Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.2 LAccepted-AOC | L1 | Accepted-AOC Being 1 L1 bidder | |
| 2 | L2₹37.7 L+₹92,605 (2.52%)Rejected-Finance | L2 | Rejected-Finance Not being a
lowest
tenderer | |
| 3 | L3₹37.9 L+₹1.2 L (3.30%)Rejected-Finance NEAR PUMP HOUSE ROAD NEAR RED ROSE SCHOOL BABINA CANTT JHANSI DISTT UP 284401 | JHANSI | UTTAR PRADESH | 284001 | L3 | Rejected-Finance Not being a
lowest
tenderer | |
| 4 | L4₹41.4 L+₹4.7 L (12.7%)Rejected-Finance | L4 | Rejected-Finance Not being a
lowest
tenderer |
Tender Value
Refer Docs
EMD Value
₹90,000
Closing Date
16 Sept 2020, 6:00 pmClosed
GE BABINA
GE BABINA CANTT 284401
REPAIR /MAINTENANCE OF DG SETS , AMF PANELS ,VARIOUS AIR CONTIONING / AC PLANTS AND LIGHTENING CONDUCTORS INCLUDING EARTHING SYSTEMS UNDER GE BABINA CANTT
2020_MES_370575_1
GE/BAB/TOKEN /37 OF 2020-2021
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE BABINA
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE BABINA
₹90,000
Yes
19 Dec 2020
19 Aug 2020
18 Sept 2020
19 Aug 2020
16 Sept 2020
2 Sept 2020
Amount
General servicing of DG Set including 'B' Check ,cleaning of machine,cleaning of fuel tank, checking of oil level, tension in fan belts,checking and repair of leakages in hose pipe, proper adjustment of tappet, checking of Governor control assembly, radiator and ensure the smoke less and fluctuation less voltage supply after servicing.complete all as per manufactaures recommendations for DG set of 300KVA Cummins capacity Make:- Cummins Note:. (i) Fuel filter ,Engine Oil and Coolent shall be measurd & paid separately under relevent items of Sch 'A'. (ii)'B' check shall be carried out on running of 500 hrs or 6 months which ever is earlier. (iii) Any service or repair to the DG sets under any item of DG set repairs schedule will be carried out through technician of authorized service dealer of manufacture/ make of DG set. Contractor has to provide his visit charges/ accommodation/ transportation etc and sub letting or local service agent will not be allowed. Contractor has to quote his rates keeping in view these aspects. (iv) Any repair/ defects / services required for DG set will be intimated via telephone/ mobile/ SMS/ e-mail followed in writing to contractor. These repairs /defects// services will be attended, completed and DG sets have to be made functional within 72 Hrs after intimation failing which a penalty of Rs 3000/- per day per DG sets will be charged from Contractor’s dues/ payment.
All as per item No:01 but DG Set of 160KVA to 200 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:01 but DG Set of 50KVA to 100 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:01 but DG set of 30 KVA to 40 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:01 but DG set of 10 KVA to 15 KVA Make:--Mahindra,Cummins,Kirloskar,Ashokleyland
Taking out existing defective Fuel filter element primary and secondary with ring and washer for DG set of 300KVA Make:- Cummins and material and labour for new Fuel filter in existing position and satisfactory testing complete all as specified and directed by Eng-in-Charge.
All as per item No:06 but DG Set of 160KVA to 200 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:06 but DG Set of 50KVA to 100 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:06 but DG set of 30 KVA to 40 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:06 but DG set of 10 KVA to 15 KVA Make:--Mahindra,Cummins,Kirloskar,Ashokleyland
Taking out existing defective oil filter element with ring and washer of DG set of 300KVA Make:- Cummins and material and labour for new Oil filter in existing position and satisfactory testing complete all as specified and directed by Eng-in-Charge.
All as per item No:11 but DG Set of 160KVA to 200 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:11 but DG Set of 50KVA to 100 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:11 but DG set of 30 KVA to 40 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:11 but DG set of 10 KVA to 15 KVA Make:--Mahindra,Cummins,Kirloskar,Ashokleyland
Taking out existing defective Air cleaner element with ring and washer ofDG set 0f 300KVA Make:- Cummins and material and labour for new Air cleaner element in existing position and satisfactory testing complete all as specified and directed
All as per item No:16 but DG Set of 160KVA to 200 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:16 but DG Set of 50KVA to 100 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:16 but DG set of 30 KVA to 40 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:16 but DG set of 10 KVA to 15 KVA Make:--Mahindra,Cummins,Kirloskar,Ashokleyland
S & F in replacement "V" belt for Radiator fan of any size suitable to DG set 10KVA to 300 KVA capacities,
S & F in replacement rubber hose pipe set with clamps suitable for DG set of 300KVA capacities Make:- Cumminss
All as per item No:22 but DG Set of 160KVA to 200 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:22 but DG Set of 50KVA to 100 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:22 but DG set of 30 KVA to 40 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:22 but DG set of 10 KVA to 15 KVA Make:--Mahindra,Cummins,Kirloskar,Ashokleyland
Taking out of FIP along with its accessories from DG Set 160/200 KVA Make :-CUMMINS/MAHINDRA/KRILOSKAR including transpotation to authorised service center for Overhauling repair/recalibration and refixing of DG Set including replacement of necessary parts such as nozzel/injection delivery valve holder benjo bolt copper washer roater bearing etc including testing complete all as specified and directed
All as per item 27 but DG set capacity 50 KVA to 100 KVA.
All as per item 27 but DG set capacity 10 KVA to 40 KVA.
M&L for servicing, repairing, maintenance of alternator assembly of DG set of 300/200/160KVA Make:- Cummins,Mahindra by decoupling alternator from DG set and strip opening of the alternator replacement of carbon bush holder, with carbon bush, mospeds, capacitor rectifiers and refixing the same in original position with satisfactory testing complete all as specified and directed
All as per item No 30 above but DG set of 62.5/50/100 KVA Make:-CUMMINS/MAHINDRA/KRILOSKAR
All as per item No 30 above but DG set of 10/15/30/35/40/KVA Make:-CUMMINS/MAHINDRA/KRILOSKAR
Taking out burnt armature winding wire and rewinding of armature with super enamelead copper winding wire of existing gauge of 160 KVA to 300 KVA DG Set insulation of armature of class 'B' insulation and varnishing of armature and drying upto desired temperature and Re-assembling of rotor and stator after rewinding and refixing of alternator with engine by assembling flexible coupling with alternator mouting with nut bolts including making cable connection complete including testing and commissioning at desired load of DG Sets complete all as specified and directed
All as per item 33 but DG set capacity 50 KVA to 100 KVA.
All as per item 33 but DG set capacity 10 KVA to 40 KVA.
Taking out burnt field coil and rewinding of field coil with super enameled copper winding of existing gauge of 160 KVA to 300 KVA DG Set insulation of armature of class 'B' insulation and varnishing of field coil and drying upto desired temperature and Re-assembling of rotor and stator after rewinding and refixing of alternator with engine by assembling flexible coupling with alternator mouting with nut bolts including making cable connection complete including testing and commissioning at desired load of DG Sets complete all as specified and directed
All as per item 36 but DG set capacity 50 KVA to 100 KVA.
All as per item 36 but DG set capacity 10 KVA to 40 KVA.
M & L for taking out radiator and connecting parts of DG set 160KVA to 300 KVA for repair,welding,brazing,leak testing, descaling & refixing to DG set to its original position and testing on load for DG Sets of Make Kirloskar/Cumins/Greaves / Mahindra /Sudhir complete all as directed.
All as per item 39 but DG set capacity 50 KVA to 100 KVA.
All as per item 39 but DG set capacity 10 KVA to 40 KVA.
S & F in replacement solonid Switch for 165 to 300 KVA DG set and testing complete for proper functioning for DG sets of Make Kirloskar/Cumins/Greaves/ Mahindra/ Sudhir complete and testing all as directed..
S & F in replacement solonid Switch for 50 to 100 KVA DG set and testing complete for proper functioning for DG sets of Make Kirloskar/Cumins/Greaves/ Mahindra/ Sudhir complete and testing all as directed..
S & F in replacement solonid Switch for 165 to 300 KVA DG set and testing complete for proper functioning for DG sets of Make Kirloskar/Cumins/Greaves/ Mahindra/ Sudhir complete and testing all as directed..
M & L for servicing, repairing, maintenance of self starter assembly of DG set 0f 300KVA capacity complete with switch magnet, carbon set, field coil, clutch assemble, solenoid switches and refixing the same in original position complete all as specified and directed.
All as per item No:45 but DG Set of 160KVA to 200 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:45 but DG Set of 50KVA to 100 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:45 but DG set of 30 KVA to 40 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:45 but DG set of 10 KVA to 15 KVA Make:--Mahindra,Cummins,Kirloskar,Ashokleyland
Descaling of water jacket of engine by using chemical descaling solution with pressure circulation pump,leak testing, soldering, brazing, checking for leaks and recirculating with clear water complete all as directed for DG set of capacity 165 KVA to 300 KVA Make\;-Mahindra,Cummins,Kirloskar,Ashokleyland complete and testing all as directed.
All as per item No:50 but DG Set of 50KVA to 100 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:50 but DG set of 30 KVA to 40 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:50 but DG set of 10 KVA to 15 KVA Make:--Mahindra,Cummins,Kirloskar,Ashokleyland
S & F in repairs Anti vibration pad suitable for 10KVA to100 KVA DG set all as directed .
S&F in replacement of Ignition Switch of DG Sets for DG sets of Make:-Mahindra,Cummins,Kirloskar,Ashokleyland complete and testing all as directed.
S&F in replacement of AVR suitable forDG set of capacity upto 160 KVA to 300 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland complete and testing all as directed.
All as per item No:56 but DG Set of 50KVA to 100 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:56 but DG set of 30 KVA to 40 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:56 but DG set of 10 KVA to 15 KVA Make:--Mahindra,Cummins,Kirloskar,Ashokleyland
Supply in repairs battery leads set, PVC insulated multisranded , copper conductor 35sqmm multistranded of 1.25 mtr long each duly fixed with brass clamps, copper lugs suitable for followling capacities of DG sets
M&L for replacement of existing street light with new generartion energy saving and enviromental friendly long life LED Street light made up innovative die cast aluminium housing high power LED as light source with IP-66 power consuption 120 Watt having minimum luminous 100/Watt complete input voltage of 150-240V (Nominal rated 240V)including multistranded twisted copper cable of 1.5 Sqmm dia for connecting street light to junction boxes through PVC coated copper connectors and the rate include taking down of existing unserviceable street light from poles etc complete all as specified and directed Make:Havells Cat part No:LHETASU7PA6J120 or equivalent Bajaj,CG.
Supply and fix in replacement Self starter, 12 Volts, suitable for fixing at 62.5/40/35/30/15 KVA DG Set fixed in repairs complete all as specified. Make: "LUCAS or equivalent as approved by GE"
Supply and fix in replacement Self starter, 24 Volts, suitable for fixing at 300/200/160 KVA DG Set fixed in repairs complete all as specified. Make: "LUCAS or equivalent as approved by GE"
Overhauling of water pump assembly complete including material and labour for impeller, shaft seal bearing, gaskets washers and rubber hose complete for DG set of 300/200/160KVA Make:- Cummins,Mahindra
All as per item No:64 but DG Set of 50KVA to 100 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:64 but DG set of 30 KVA to 40 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:64 but DG set of 10 KVA to 15 KVA Make:--Mahindra,Cummins,Kirloskar,Ashokleyland
S&F in replacement control wiring existing specifications and size of DG Set 160 to 300 KVA for DG sets of Make:-Mahindra,Cummins,Kirloskar,Ashokleyland complete and testing all as directed.
All as per item 68 above but for DG Set 50 to 100 KVA of Make:-Mahindra,Cummins,Kirloskar,Ashokleyland complete and testing all as directed.
All as per item 68 above but for DG Set 10 to 40 KVA of Make:-Mahindra,Cummins,Kirloskar,Ashokleyland complete and testing all as directed.
Disconnection and taking out the unservisable turbo charger assembly for DG set of 300/200/160KVA Make:- Cummins,Mahindraand taking to workshop, strip opening of turbo charger and replacement of repair kit reassembling and fixing back to engine and testing complete all as specified and directed.
All as per item No:71 but DG Set of 50KVA to 100 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:71 but DG set of 30 KVA to 40 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:71 but DG set of 10 KVA to 15 KVA Make:--Mahindra,Cummins,Kirloskar,Ashokleyland
Supply only Battery of capacity 12V 180 AH Make:- Exide/Amaron
Supply only Battery of capacity 12V 150 AH Make:- Exide/Amaron
Supply only Battery of capacity 12V 100 AH Make:- Exide/Amaron
M&L for repairing decarburizing, Engine ,cleaning ,washing manifolds exhaust system for DG set 0f 300/200/160KVA Make:- Cummins,Mahindra and connected items including replacement of necessary nuts bolts washers bolts washer etc with necessary masonry work reqd for above complete all as specified and directed
All as per item No:78 but DG Set of 50KVA to 100 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:78 but DG set of 30 KVA to 40 KVA Make:-Mahindra,Cummins,Kirloskar,Ashokleyland
All as per item No:78 but DG set of 10 KVA to 15 KVA Make:--Mahindra,Cummins,Kirloskar,Ashokleyland
S & F in replacement DG Set power controller for capacity up to 300/200/160KVA DG Set for DG sets of Make Mahindra,Cummins,Kirloskar,Ashokleyland complete and testing all as directed.
All as per item 82 above but power controller for 50KVA to 100 KVA DG Set .
All as per item 82 above but power controller for 30 KVA to 40 KVA DG Set .
All as per item 82 above but power controller for 10 KVA to 15 KVA DG Set .
Supply and fix in replacement Relay for AMF panel for capacity 30 KVA to 200 KVA DG sets of Make Mahindra,Cummins,Kirloskar,Ashokleyland complete and testing all as directed.
M & L for complete checking of AMF panel control panel on DG sets or seprate on site ,finding the fault,servicing complete including replacement of unserviceable spares and testing complete for manual & Auto operations all as directed. Note:- Supply only of new items required for replacement will be measured & paid seperately under respective item of schedule.
Supply & Fix in replacement 3 pole power Contactor ML-1.5,25 A,415 V of Make L&T or equvalent in ABB/Siemens/Crompton
Supply & Fix in replacement 3 pole power Contractor ML-2,32/40 A,415 V of Make L&T or equvalent in ABB/Siemens/Crompton
Supply & Fix in replacement 3 pole power Contractor ML-3,40/45 A,415 V of Make L&T or equvalent in ABB/Siemens/Crompton
Supply & Fix in replacement 3 pole power Contractor ML-4,70 A,415 V of Make L&T or equvalent in ABB/Siemens/Crompton
Supply & Fix 3 pole power Contractor ML-6,110/125 A,415 V of Make L&T or equvalent in ABB/Siemens/Crompton
Supply & Fix 3 pole power Contractor ML-10/ML12 ,200/250 A,415 V of Make L&T or equvalent in ABB/Siemens/Crompton
S & F in replacement Off Load Change over switch 4 pole 415 Volt 50 HZ ,side operated 320 Amp in SS enclosure with side handle Make Havells /INDO ASIAN/L&T
S & F in replacement Off Load Change over switch 4 pole 415 Volt 50 HZ ,side operated 200 Amp in SS enclosure with side handle MakeHavells /INDO ASIAN/L&T
S & F in replacement Off Load Change over switch 4 pole 415 Volt 50 HZ ,side operated 100 Amp in SS enclosure with side handle MakeHavells /INDO ASIAN/L&T
S & F in replacement MCCB's,415 Volts , 4 pole , fixed thermal & fixed magnetic settings, having 250 Amps 35 KA 4 Pole capacities
All as per item No:97 but capacity 200 Amps 35 KA 4 Pole
All as per item No:97 but capacity 160 Amps 35 KA 4 Pole
All as per item No:97 but capacity 125 Amps 25 KA 3 Pole
All as per item No:97 but capacity 63 Amps to 100 Amps 16 KA 3 Pole
S & F in replacement Automatic transfer switch, 4 pole 415 Volt 50 HZ , 200 Amp in SS enclosure with Automatic/manual with complete protection complete all as specified and directed Make Havells /INDO ASIAN/L&T
Supply only for toping up of pre mix Coolant for DG Set Make :MAK/Castrol/TVS/valvoline
M&L for complete servicing of central AC chiller plant, scroll type capacity 2 X 50 TR central AC plant of Make BLUE STAR Model No:XWC4S-052W (01 x 50 TR running and 01 x 50 TR standby) comprising of all the installed machineries and accessories with scroll compressors (04 x 12.5 TR in each unit), cooling towers , AHUs , water pumps, LT panels ,shell & tube type condensing unit and insulated chiller complete including checking of any leakage in system and repairing, checking of all controls , cleaning of cooling tower unit and greasing/ lubricating of moving parts, fan motors, checking of core filters etc complete all as specified and directed . All servicing and repairs works shall be carried out by authorised service centre /OEM of Blue star company . Note A : 1. The plant shall be visited twice during contract period by auth service technician /engineer of Bluestar company and will check all parameters /defects and leakage of plant and submit report to Engineer in charge. All necessary repairs/servicing will be done by auth service engineer of Blue star company. Cost visiting charges of engineer are deemed to be included in unit rate. 2. All spares /material required for repairs will be paid and measured separatly against relevent items of schedule hereunder Note B:- The unit rate includes the following works :- (i) Checking of gas leakage in complete system.Gas and gas charging shall be measured and paid separately. (ii) Carry out preventive maintenance as per the company recommendations and standard practice in every visit. Lubricating the bearings of motors & fans . (iii) Checking the refrigeration system, motor and starters and ensuring healthy condition of the plant. (iv) Taking set of readings and evaluating to ensure satisfactory performance of the plant.(v) Cleaning of the evaporator/condenser coils once a year and cleaning of chiller.(vii) complete checking of control wiring for the AC plant control panel and connected safety switches/ cut-outs / thermostats etc, removing and re-terminating the burnt wires, checking of all contactors/contacts for proper Manually functioning and rectifying the faults/ faulty components by replacing with new spares and setting the relays etc.(viii) Checking the Central chiller plant control system for operation and adjusting the settings. (ix) Checking of condenser unit and its accessories and take the reading of EWT and LWT in hot and cold side and set CR at prescribed value.(x) Checking the functioning of scroll compressor in every visit andrectify /repair defects. (xi) Checking of Evoprator unit(Chiller unit) and its accessories and take the reading of EWT and LWT in hot and cold side and set CR at prescribed value. (xii) Checking of compressor oil level and quality of oil and replacement / top up if required. (xiii) Checking of the central chiller plant control panel for its proper functioning and replacement of unserviceable accossaries connected to the control panel like fuse,microprocessor, display etc (xiv) Servicing /repairsworks will be carried out within 03 days after intimation to contractor on telephone followed by in writing. Any delay beyound 03 day shall be penalised through panel recovery @ 3000 per day till rectificatio/repair starts.
M&L for complete servicing of 3x5 TR floor-mounted vertical units Central AC Plant( 02 x 5 TR of Blue Star Make and 01 x 5 TR of Voltas Make ) comprising the installed machineries and accessories mainly sealed compressors (01 x 5 TR in each unit), compressors, cooling towers , AHUs , water pumps, LT panels ,shell & tube type condensing unit and insulated chiller complete including checking of any leakage in system and repairing, checking of all controls , cleaning of cooling tower unit and greasing/ lubricating of moving parts, fan motors, checking of core filters etc complete all as specified and directed . All servicing and repairs works shall be carried out by authorised service centre /OEM of Blue star and Voltas company . Note A : 1. The plant shall be visited twice during contract period by auth service technician /engineer of Blue star and Voltas company and will check all parameters /defects and leakage of plant and submit report to Engineer in charge. All necessary repairs/servicing will be done by auth service engineer of Blue star company. Cost visiting charges of engineer are deemed to be included in unit rate. 2. All spares /material required for repairs will be paid and measured separatly against relevent items of schedule hereunder Note B:- The unit rate includes the following works :- (i) Checking of gas leakage in complete system.Gas and gas charging shall be measured and paid separately. (ii) Carry out preventive maintenance as per the company recommendations and standard practice in every visit. Lubricating the bearings of motors & fans . (iii) Checking the refrigeration system, motor and starters and ensuring healthy condition of the plant. (iv) Taking set of readings and evaluating to ensure satisfactory performance of the plant. (v) Cleaning of the evaporator/condenser coils once a year (vii) Taking set of readings and evaluating to ensure satisfactory performance of the plant. (viii) Checking the packed type central AC plant control system for operation and adjusting the settings. (ix) Checking of condenser unit and its accessories and take the reading of hot and cold side . (x) Checking the functioning of hermitically sealed compressor in every visit and rectify /repair defects. (xi) Checking of Evoprator unit and its accessories (xii) Checking of compressor oil level and quality of oil and replacement / top up if required. (xiii) Checking of the central chiller plant control panel for its proper functioning and replacement of unserviceable accossaries connected to the control panel like fuse,microprocessor, display etc (xiv) Servicing /repairsworks will be carried out within 03 days after intimation to contractor on telephone followed by in writing. Any delay beyound 03 day shall be penalised through panel recovery @ 3000 per day till rectificatio/repair starts.
M&L for descaling of condensor unit of 1x50 TR capacity shell and tube type by removing end cover/pipe line to make access and descaling the condenser tubes manually by wire brushing the tubes, cleaning by flushing in De-scaling agent through the condensers by forced feed type method cleaning each tube of the condenser internally by brushing without damaging the tubes and re-fixing back the end covers with new rubber gasket, nuts, bolts and washers and pressure testing for 24 hours complete all as specified.
M&L for descaling of condensor unit of 1x5 TR capacity shell and tube type by removing end cover/pipe line to make access and descaling the condenser tubes manually by wire brushing the tubes, cleaning by flushing in De-scaling agent through the condensers by forced feed type method cleaning each tube of the condenser internally by brushing without damaging the tubes and re-fixing back the end covers with new rubber gasket, nuts, bolts and washers and pressure testing for 24 hours complete all as specified.
Cleaning of the evaporator unit of 50 TR capacity central air conditioning plant with cleaning agent by forced feed method to remove the unwanted dust formed over the cooling coil fins without disturbing the mounting of the coils and greasing to the AHU blower bearing and tightening of all fasteners etc complete all as specified and directed by Engineer-in-Charge. Note : The descaling and cleaning works neet to be carried out by authorised skilled person by the service dealer or from the Manufacturer.
Cleaning of the evaporator unit of 5 TR capacity central air conditioning plant with cleaning agent by forced feed method to remove the unwanted dust formed over the cooling coil fins without disturbing the mounting of the coils and greasing to the AHU blower bearing and tightening of all fasteners etc complete all as specified and directed by Engineer-in-Charge. Note : The descaling and cleaning works neet to be carried out by authorised skilled person by the service dealer or from the Manufacturer.
Disconnecting & dismantling of existing unserviceable cooling tower, FRP type, 50 TR capacity of any description & in any position including dismantling all old connected part/filters, like motor, FRP casing basin, PVC filling , MS/GI pipe line, sluice valve, stop valve, steel structure frame etc, servicing/overhauling, cleaning, oiling/greasing and fixing of serviceable parts in position removing & replacement of defective/unserviceable parts with new parts, reassembling the cooling towers and connected parts/items fixed in position for connecting to existing system and testing at site on full load to the entire satisfaction of the Engr-in-Charge. Note:- Spare parts required for repair will be paid and measured separately.
All as per item 110 above but for cooling tower of AC plant of capacity 5 TR
Supply & Fix PVC filling blocks of size approx 600mm x 300mm x 150mm suitable for cooling tower of 50 TR AC plant complete all as specified and as directed. Make : MIHR/AVIRAT/SUVIDHA
S&F in repairs PVC honey comb fillings for 5 ton AC plants cooling tower by taking down cooling tower at site & dismanteling carefully and keeping in safe custodyn for reuse complete all as specefied and directed by Engnr-in-charge.
Taking out the burnt electric motor of capacity 1.0 HP to 3 HP from existing position, transporting to civil work shop, separating the stator and rotor housing, cutting and removing the existing winding of stator completely, cleaning the slots and rewinding with existing gauge of super enamelled copper winding wire with suitable insulation, applying insulation varnish and heating in heating chamber till completely dried and reassembling the motor including supply and replacement of DE(01 No.) &NDE(01 No) bearings (make: NBC/SKF/TATA), transporting back to site and re-installing in its original position including proper alignment for smooth running and testing on completion complete all as specified and directed by Engineer-in-Charge.
All as per item no 114 but 5 HP to 7.5 HP motor
All as per item no 114 but 10 HP to 15 HP motor
M&L for taking out the defective pump set of capacity upto 3 to 5 HP of AC plant from existing position by carefully disconnecting all water pipe lines and electrical cables and carrying out overhauling by dismantling the pump casing, cleaning of the impeller and supply and replacement of Gunmetal bush(01 No), gland plate (01 No.) alongwith studs, nuts, gland packing rope, greasing and re-assembling and re-installing in its original position and testing on completion complete all as specified and directed by Engineer-in-Charge. Note:-spare parts other than mentioned above under this item will be measured and paid separately as supply only.
supply only end ball / roller bearing with good quality grease suitable for pump sets 3 HP to 5 HP Make:NBC/SKF/Tata
Supply only star coupling key any size as per sample complete all as specified and directed.
supply only pump shaft suitable for pump sets 3 HP to 5 HP capacity
Supply only pump impeller brass suitable for pump sets 3 HP to 5 HP capacity
Supply only gun metal bush bearing complete set of two as per sample for 3 HP to 5 HP pump
Supply and fix in repalcement of high grade iron pully having dia up to 60 cm and thickness up to 3 cm with V shape grooves suitable for B-77 belt and shaft hole up to dia 6 cm suitable for AHU blower motor complete by dismantling old pully from blower unit and fixing the same in original position complete all as specified and directed
Supply and fix in replacement of Blower Shaft having approx dia 6 cm suitable for 10/15HP AHU motor by dismantling old unserviceable shaft from AHU unit including transportation ,filling metal to deshaped portion of key groove,grinding ,polishing the key groove ,replacing lock key ,refixing in existing position in AHU unit, testing complete all as specified and directed
Supply and fix in repalcement of 6 mm thick nitrile rubber insulation on condensate drain pipe of size 50/40mm dia and fitting like valve,flanges, and union etc complete all as specified and directed Make: Accoflex,Armacell,K flex
Dismantling and taking down scrolled type sealed compressor 12.5 TR( Make : Denfoss model No:SZ18554RC,) from main unit and complete repair of compressor including changing of compressor oil to existing capacity ,solder sleeve,Rotolock valve,gasket ,angle adapter descaling the entire copper tube by using HCL or any other chemical specified as per manufacturer complete testing and refixing to original position all as specified and directed
S&F in replacement sealed compressor unit suitable for 5 ton package type AC plant, Model No. CR72KQM-TFM of Emerson Copeland or equivalent approved make suitable for working on 380-420 V 50 Hz 3 phase including necessary welding/bracing work to existing refrigerant pipes and including R-22 refrigerant gas of required and testing on load complete all as specefied and directed .
S&F in replacement sealed compressor unit suitable for 5 ton package type AC plant, Model No. KCG572HAE of Emerson Copeland or equivalent approved make suitable for working on 380-420 V 50 Hz 3 phase including necessary welding/bracing work to existing refrigerant pipes and including R-22 refrigerant gas of required and testing on load complete all as specefied and directed .
S&F in replacement cooling coil unit complete for AC plant 5 ton capacity including making connection with expansion valve & discharge of compressor (for reference only dimensions of cooling coil 70 x 46 x 12 cm approx 09 vertical coils & 03 Horizontal coils, dia of cooling coil 15 mm approx) including top up filling of refg. gas R 22 of required quantity including testing on full load complete all as specefied and directed by Engnr-in-charge. Note : Refg Gas for top up /filling will be measured & paid separatly under relevant items.
Supply and fix in replacement of filter drier danfoss model No:DCL165 suitable for 5TR AC plant complete all as specified and directed.
Supply and fix in replacement of filter drier danfoss model No:DCL305 suitable for 50 TR AC plant complete all as specified and directed.
Supply and fix in replacement of Bimetal overload relay suitable for 5 TR central AC plant complete all as specified and directed.
Supply and fix in replacement of Bimetal overload relay suitable for 50 TR central AC chiller plant complete all as specified and directed.
Supply and fixing in replacement of expansion valve Denfoss model No:TGEX or equivalent approved by GE for 12.5TR compressor complete removing of old expansion valve from company mechanics and refixing the new expansion valve and connection with own arrengement and making plant running condition complete all as specified and directed.
Supply and fixing in replacement of expansion valve of 5 TR plant complete removing of old expansion valve from company mechanics and refixing the new expansion valve and connection with own arrengement and making plant running condition complete all as specified and directed.
M&L for gas charging to compressor 5 ton capacity with R 22 gas to top up to specified quantity including flushing out old gas and oil including testing on full load & checking for leakage by filling nitrogen gas up to the pressure of 250 psi in the plant for 24 hours complete all as directed. Note:- (i) No extra payment will be given to contractor to top up the gas in case of leakage from plant. (ii) The refrigerant gas will be brought in cylinder and will be given to the department . Empty cylinder will be returned to the Contractor after consumption of refrigerant gas . Nothing extra will be admissible on this account .
M&L for gas charging to compressor 12.5 ton capacity with R 407C gas including flushing out old gas and oil including testing on full load & checking for leakage by filling nitrogen gas up to the pressure of 250 psi in the plant for 24 hours complete all as directed. Note:- (i) No extra payment will be given to contractor to top up the gas in case of leakage from plant. (ii) The refrigerant gas will be brought in cylinder and will be given to the department . Empty cylinder will be returned to the Contractor after consumption of refrigerant gas . Nothing extra will be admissible on this account .
S&F in repair complete wiring kit as per existing size for 5 ton capacity AC plant complete all as directed.
S&F in repair complete wiring kit as per existing size for 50 TR capacity AC plant complete all as directed.
S&F in repair high pressure / low pressure control switch complete all as directed Make : Emerson / Denfoss
S&F of aluminium rotery sprinkler 50 mm dia with branch/sprinkler pipe 4 Nos suitable for cooling tower unit complete all as specefied and directed .
S&F in replacement Gun metal gate valve 25 mm bore (class I) ISI marked with iron wheel head, screwed both ends for iron pipe including dismantling and taking up/ down all as specified and directed . Make : Sant /Zoloto/Leader
S&F in replacement Gun metal gate valve of 40 mm bore (class I) ISI marked with iron wheel head, screwed both ends for iron pipe including dismantling and taking up/ down all as specified and directed at site. Make : Sant /Zoloto/Leader
S&F in replacement Gun metal gate valve of 50 mm bore (class I) ISI marked with iron wheel head, screwed both ends for iron pipe including dismantling and taking up/ down all as specified and directed at site. Make : Sant /Zoloto/Leader
Taking up or down 25 mm dia steel tubing and connections including cleaning for refixing or removal to store complete all as specified and directed.
Taking up or down 40 mm dia steel tubing and connections including cleaning for refixing or removal to store complete all as specified and directed.
Taking up or down 50 mm dia steel tubing and connections including cleaning for refixing or removal to store complete all as specified and directed.
Supplying, fixing, jointing and testing 25 mm dia galvanised steel tubing medium grade ( ISI Marked ) with all fittings such as bends, elbow, socket, reducer etc, laid under floor / trenches complete all as specified and directed. Make : Prakash/Tata/Jindal/Zenith
Supplying, fixing, jointing and testing 40 mm dia galvanised steel tubing medium grade ( ISI Marked ) with all fittings such as bends, elbow, socket, reducer etc, laid under floor / trenches complete all as specified and directed. Make : Prakash/Tata/Jindal/Zenith
Supplying, fixing, jointing and testing 50 mm dia galvanised steel tubing medium grade ( ISI Marked ) with all fittings such as bends, elbow, socket, reducer etc, laid under floor / trenches complete all as specified and directed. Make : Prakash/Tata/Jindal/Zenith
S&F in replacement Butterfly valve PN class 1.6 flanged type heavy duty of size 100 mm bore ( ISI Mrked ) including necessary accessories to fix the same in existing hot as well as in chilled water line complete all as specified and directed. Make : Audco/Advance/Castle
S&F in replacement Butterfly valve PN class 1.6 flanged type heavy duty of size 150 mm bore ( ISI Mrked ) including necessary accessories to fix the same in existing hot as well as in chilled water line complete all as specified and directed. Make : Audco/Advance/Castle
S &F in replacement of PCB card for 50 TR Central AC Plant BLUE STAR Model No:XWC4S-052W as per existing size and capactiy installed by othorised company mechanics/dealer and install all the programe and making plant in running condition complete all as specified and directed.
S &F in replacement Power contactor 3 pole 32/30 Amps with no volt coil and all accessories for fixing the same in exisitng starter all as specified and directed. Make : L&T Type MNX 32 or equivalent in Schneider/GE/Siemens./ABB
S & F in replacement Power contactor 3 pole 25 Amps with no volt coil and all accessories for fixing the same in exisitng starter. Make : L&T/Siemen/C&S./ABB
S&F in repair thermal overload relay range28 - 36 Amps complete all as directed Make : Seimens / L&T/ABB
S&F in repair thermal overload relay range17 - 25.5 Amps complete all as directed Make : Seimens / L&T/ABB
S&F single phasing preventor suitable for AC plant complete all as directed Make : Minilec / L&T / Seimens
S & F in replacement MCCB 4 pole 415 volts Ics=100%Icu, 35 KA of capacity 200 Amps with adjustable thermal setting all as specified and directed. Make : L&T/Schneider/GE/Legrand/Havells
S & F in replacement MCCB 3 pole 415 volts Ics=100%Icu, 25 KA of capacity 100 Amps with adjustable thermal setting all as specified and directed. Make : L&T/Schneider/GE/Legrand/Havells
S & F in replacement Off Load Change over switch 4 pole 415 Volt 50 HZ ,side operated 200 Amp in SS enclosure with side handle Make Havells /SSK/HPL/INDO ASIAN
S & F in replacement Off Load Change over switch 4 pole 415 Volt 50 HZ ,side operated 315 Amp in SS enclosure with side handle Make Havells /SSK/HPL/INDO ASIAN
S &F in replacement of automatic RYB phase sequence corrector in sheet metal enclosure having current rating 400 Ams complete all as specified and directed. Make:Techno power model No:400a APSC or equivalent in L&T/Siemens/ABB
S &F in replacement of automatic RYB phase sequence corrector in sheet metal enclosure having current rating 200 Ams complete all as specified and directed. Make:Techno power model No:200a APSC or equivalent in L&T/Siemens/ABB
M&L for Opening of AHU Coil, Supply duct & return duct, diffusers, grills, fire damper and any other installed component that part of Central AC plant at Cav Auditorium and signal center . All above part should be cleaned with following procedures and equipments:-(a) Rotary brushes system self-propelled type with different types of brushes and used to agitated and loosen dirt with duct. (b) Wiper set used again to loosen dirt depending upon the type & size of duct. (c) Contact vacuuming menthod of HVAC system cleaning which incorporates agitation and vcuum collection principle into one operation. (d) Compressed air washing mechanical means to agitate and dislodge particulate form the interior surface of HVAC system. (e) All of the grill and differs are removed and clean (f) Starting for farthest vent opening each branch line is cleaned using nylon duct brushes, cable driven brushes, or forwarded air blast assemblies to loosen debris. The agitation tool causes debris to the quickly caught up in the air movement from the HYPE M/c The process is then repeated at each vent opening . Once all the branch line have been cleaned , the main pocket filter is cleaned. (g) After the dust and debris is removed from the system, an light fogged through the air duct system, This product immediately kills fungus or bacteria. The blower motor is inspected and cleaned if necessay and accessible. (m) The insulation in the air handler unit case is manually cleaned and then treated with fogger m/c to kill an residual mold, fungus, or bacteria. The blower motor is inspected and cleaned if necessary and acessible. (n) Coil cleaning with the COIL CLEANER (o)Testing the duct after cleaing all part of the system of air ducts.
Dismantling and taking down of existing micro filters of size 5 to 10 micron from AHU duct plannum for checking the serviceablility of flter element, servicing and cleaning of filter elements, replacement of existing unserviceable filters and fixing serviceable filters in position, including preparation of the surfaces of MS cover of filters and applying one coat of synthetic enamel paint of approved colour complete all as specified and as directed.
S& F in replacement Pressure guage 0-10 Kg/cm2, round dial type including brass nipple, test cock and other minor accessories to fix the same in AC plant/AHUs all as specified and directed. Make : H. Guru/ Fiebig/ Dwyer.
S &F in replacement Temperature guage 0-50ºC, rectangular type with transparent glass to see the reading including brass nipple and other minor accessories to fix the same in AC plant/AHUs all as specified and directed. Make : Taylor/ H. Guru/ DS Engg or any equivalent ISI marked.
S &F in replacement VFD of AHU/ AC plant unit for existing motor capacity. Make: Danfoss or as approved by GE
S &F in replacement fully automatic star-delta starter for central AC plant capacity from exceeding 10 to 15 HP etc complete incl taking out old unserviceable all as specified and directed . Make L&T/Havells/C&S
S&F in replacement PVC Insulated, unsheathed multi stranded copper conductor cable, heavy duty, 1100 Volts grade single core of RYB colour 16 Sqmm in replacement for connection from LT panel board to motor starters and from starters to electric motors including necessry cable end termination with copper lugs of suitable size all as directed, confirmong to IS:694drawn through concealled heavy grade PVC conduites of not less than 32 mm nominal dia with necessary fittings such as bends, sockets etc. laid under the floor or fixed to the walls with suitable clamps or saddles including taking down of existing cable all as specified and directed
S&F in replacement of fins and strip type heating element industrial type suitable for AHU unit of AC plant of capacity 4/6KW or higher capacity available by dismantling old unserviceable heater including refixing at existing place,testing complete all as specified and directed.
Supply and fix in replacement flow meter having max pressure 10 bar ,liquid temp 1 to 100ºC,synergy HFS-25 complete all as specified and directed
M & L for earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6 mm thick burried directly in ground vertically to a depth not less than 3.0 mtr deep below GL with top edge of the plate not less than 2.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt upto 1.5 meter depth all around the earth plate and connected to earth lead of GI wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvd iron or steel and thimbles and other end of the earth wire connected to DB and protected by galvanized iron or steel pipe light grade 15 mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh, including required excavation for making the pit perfect to size and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 3 of MES schedule Pt I of 2009 and also including making test point for testing of earthing complete . Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover. 2. Charcoal dust and common salt upto 1.5 meter depth shall be filled in layers of 15 centimeters all around the earth plate inside earth pit . On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values
M & L for earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6 mm thick burried directly in ground vertically to a depth not less than 3.0 mtr deep below GL with top edge of the plate not less than 2.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt upto 1.5 meter depth all around the earth plate and connected to earth lead of GI strip 25x4 mm by means of bolts, nuts, check nuts and washers of galvd iron or steel and thimbles and other end of the earth wire connected to DB and protected by galvanized iron or steel pipe light grade 15 mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh, including required excavation for making the pit perfect to size and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 3 of MES schedule Pt I of 2009 and also including making test point for testing of earthing complete . Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover. 2. Charcoal dust and common salt upto 1.5 meter depth shall be filled in layers of 15 centimeters all around the earth plate inside earth pit . On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values
M & L for earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6 mm thick burried directly in ground vertically to a depth not less than 3.0 mtr deep below GL with top edge of the plate not less than 2.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt upto 1.5 meter depth all around the earth plate and connected to earth lead of GI strip 32x6 mm by means of bolts, nuts, check nuts and washers of galvd iron or steel and thimbles and other end of the earth wire connected to DB and protected by galvanized iron or steel pipe light grade 15 mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh, including required excavation for making the pit perfect to size and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 3 of MES schedule Pt I of 2009 and also including making test point for testing of earthing complete . Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover. 2. Charcoal dust and common salt upto 1.5 meter depth shall be filled in layers of 15 centimeters all around the earth plate inside earth pit . On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values.
M & L for earthing complete with copper earth plate electrode 60cm x 60cm x 3.15 mm thick burried directly in ground vertically to a depth not less than 3.0 mtr deep below GL with top edge of the plate not less than 2.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt upto 1.5 meter depth all around the earth plate and connected to copper earth strip of size 20 mm x 3mm thick by means of bolts, nuts, check nuts and washers of galvanised iron or steel and thimbles and other end of the earth wire connected to DB and protected by galvanized iron or steel pipe light grade 15 mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh, including required excavation for making the pit perfect to size and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 3 of MES schedule Pt I of 2009 and also including making test point for testing of earthing complete . Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover. 2. Charcoal dust and common salt upto 1.5 meter depth shall be filled in layers of 15 centimeters all around the earth plate inside earth pit . On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values
S & F in replacement electrical insulating mats conforming toIS 15652/2006 for 11 KV grade system 1mtr x 2mtr sheet thickness 3mm one side plain other side chequred/patterened moisture proof, fire retardant complete all as specified and directed .
S&F in repair thermostat as per existing size complete all as directed Make : Emerson / Denfoss
S & F in replacement of superior quality V belt(B-77) suitable for blower motors of AHU unit. Make; Fenner/ Dunlop
S &F in replacement of ACE AM 4201 ACE Digital Anemometer along with calibration certificate which measure air velocity in M/s,km/hr,ft/min,knots having measurment range of 0.4-30M/s complete all as specified and directed.
Supply and filling compressor oil Freezol 68 or equivalent as approved by GE for topping up all as specified Make: HP/Bharat Petrolium / Indian Oil
S&F in replacement of mild steel foundation channel support assembly made out of MS channel size 4X10cm having thickness of 4 mm suitable for monoblock pump moter set of capacity 3 HP to 5 HP coupled with suction/delivery pipes of size 150mm/100mm/80mm/50mm/40mm with necessary bolts complete all as specified and directed Note:Provision of connection withn existing suction/delivery pipe including proper alignment necessary bushing,tapers,reducesers,MS flange ,welding work,etc as required at site for commissioning of pump sets in deemed to be included in the quoted rates.
M&L for rectification of leakage and flushing nitrogen gas in the system and kept for a period of 24 Hr with sufficient pressure for 50TR AC plant complete all as specified and directed
All as per item No 190 but for 5 TR
Excavation in trenches in any type of soil not exe 1.5 mtrs wide and not exe 1.5 mtr in depth for laying of pipe/cables etc and getting out incl forming bottom surface to the required level/slope etc complete all as specified and directed .
Returning, filling in, approved earth including spreading, levelling, watering and well ramming in layers n.exc 25 Cm thick after cable are laid and tested complete all as specified and directed.
Removing excavated material / surplus soil to a distance not exc. 50 mtrs & deposited where directed at a level not exc.1.5 mtr above the ground level complete all as specified & directed.
Taking out of unservaiceable lightening conductor complete of any type any description and of any size and as directed .
S &F in replacement single pointed air termination aluminium rod 12mm dia and 300 mm long for lightening conductor and fix to aluminium by making holes with nuts, bolts & washers as directed by Engineer-in-Charge.
S &F in replacement single pointed air termination copper rod 12mm dia and 300 mm long for lightening conductor and fix to copper strips by making holes with nuts, bolts & washers as directed by Engineer-in-Charge.
M&L for Test point terminal block made of gun metal or phosphorus bronze size 75 x75 x10 mm drilled and screwed including 3 nos. 8mm dia 25mm long hexagonal head screw etc complete and as directed.
MAterial and labour for re fixing of old GI / Aluminium strips with saddles and fixing screws for roof conductors and down conductors above level etc including M & L for PCC work in 1:2 :4 type B-1 using 20 mm graded stone aggregates complete all as specified and directed. Note : Cost of refixing strip of one earthing will be considered as one Job .
S &F in replacement GI strip of size 32 mm x6 mm with saddles and fixing screws etc on roof conductors and down conductors etc complete all as specified and directed
S &F in replacement aluminium strip of size 25 mm x3.15 mm with saddles and fixing screws etc on roof conductors and down conductors etc complete all as specified and directed
S &F in replacement copper strip 20 mm x3.15 mm with saddles and fixing screws etc on roof conductors and down conductors etc complete all as specified and directed
S & F galvanised mild steel water tubing of 40 mm dia bore in light grade with ISI Mark and incl all fittings like bends, elbow, Tee, reducer sockets & union etc laid in trenches, under floor or fixed to walls / ceilings complete all as specified and as directed. Make : Prakash Surya / Tata /Jindal
S & F galvanised mild steel water tubing of 50 mm dia bore in light grade with ISI Mark and incl all fittings like bends, elbow, Tee, reducer sockets & union etc laid in trenches, under floor or fixed to walls / ceilings complete all as specified and as directed. Make : Prakash Surya / Tata /Jindal
Taking out old unserviceable earthing materails incl earth plates of any type /size , nut ,bolt,washers incl GI wire/strips & GI pipe of any dia including necessary excavation etc complete as directed
Demolition of PCC ( Un reinfored) in ground floor and pavings n exc 15 cm thick below or above ground level complete and as directed
M&L for PCC 1:2:4 type B-2 (using 40mm graded stone aggregates) as in foundation /mass concrete etc all as specified and directed .
M&L for 100 mm thick PCC(1:3:6) type C1 (using 20mm graded crushed stone agregate) as in floors/Pavings /hard standing laid in alternate panels of size n exc 12 sqm each ,panels made of 10 mm thick plywood and joints filled up with sealing compound grade 'A' complete , surface of concrete finished even & fair complete all as specified. Note : Cost of forming joints and filling joints with sealing compound grade 'A ' deemed to be included in the unit rate quoted by the tenderer.
m/s gupta trading
M/S Ritu Tandon
M/S DEVINDER ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .