S&F in repairs MCCB 125 Amps, 4 pole 50 HZ , 4 pole 50 HZ 16 KA thermal magnetic, adjustable S/c, O/c settings Icu= 100% complete all as directed.
S&F in repairs MCCB 400 Amps, FP, 50HZ, 4 pole 50 HZ 35/36KA thermal magnetic, adjustable S/c, O/c settings Icu= 100% complete all as directed.
S&F in repairs MCCB 630 Amps, 4 pole 50 HZ, 35/36 KA , complete all as directed. Note for item No. 71 to 72: Cost of fixing on to walls/surface on suitable angle iron bracket support and civil work shall be included quoted rate.
S&F in replacment MCCB enclosure of suitable size for MCCBs 4P upto 250Amps capacityof existing size complete all as directed.
S&F in replacment MCCB enclosure of suitable size for MCCBs 4P 400/630Amps capacityof existing size complete all as directed.
Supply and Fixing Battery cell UPST 100 for 110V or 30 V Battery Bank including taking down old battery complete all as directed. Make :- Exide - UPST 100 or AMARON
Disconnection of all Primary/Secondary connection of the defective transformer of any KV rating, out door / indoor any make taking down / out from plinth / pole / platform with the help of crane and transporting the same carefully to workshop for repair and bringing back and install, with all connections as per directions, after repair to its existing position, upto 2.5MVA capacity of transformer complete with testing and commissioning, complete all as directed.
Opening of the 11 KV / 0.433 KV transformer 800 KVA to 1000 KVA by removing the inspection cover / top cover, decanning of the transformer oil up to the required level for replacement of leaked cork seal with insulator or LT/HT bush (which is unsv) complete from the shell and making again connections of LT/HT bush to avoid leakage of oil refilling back to existing oil into the transformer testing & commissioning complete all as directed Note : HT/LT bush will be measured and paid separately under relevant item and cork seal with insulator is deemed to be included in quoted rate.
M&L for opening the top of Transformer upto 2.5 KVA for renewal of jumpering (with brazing or welding) with new copper wire of existing size after removal of burnt out internal copper links from winding top to studs including decanning of oil upto required level and testing the tranformer complete all as directed.
Making Primery/Secondary coil with insulating copper wire of required gauge craft paper cotton tape HT/LT insulation as per specification of old transformer including making of coil as required of any capacity of transformer of any voltage and range including removing burnt out windy complete all as directed .
Supply and fixing of HT bushing including metal parts and washer complete for any make of plinth/pole mounted transformer 1000 KVA to 2.5 KVA capacity complete all as directed.
Supply and fixing of LT rod / studs for Up to 2.5 KVA capacity KVA transformer made of brass with nuts and washers, Insulator and fittings etc as per size and shape of original complete all as directed.
Supply and fixing of HT bushing including metal parts and washer with complete set for any make of plinth/pole mounted transformer up to 630KVA capacity complete all as directed.
Reconditioning of over heated 33/11 KV coil of transformer from to 1000 to 5000 KVA after removing all old insulation any type and re-insulation as required and remaking of coils complete all as directed .
M&L in replacement of analog type Winding tempreture indicator ,50-60 HZ ,110-220 V IP 48 temperature 0-160 degree mild steel body and indicator for oil/ temperature for any type/size /capacity transformer all as specified and directed.
M&L in replacement of analog type Oil tempreture indicator, 50-60 HZ,110-220 V IP 48 temperature 0-160 degree mild steel body and indicator for oil/ temperature or any type/size /capacity transformer all as specified and directed.
M&L in replacement of Mog Magnetic oil level indicator,of aluminium body, industrial use of size 1500mm, temparature indication upto 30 DC , works on max pressure 4Kg/sqcm accuracy 95% complete for any type/size /capacity transformer all as specified and directed.
M&L in replacement of buchholz relay/gas operative relay of existing size and shape all as specified and directed
M&L Earthing complete with galvanised steel earth plate electrode 600x600x6mm thick, buried directly and preferably vertically in ground ( earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to galvanised iron strip of 25x4mm (upto 7.5 M in length from earth plate) by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 5, connected to earthing test point all as specified including earth work and excavation in any type of soil, PCC 1:3:6 type C1 chamber and RCC 1:2:4 type B1 cover 40 mm thick, with 8 mm dia steel deformed (TMT bars) reinforcement at 150mm c/c both ways, 40 mm dia GI light grade pipe for earth lead protection, 20 mm dia GI light grade pipe for watering , water funnel, testing point etc., complete all as specified and testing on completion.
M&L for common salt to fill in existing earthing pit to recharge the pit all as specified and directed.
M&L in repairs for 2 core round flexi copper wire of 1sqmm dia for AC/DC supply connections to VCBs/SF6 with suitable size glands and insulated lugs of required qty complete all as directed.
Testing protection by secondary injection method and other relays such as IDMT, Over current earth fault relays, auxilary relays, such as VAJ 10C & VATH relays provided on 33 KV Breakers and servicing of relays complete all as directed.
Testing and calibration of protection Over current and Earth Fault relays numerical type P-111/123 complete all as directed.
Testing and calibration conducting stability test of transformer 33/11 Differential relay complete all as directed.
Supply, erect, Testing & Commissioning of numerical directional over current & earth fault relay model Micon P-642 complete control wiring with material programming /setting /calibration including software of relays required and necessary addition/alternation of panel alongwith dismantling of old unserviceable old type of relay. Make- Schneider or eqiuvalent in ABB/L&T/SEIMENS.
Dismantling of old unserviceable Panel and Supply & fabrication of LT Panel Board CPRI approved cubical type made of 2 mm thick sheet steel indoor type with IP-43 mounting on suitable 'C' channel base frame at not less than 50mm unit with locking arrangement in front and back openable inspection doors PVC sleeved Aluminium bus bar of 1000 Amps for each phases and half neutral fixed on suitable epoxy insulators all housed in suitable bus bar chamber and cable alloy including provision and fixing of digital Voltmeter -01 No, Ammeter-01 No multifunction meter with V,A,VA,W,KWH,of -01 No CTs of suitable ratio, and Indicating LED type lamp for Red, Yellow and Blue in incomer phases complete along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable cable glands etc fixed on suitable PCC foundations, testing and commissioning complete and consisting the following :- (Drawing of Panel and connections shall be submitted for approval of accepting officer before starting the panel work. (a) MCCB 4 Pole 630 Amps 36KA thermal magnetic ,adjustable S/c,O/c settings Icu=100% ICS-01 No. (as Incoming) (b) MCCB 3 Pole 400 Amps 25KA thermal magnetic ,adjustable S/c,O/c settings Icu=100% ICS -02 No. (as Outgoing) (c) MCCB 3 Pole 350 Amps 25KA thermal magnetic ,adjustable S/c,O/c settings Icu=100% ICS -03 Nos (as Outgoing) (d) MCCB 3 Pole 100 Amps 16KA thermal magnetic ,adjustable S/c,O/c settings Icu=100% ICS -01 Nos
Dismantling of old unserviceable Panel and Supply & fabrication of LT Panel Board CPRI approved cubical type made of 3.15 mm thick sheet steel outdoor type inner comportments made of 2mm thick CRCA heat powder coated with IP 65 grade of protection CRCA sheet powder coated with support of angle iron of 50 x 50 x 6 mm angle with double hinged front openable shutters of each feeder control unit with locking arrangement in front and back openable inspection doors PVC sleeved Aluminium bus bar of 400 Amps capacity for each phases and half neutral fixed on suitable insulator all housed in suitable bus bar chamber and cable alloy including provision and fixing of digital Vmultifunction meter with V,A,VA,W,KWH,of -01 No of suitable ratio, and Indicating LED type lamp for Red, Yellow and Blue in incomer phases complete along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable cable glands etc fixed on suitable PCC foundations, testing and commissioning complete and consisting the following :- (Drawing of Panel and connections shall be submitted for approval of accepting officer before fabricating the panel work. (a) MCCB 4 Pole 250 Amps 36KA thermal magnetic ,adjustable S/c,O/c settings Icu=100% ICS -01 No. (as Incoming) (b) MCCB 3 Pole 100 Amps 25KA thermal magnetic ,adjustable S/c,O/c settings Icu=100% ICS -03 Nos (connected-02 & Spare-01) (as Outgoing) (c) Strret light timer control unit compressing MCb TPN,contactors,Analog timer switch,bypass switch,relay & indication lamp with control wiring suitable for 12 KW capacity.
M&L for factory repairing reconditioning of by authorised service workshop 11 KV Sulphur Hexafluoride breaker defective pole assembly of type 63D, KEC make including Gas Charging (SF6) and testing and commissioning complete all as directed. Note:- Quated rates are deemed to be including transport material required envelope,FRP links Gas Rings,Membrane,Aluminium Silicate, Mesh box,Pressure switch& filling of Gas
Charges for fixing for SF6 pole assembly to the breaker after repair and testing of breaker and charging at site including packing Note:- Nature of work Assembly of poles Assembly replacment of pole Assembly Gas filling and testing.
M & L for Inspection and servicing of OLTC of transformer of capacity 1.5 MVA and checking the electrical/manual operation of tap changer mechanism, check the integrity of the active components /contact surface mating for all tap positions, voltage ratio test for all tap position etc including cleaning of the OLTC complete all as directed. Note : The Contrator shall be responsible for correct servicing of the OLTC and servicing to be done through OEM of OLTC.
Supply and fix in repairs wiring and commissioning including thormostate switch space heater 200w for VCB/SF6 breaker/RMU complete all as directed.
M&L for repairs servicing CT/PT wiring with required material all as directed.
Servicing of capacitor bank 200 KVAR, 12 KV, 3 Ph Dry Type Series Reactor and checking of capacity of capacitor including control & power wiring, barrel fuses cleaning of spare parts including testing of relay & contactor, tightening of nuts/bolts etc after taking shutdown as per electrical safety norms complete all as directed Note: Spares costing upto Rs 1500.00 shall be deemed to be included the in quoted rate.
Supply and fix 11 KV voltage transformer (Potential Transformer) Ratio1100/110Volts- V3 complete wiring testing and commissioning complete all as per directed.
Supply and fixing Kirloskar 11 KV safety shutters as per site requirement including painting and fixing of safety nuts and bolts complete all as directed.
S&F Tripping coils for sulphur hexafluoride (SF6) breakers operated on 30/110Volts DC including taking down old unserviceable coil complete all as directed.
Supply and installation of Spring Charging Motor for breaker including taking down of old Unserviceable spring charging motor complete all as directed.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in soft loose soil for foundation of poles, structures, stay rods, laying of underground cable etc complete all as directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers each not exceeding 25cm thick using soil complete all as directed.
Removing excavated surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as directed.
Supply and spreading of natural, clean, dry, river sand in trenches for cable protection / transformer yard/ two pole structure yard complete all as directed. Note:- Punned thickness only shall be measured for payment purpose.
Supplying and laying synthetic Rubber insulated mats 3mm thick for voltage upto 3.3 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and directed.
All as per item No.112 above but 2.5 mm thick for voltage upto 11KV (size 2x1m).
M&L for opening the top of Transformer upto 1000 KVA for renewal of jumpering (with brazing or welding) with new copper wire of existing size after removal of burnt out jumpering including decanning of oil upto required level and testing the tranformer complete all as directed.
S&F in repairs Silica gel complete all as directed.
M&L for replacement of UNSV push button of existing size in breakers/panels complete all as directed.
S&F 11 KV top or bottom bushing with internal bus bar supporting insulator complete all as directed.
hari enterprises
saradhi construction combines
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .