| Sl No | Description | Qty | Unit | NATIONAL ELECTRO-MECH COMPANY L3 | PERFECT ELECTRICAL WORKS L1 | BEE AAR ENTERPRISES L2 |
|---|---|---|---|---|---|---|
| 1.01 | Replacement of damaged 250 KVA control panel and other allied works of dewatering pumping station situated at RRL Canal Road, Jammu by way of replacement of existing damaged panel & cables by designing, fabrication, Installation, testing & commissioning of new LT control panel cum automatic starter suitable for 75HP motor.
Incoming Feeder: The incoming feeder must be equipped with a 250 amp MCCB of suitable breaking capacity & 1 No. Main switch-300 Amp capacity. There must be Al. bus bars for all the three phases and Neutral on the outgoing of the MCCB. The panel must be fitted with 01 No. Volt cum ampere meter showing voltage and current of all the three phases and RYB phase indicator lamps. | 1 | Job | 3,49,000 ₹3,49,000 | 3,34,999 ₹3,34,999 Lowest | 3,44,700 ₹3,44,700 |
| 1.02Outgoing Feeder no. 1: The outgoing feeder is to be used for the operation of up to 75 HP motor. Following items must be fitted in this feeder: 1. 03 No. air break contactors. Not Les than 110 Amp. 2. Star-Delta timer. 3. Motor Protection relay having all the features such as Overload, short circuit, under current, phase unbalance, Phase sequence, Phase Loss, Earth fault, Prolonged Starting/ Stalled rotor. The relay is be fitted on the door and it must be accessible by keeping the door of the panel closed. 4. Single Phase preventor. 5. 01 No. digital ampere meter showing current (0-100 amp) showing the current the three phases along with current transformers. 6. 02 No. indicator lamps for ON and TRIP indication. 7. 02 No. Push Buttons for ON/OFF. 8. 10 amp MCBs for protection of the control wiring. 9. Auto start with on delay timer and Time clock. | ||||||
| 1.03The cabling of the Control panel must be done with the suitable rating multi strand copper cable to withstand the full load of running motors. The internal control wiring should be done with flexible PVC LT cable with proper thimbing at each end. The job also includes the P/F of 30 mtrs single core copper cable of 50 sq.mm from Main switch to panel & 20 mts ,3 core 35 sq mm Cu Cable for the connection of LT Panel from bus bar to motor. The LT panel shall be dust and vermin proof fabricated out of 14/16 SWG CR sheet supported on MS angle of Suitable size and provision for fixing it on the ground with the help of foundation Bolts. The panel should be sturdy enough for vibration free operation and should be equipped with suitable locking/ sealing arrangement for each box. The structure should be provided with the suitable entry and exit holes for incoming and outgoing cables. The Panel should be given two coats of anti-rust primer and two coats of enamel paint for smooth and even finish. Complete job includes cost of panel/ material, labour charges, transportation/ shifting charges up to site of work, including installation, testing and commissioning on turn key basis. | ||||||
Tender Value
₹3.5 L
EMD Value
₹7,000
Closing Date
18 Oct 2025, 6:00 pmClosed
Executive Engineer
S and D Div. West Jammu
Replacement of damaged 250 KVA control panel and other allied works of dewatering station situated at RRL Canal Road, Jammu. Contract No SDJ/W /27/2025-26
2025_HAUDD_291258_1
E-NIT No 18 of 2025-26 Dated 08-10-2025
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
30 days
Jammu
refer PQ terms and conditions
3 documents required · 3 mandatory
₹600
Executive Engineer, S and D Div. (West), Jammu
₹7,000
29 Oct 2025
8 Oct 2025
20 Oct 2025
8 Oct 2025
18 Oct 2025
8 Oct 2025
Amount
Replacement of damaged 250 KVA control panel and other allied works of dewatering pumping station situated at RRL Canal Road, Jammu by way of replacement of existing damaged panel & cables by designing, fabrication, Installation, testing & commissioning of new LT control panel cum automatic starter suitable for 75HP motor. Incoming Feeder: The incoming feeder must be equipped with a 250 amp MCCB of suitable breaking capacity & 1 No. Main switch-300 Amp capacity. There must be Al. bus bars for all the three phases and Neutral on the outgoing of the MCCB. The panel must be fitted with 01 No. Volt cum ampere meter showing voltage and current of all the three phases and RYB phase indicator lamps.
Outgoing Feeder no. 1: The outgoing feeder is to be used for the operation of up to 75 HP motor. Following items must be fitted in this feeder: 1. 03 No. air break contactors. Not Les than 110 Amp. 2. Star-Delta timer. 3. Motor Protection relay having all the features such as Overload, short circuit, under current, phase unbalance, Phase sequence, Phase Loss, Earth fault, Prolonged Starting/ Stalled rotor. The relay is be fitted on the door and it must be accessible by keeping the door of the panel closed. 4. Single Phase preventor. 5. 01 No. digital ampere meter showing current (0-100 amp) showing the current the three phases along with current transformers. 6. 02 No. indicator lamps for ON and TRIP indication. 7. 02 No. Push Buttons for ON/OFF. 8. 10 amp MCBs for protection of the control wiring. 9. Auto start with on delay timer and Time clock.
The cabling of the Control panel must be done with the suitable rating multi strand copper cable to withstand the full load of running motors. The internal control wiring should be done with flexible PVC LT cable with proper thimbing at each end. The job also includes the P/F of 30 mtrs single core copper cable of 50 sq.mm from Main switch to panel & 20 mts ,3 core 35 sq mm Cu Cable for the connection of LT Panel from bus bar to motor. The LT panel shall be dust and vermin proof fabricated out of 14/16 SWG CR sheet supported on MS angle of Suitable size and provision for fixing it on the ground with the help of foundation Bolts. The panel should be sturdy enough for vibration free operation and should be equipped with suitable locking/ sealing arrangement for each box. The structure should be provided with the suitable entry and exit holes for incoming and outgoing cables. The Panel should be given two coats of anti-rust primer and two coats of enamel paint for smooth and even finish. Complete job includes cost of panel/ material, labour charges, transportation/ shifting charges up to site of work, including installation, testing and commissioning on turn key basis.
BEE AAR ENTERPRISES (BID ID -2600029)
NATIONAL ELECTRO-MECH COMPANY (BID ID -2603681)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Document
0.30 MB
BOQ
BOQ • 0.26 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .