HEADQUARTERS COMMANDER WORKS ENGINEERS GEN CARIAPPA MARG, PUNE-411 001
81694REPAIR / MAINT OF TRANSFORMER, SWITCHGEARS AND ITS CONNECTED WORKS AT NDA KHADAKWASLA
2021_MES_442044_1
81694(R)/Transformer Khadakwasla
Open Tender
Electrical and Maintenance Works
Item Rate
273 days
NDA Khadakwasla
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE NDA Khadakwasla
₹52,280
Yes
30 Jul 2021
12 May 2021
11 Jun 2021
12 May 2021
9 Jun 2021
27 May 2021
Amount
Preventive Maintenance and Servicing of 22/11 KV Power Transformer outdoor type by disconnecting carefully electric connection on primary & secondary side, Checking both side HT bushing, bushing rod, opening top cover of the transformer by unscrewing nuts, bolts, washers etc, rectify the oil leakages issues, if noticed any, during servicing and re-fixing the top cover of transformer according to previous system. Servicing of the transformer must be done through OEM or authorised personnel including maintaining and submitting the inspection and testing records of each transformer to the Engr-in-Charge. Note 1. :- Inspection of transformer shall involve :- (a) Checking of all clamps, nuts, bolts including core bolts & cover fixing bolts etc. (b) Checking all brazings, joints, tap heads, gaskets and connection joints. (c) Checking all terminations / connections inside/ouside the transformer. (d) Checking of off load tap changer assembly, checking the moving and fixed contacts for contact wear and connection to winding. (e) Conducting the test on core and windings as per IS like ratio, magnetic imbalance, short circuit, IR Value, High Voltage Test etc. in presence of Engr-in-Charge. Note 2. : Spares used e.g. rewinding of primary & secondary coils, Iron Core, bushes studs HT/LT, bushing rod HT/LT, transformer oil, filteration of oil, buchholtz relay, Gaskets set, Off Load Change over switch etc will be measured and paid separately under respective item of BOQ. Note 3 :- The rates quoted against the item is deemed to be included for cost of Labour for lifting/transporting to civil workshop and vice-versa, if required as per site requirement.
1000 KVA, Make : Bleco Lawries Ltd
2000 KVA, Make : Kirloskar
All as per item No. 1 herein before (including Notes) but 11/0.433 KV, Distribution Transformer, Outdoor/Indoor type of capacity 500 to 750 KVA. Make of Transformer : Kirloskar/Rajstan Transformer/Pactil/Mahati/Urja/CG/Voltamp Note 1. : For this job cost includes transportation of trolly mounted 500 to 750 KVA transformer from MES store yard to work site/Sub Stn, disconnecting previous transformer HT /LT Cables and installation with its HT/LT connection upto Panel. Transformer will be provided by the department. Note 2. :- The rates quoted against the item is deemed to be included for cost of Labour for lifting/transporting to civil workshop and vice-versa, if required as per site requirement.
All as per item No. 1 herein before (including Notes) but 11/0.433 KV, Distribution Transformer, Outdoor/Indoor type of capacity 200 to 400 KVA. Make of Transformer : Kirloskar/Rajstan Transformer/Pactil/Mahati/Urja/CG/Voltamp Note 1. : For this job cost includes transportation of trolly mounted 200 to 400 KVA transformer from MES store yard to work site/Sub Stn, disconnecting previous transformer HT /LT Cables and installation with its HT/LT connection upto Panel. Transformer will be provided by the department. Note 2. :- The rates quoted against the item is deemed to be included for cost of Labour for lifting/transporting to civil workshop and vice-versa, if required as per site requirement.
All as per item No. 1 herein before (including Notes) but 11/0.433 KV, Distribution Transformer, Outdoor/Indoor type of capacity 50 to 160 KVA. Make of Transformer : Kirloskar/Rajstan Transformer/Pactil/Mahati/Urja/CG/Voltamp Note 1. : For this job cost includes transportation of trolly mounted 50 to 160 KVA transformer from MES store yard to work site/Sub Stn, disconnecting previous transformer HT /LT Cables and installation with its HT/LT connection upto Panel. Transformer will be provided by the department. Note 2. :- The rates quoted against the item is deemed to be included for cost of Labour for lifting/transporting to civil workshop and vice-versa, if required as per site requirement.
Supply and topping up of transformer oil with di-electric strength not less than 50 KV in to the conservator tank / body tank of the transformer at various Sub Stations inside NDA Campus including maintaining and submitting the test results to Engr-in-charge. Make : Poweroil / Transol/ Sabitha Chemicals. Note : (i) New Transformer oil will be filled in the transformer only after filteration and de-hydration of existing transformer oil of the transformer. (ii) Transformer oil shall be supplied in sealed container /barrel with test result and test certificate etc.
Supply only Super enamelled Copper winding wire as per existing gauge and specifications required for repair and re-winding of Power/Distribution transformers HT/LT Coil with insulation including necessary class of insulation, including testing and commissioning the transformer and recording the test results as per IS complete all as directed.
Supply only Super enamelled Iron Core as per existing gauge and specifications required for repair and re-winding of Power/Distribution transformers HT/LT Coil with insulation including necessary class of insulation, including testing and commissioning the transformer and recording the test results as per IS complete all as directed.
Supply only Gasket set suitable for top cover of 22/11 KV Power transformers of the following capacity and make including dismentling old one :-
1000 KVA, Make : Bleco Lawries Ltd
2000 KVA, Make : Kirloskar
Supply only Gasket set suitable for top cover of 11/0.433 KV Distribution transformers of the following capacity including dismentling old one :- Make of Transformer : Kirloskar/Rajstan Transformer/Pactil/Mahati/Urja/CG/Voltamp
50 to 160 KVA
200 to 400 KVA
500 to 750 KVA
Supply only HT porcelain bushing suitable for 22/11 KV Power Transformers of following capacity and Make including dismantling old one :-
1000 KVA, Make : Bleco Lawries Ltd
2000 KVA, Make : Kirloskar
Supply only HT porcelain bushing suitable for 11/0.433 KV Distribution Transformers of following capacity including dismantling old one :- Make of Transformer : Kirloskar/Rajstan Transformer/Pactil/Mahati/Urja/CG/Voltamp
50 to 160 KVA
200 to 400 KVA
500 to 750 KVA
Supply only LT porcelain bushing suitable for 11/0.433 KV Distribution Transformers of following capacity including dismantling old one :- Make of Transformer : Kirloskar/Rajstan Transformer/Pactil/Mahati/Urja/CG/Voltamp
50 to 160 KVA
200 to 400 KVA
500 to 750 KVA
Supply of HT bushing rod made out of gun metal with threading & of suitable length/ size all as per existing including metal rings/ bolts/ washers/ rubber rings etc, suitable for 22/11 KV Power Transformers of following capacity and make including dismentaling old one :-
1000 KVA, Make : Bleco Lawries Ltd
2000 KVA, Make : Kirloskar
Supply only HT bushing rod made out of gun metal with threading & of suitable length/ size all as per existing including metal rings/ bolts/ washers/ rubber rings etc, suitable for 11/0.433 KV Distribution transformers of following capacity including dismentaling old one :- Make of Transformer : Kirloskar/Rajstan Transformer/Pactil/Mahati/Urja/CG/Voltamp
50 to 160 KVA
200 to 400 KVA
500 to 750 KVA
Supply only LT bushing rod made out of gun matel with threading, suitable length / size all as per existing including metal rings/ bolts/ washers/ rubber rings etc, suitable for 11/0.433 KV Distribution Transformer of following capacity including dismentling old one :- Make of Transformer : Kirloskar/Rajstan Transformer/Pactil/Mahati/Urja/CG/Voltamp
50 to 160 KVA
200 to 400 KVA
500 to 750 KVA
Supply only in replacement of hand operated off load tap changing gear assembly suitable for 11/0.433 KV distribution transformer outdoor/ indoor type of following capacity/make including testing after re-installation and taking down existing old one complete all as directed. Make of Transformer : Kirloskar/Rajstan Transformer/Pactil/Mahati/Urja/CG/Voltamp
50 to 160 KVA
200 to 400 KVA
500 to 750 KVA
Supply only Oil Temperature Indicator (OTI), suitable/compatible to 11/0.433 KV Distribution Transformers outdoor/indoor type of following capacity/make including dismentling old one :- Make of Transformer : Kirloskar/Rajstan Transformer/Pactil/Mahati/Urja/CG/Voltamp
50 to 160 KVA
200 to 400 KVA
500 to 750 KVA
Labour and Plant/Machinery for online dehydration of Transformer Oil of Transformer /OCB at various Sub Stations inside NDA Campus. Desired di-electric strength of transformer oil must not be less than 50 KV including maintaining and submitting the test results of each transformer before and after the dehydration of transformer oil to Engr-in-Charge.
M & L for collecting the sample of Transformer Oil from 22/11 KV Power Transformer of 1000 /2000 KVA capacity and Make : Bleco Lawries Ltd/Kirloskar from MRS, inside NDA Campus and carrying out the Acidity Test according to relevant IS Standard through Approved/Authorised Laboratory and submitting test result to the Engr-inCharge.
M & L for collecting the sample of Transformer Oil from 11/0.433 KV Distribution Transformer of 50/63/100/125/150/160/200/250/315/400/500/750 KVA capacity and Make of Transformer : Kirloskar/Rajstan Transformer/Pactil/Mahati/Urja/CG/Voltamp, from various Sub Stns, inside NDA Campus and carrying out the Acidity Test according to IS Standard by Approved/ Authorised Laboratory and submit test result to the Engr-inCharge.
M & L for construction of transformer plinth, size 2.0 m x 2.0 m x 1.6 m for transformer by using 100 mm thick PCC 1:4:8 type D-2 as in lean concrete, flyash brick masonary in CM 1:6, the top of the plinth shall consist of 100 mm thick PCC 1:2:4 type B-1 (using 20 mm graded stone aggregates) over 75 mm thick PCC 1:4:8 type D-2 over compacted moorum filling, 10 mm thick rendering in CM 1:4 on brick surface with and including 25 cm thick stone aggregates of size 12.5 mm all around upto and including 1.5 m from the adge of the plinth complete all as specified, including taking down existing transformer from Two Pole Structure by dis-connecting its HT/LT connection, nut, bolts, clamps etc and re-installed the same transformer at newly constructed transformer plinth with the help of suitable size/capacity of Crane including re-connecting its HT/LT Cable & Earthing Strip connection etc complete all as specified and directed at site by Engr-in-Charge. Note : During this job, if any damages occurred to the transformer, Contractor shall be fully responsible to make good without any extra cost to the Department.
M & L for MS 'C' Channel, MS Work, Angle Iron, Hand rails, half round or other steel work, drilling, bolting, cutting and welding etc conforming to Fe-290 Gde E-165 including fixing and clamped on Two or Four Pole structure with suitable size of nut, bolts and washers etc complete all as specified and directed.
M & L for preparation of existing surface of transformer by scrapping down peeled off old paint, cleaning etc and applying one coat of smoke gray paint by spray to the following capacity of transformer complete all as directed by Engr-in-Charge.
50 to 160 KVA
200 to 400 KVA
500 to 750 KVA
1000 to 2000 KVA
S & F in replacement of Silica gel breather assembly suitable/compatible to 22/11 KV Power transformers of the following capacity and make including taking down old one :- Note : Rate quoted shall be deemed to include the cost of modification if any, required to fix on Transformer.
1000 KVA, Make : Mahati
2000 KVA, Make : Kirloskar
S & F in replacement of Silica gel breather assembly suitable/compatible to 11/0.433 KV Distribution transformers of the following capacity including taking down old one :- Make of Transformer : Kirloskar/Rajstan Transformer/Pactil/Mahati/Urja/CG/Voltamp Note : Rate quoted shall be deemed to include the cost of modification if any, required to fix on Transformer.
50 to 160 KVA
200 to 400 KVA
500 to 750 KVA
Preventive maintenance and servicing of 22 KV HT VCB, MDO Type, Rated Current 630A, 50 Hz by taking out the breaker trolley of 22 KV HT VCB, cleaning from inside and outside by using CRC-26 spray and applying petrolium jelly to the all moveable parts, Male female bushing/ terminals of VCB. Complete servicing of switchgear including checking the fixed / moving contacts of all the 3 phases adjusting electrical/ electronic/mechanical components all as per mfg instruction manual and standard practice including testing, charging/re-filling of SF6 gas and rectifying the gas leakage issues and calibration of relay of any make (e.g. Earth Fault relay / Over current relay/ Master Trip relay etc) of 22 KV VCB Panel. The fault level setting of these relays shall be as per the MSEB Norms so that individual breaker will activate / trip to arrest the fault in local circuit and fault will not travel to main breakers at MRS and subsequently to MSEB Power Feeder. This Job must be carried out carried out through OEM or authorised personnel including maintaining and submit the testing report to the entire satisfaction of Engr-in-Charge. Make of VCB : ABB Note :- Spares and SF6 gas used during servicing will be measured and paid separately under respective item of BOQ.
Supply only in replacement including testing and commissioning of spring charging motor, 220 VDC, suitable/compatible to existing 22 KV VCB Panel, VCB Breaker Model VD4/W24.12.32 type including dismantling of existing one complete all as specified and directed. Make of VCB : ABB as OEM.
Supply only in replacement including testing and commissioning of Coil Closed & Tripped Coil, 110 Volts, suitable/compatible to existing 22 KV VCB Panel, VCB Breaker Model : VD4/W24.12.32 type including dismentaling of existing one complete all as directed. Make of VCB: ABB as OEM.
Supply only in replacement of TNC switch, 220 VDC, suitable/compatible for operation of existing 22 KV VCB Breaker, Model VD4/W24.12.32 type Breaker including dismantling of existing one complete all as directed. Make : ABB as OEM.
Supply only Master Trip Relay, Cat Part /Model No. 1MYN563613-DAC, suitable/compatible to existing 22 KV VCB Panel, VCB Breaker Model : VD4/W24.12.32 type including all complete control wiring and dismentaling of existing one complete all as directed. Make : ABB or its equivalent make.
Supply only Master Trip Relay, Cat Part /Model No. VAJH13YF0751BBA, suitable/compatible to existing 22 KV VCB Panel, VCB Breaker Model : VD4/W24.12.32 type including all complete control wiring and dismentaling of existing one complete all as directed.
Supply only in replacement including testing and commissioning of instantaneous O/C & E/F protection relay 30V DC supply, numerical 4 Pole, 3 O/C & E/F non directional protection relay, model ADR241A including relay testing by injecting fault current and calibration, taking down existing one complete all as directed.
Preventive maintenance and servicing of 22 KV HT VCB, MDO Type, Rated Current 630A, 50 Hz by taking out the breaker trolley of 22 KV HT Panel, A2463G type, cleaning from inside and outside by using CRC-26 spray and applying petrolium jelly to the all moveable parts, Male female bushing/ terminals of VCB. Complete servicing of switchgear including checking the fixed / moving contacts of all the 3 phases adjusting electrical/ electronic/mechanical components all as per mfg instruction manual and standard practice including testing, charging of SF6 gas and rectifying the gas leakage issues and calibration of relay of any make (e.g. Earth Fault relay / Over current relay/ Master Trip relay etc) of 22 KV VCB Panel. The fault level setting of these relays shall be as per the MSEB Norms so that individual breaker will activate / trip to arrest the fault in local circuit and fault will not travel to main breakers at MRS and subsequently to MSEB Power Feeder. This Job must be carried out through OEM or authorised personnel including maintaining and submit the testing report to the entire satisfaction of Engr-in-Charge. Make of VCB : Kirloskar Note :- Spares and SF6 gas used during servicing will be measured and paid separately under respective item of BOQ.
Supply only in replacement including testing and commissioning of spring charging motor, 220 VDC, suitable/compatible to existing 22 KV VCB Panel, A2463G type including dismantling of existing one complete all as specified and directed. Make of VCB : Kirloskar as OEM.
Supply only in replacement including testing and commissioning of Coil Closed & Tripped Coil, 110 Volts, suitable/compatible to existing 22 KV Panel, A2463G type including dismentaling of existing one complete all as directed. Make of VCB: Kirloskar as OEM.
Supply only in replacement of TNC switch, 220 VDC, suitable/compatible for operation of existing 22 KV Panel, A2463G type including dismantling of existing one complete all as directed. Make of VCB : Kirloskar as OEM.
Supply only in replacement including testing and commissioning of Master trip relay, model AVAJH13-AM-011-03-01-05-00-00-00 suitable/compatible to existing 22 KV Panel, A2463G type including, cutting, welding to CRCA sheet without disturbing to other fitments and testing the relay by injecting fault current and calibration, taking down existing one complete all as directed.
Supply only in replacement 22 KV HT Cable terminal Protector right angle boot to prevent flashover/short circuit due to intervention by reptiles/insects etc, suitable / compatible to existing 22 KV HT Panel, A2463G type including taking down existing one complete all as directed. Make : 3M/ Mseal/Raychen/Denson
Preventive maintenance and servicing of 11 KV HT VCB, MDO Type, Rated Current 630/400A, 50 Hz by taking out the breaker trolley of 11 KV HT VCB, Model : Vind 12.12.25, cleaning from inside and outside by using CRC-26 spray and applying petrolium jelly to the all moveable parts, Male /female bushing/ terminals/ Spouts of VCB. Complete servicing of switchgear including checking the fixed / moving contacts of all the 3 phases adjusting electrical/ electronic/mechanical components all as per mfg instruction manual and standard practice including testing, charging of SF6 gas and rectifying the gas leakage issues and calibration of relay of any make (e.g. Earth Fault relay / Over current relay/ Master Trip relay etc) of 11 KV VCB Panel. The fault level setting of these relays shall be as per the MSEB Norms so that individual breaker will activate / trip to arrest the fault in local circuit and fault will not travel to main breakers at MRS and subsequently to MSEB Power Feeder. This Job must be carried out through OEM or authorised personnel including maintaining and submit the testing report to the entire satisfaction of Engr-in-Charge. Make of VCB : ABB as OEM Note :- Spares and SF6 gas used during servicing will be measured and paid separately under respective item of BOQ.
Supply only in replacement including testing and commissioning of spring charging motor, 110 VDC suitable /compatible for 11 KV VCB Breaker, VCB Breaker Model : Vind 12.12.25 including dismantling of existing one complete all as specified and directed. Make of VCB : ABB as OEM.
Supply only in replacement including testing and commissioning of Coil Closed & Tripped Coil, 110 Volts, suitable/compatible to existing 11 KV VCB Panel, VCB Breaker Model : Vind 12.12.25 type including dismentaling of existing one complete all as directed. Make of VCB : ABB as OEM.
Supply only Vaccum Interrupter Bottle/Chamber/Pole with complete assembly, Cat Part No./Model No. 2REA019936A000, suitable/ compatible to existing 11 KV VCB Panel, Current rating 1250 Amps, VCB Breaker Model : Vind 12.12.25 type including dismentaling of existing one complete all as directed. Make of VCB : ABB as OEM.
Preventive maintenance and servicing of 11 KV HT VCB, MDO Type, Rated Current 630A, 50 Hz by taking out the breaker trolley of 11 KV HT VCB, cleaning from inside and outside by using CRC-26 spray and applying petrolium jelly to the all moveable parts, Male /female bushing/ terminals/ Spouts of VCB Panel, A12 62D type. Complete servicing of switchgear including checking the fixed / moving contacts of all the 3 phases adjusting electrical/ electronic/mechanical components all as per mfg instruction manual and standard practice including testing, charging of SF6 gas and rectifying the gas leakage issues and calibration of relay of any make (e.g. Earth Fault relay / Over current relay/ Master Trip relay etc) of 11 KV VCB Panel. The fault level setting of these relays shall be as per the MSEB Norms so that individual breaker will activate / trip to arrest the fault in local circuit and fault will not travel to main breakers at MRS and subsequently to MSEB Power Feeder. This Job must be carried out through OEM or authorised personnel including maintaining and submitting the testing report to the entire satisfaction of Engr-in-Charge. Make of VCB : Kirloskar as OEM Note :- Spares used during servicing will be measured and paid separately under respective item of BOQ.
Supply only in replacement including testing and commissioning of spring charging motor, 220 VDC, suitable/compatible to existing 11 KV VCB Panel, A12 62D type including dismantling of existing one complete all as specified and directed. Make of VCB : Kirloskar as OEM.
Supply only in replacement including testing and commissioning of Coil Closed & Tripped Coil, 110 Volts, suitable/compatible to existing 11 KV VCB Panel, A12 62D type including dismentaling of existing one complete all as directed. Make of VCB: Kirloskar as OEM.
Supply only in replacement of TNC switch, 220 VDC, suitable/compatible for operation of existing 11 KV VCB Panel, A12 62D type including dismantling of existing one complete all as directed. Make : Kirloskar as OEM.
Supply only Vaccum Interrupter Bottle, Model No/Cat Part No. 12014, suitable /compatible to existing 11 KV VCB Panel, A12 62D type, Current rating 2000 Amps, 12 kV, 26.3 kA including dismentaling of existing one complete all as directed. Make of Vacuum Interrupter Bottle : Bharat Electronics or its equivalent as approved by Engr-in-Charge.
Preventive maintenance and servicing of 11 KV HT VCB, MDO Type, Rated Current 400A, 50 Hz, Outdoor type by taking out the breaker trolley of 11 KV HT VCB, cleaning from inside and outside by using CRC-26 spray and applying petrolium jelly to the all moveable parts, Male /female bushing/ terminals/ Spouts of VCB. Complete servicing of switchgear including checking the fixed / moving contacts of all the 3 phases adjusting electrical/ electronic/mechanical components all as per mfg instruction manual and standard practice including testing, , charging of SF6 gas and rectifying the gas leakage issues and calibration of relay of any make (e.g. Earth Fault relay / Over current relay/ Master Trip relay etc) of 11 KV VCB Panel. The fault level setting of these relays shall be as per the MSEB Norms so that individual breaker will activate / trip to arrest the fault in local circuit and fault will not travel to main breakers at MRS and subsequently to MSEB Power Feeder. This Job must be carried out through OEM or authorised personnel including maintaing and submit the testing report to the entire satisfaction of Engr-in-Charge. Make of VCB : L & T as OEM Note :- Spares and SF6 gas used during servicing will be measured and paid separately under respective item of BOQ.
Supply only in replacement Master Trip Relay, Model No. VAX31ZG8071BCH (ALSTOM), suitable/compatible to existing 11 KV VCB Panel, including dismentaling of existing one complete all as directed. Make of VCB : L & T as OEM.
Supply only in replacement including testing and commissioning of Spring charged indication switch, suitable/compatible to existing 11 KV VCB Panel including taking down of existing one complete all as directed. Make of VCB: L & T as OEM.
Supply only in replacement of TNC switch, 220 VDC, suitable/compatible for operation of existing 11 KV VCB Breaker including dismantling of existing one complete all as directed. Make : L & T as OEM.
Supply only in replacement including testing and commissioning of spring charging motor, 220 VDC, suitable/compatible to existing 11 KV VCB Panel including dismantling of existing one complete all as specified and directed. Make of VCB : L & T as OEM.
Supply only in replacement O/C & E/F protection relay 30V DC supply, numerical 4 Pole, 3 O/C & E/F non directional protection relay, model MC61A-nX including relay testing by injecting fault current and calibration, taking down existing one complete all as directed.
Preventive maintenance and servicing of 11 KV HT VCB, MDO Type, Rated Current 400A, 50 Hz, Outdoor type by taking out the breaker trolley of 11 KV HT VCB, cleaning from inside and outside by using CRC-26 spray and applying petrolium jelly to the all moveable parts, Male /female bushing/ terminals/ Spouts of VCB. Complete servicing of switchgear including checking the fixed / moving contacts of all the 3 phases adjusting electrical/ electronic/mechanical components all as per mfg instruction manual and standard practice including testing, charging of SF6 gas and rectifying the gas leakage issues and calibration of relay of any make (e.g. Earth Fault relay / Over current relay/ Master Trip relay etc) of 11 KV VCB Panel. The fault level setting of these relays shall be as per the MSEB Norms so that individual breaker will activate / trip to arrest the fault in local circuit and fault will not travel to main breakers at MRS and subsequently to MSEB Power Feeder. This job must be carried out through OEM or authorised personnel including maintaining and submit the testing report to the entire satisfaction of Engr-in-Charge. Make of VCB : Areva as OEM
Preventive maintenance and servicing of 11 KV HT OCB, MDO Type, Rated Current 400A, 50 Hz by taking out the breaker trolley of 11 KV HT OCB, cleaning from inside and outside by using CRC-26 spray and applying petrolium jelly to the all moveable parts, Male /female bushing/ terminals/ Spouts of VCB. Complete servicing of switchgear including checking the fixed / moving contacts of all the 3 phases adjusting electrical/ electronic/mechanical components all as per mfg instruction manual and standard practice including testing and calibration of relay of any make (e.g. Earth Fault relay / Over current relay/ Master Trip relay etc) of 11 KV OCB Panel. The fault level setting of these relays shall be as per the MSEB Norms so that individual breaker will activate / trip to arrest the fault in local circuit and fault will not travel to main breakers at MRS and subsequently to MSEB Power Feeder. This job must be carried out through OEM or authorised personnel including maintaining and submit the testing report to the entire satisfaction of Engr-in-Charge. Make of OCB : Alstom as OEM Note :- Spares used during servicing will be measured and paid separately under respective item of BOQ.
Supply only in replacement of TNC switch, 220 VDC, suitable/compatible for operation of existing 11 KV VCB Breaker including dismantling of existing one complete all as directed. Make of OCB : Alstom as OEM.
Supply and Toping up of Insulation oil, suitable/compatible to Existing OCB 11 KV HT, di-electric strength not less than 50 KV. All as specified and directed.
Preventive Maintenance & Servicing of 11 KV HT RMU (Ring Main Unit), type - RM6, cleaning from inside and outside by using CRC-26 spray and applying petrolium jelly to all moveable parts, male /female bushing/terminals/spouts of RMU. Complete servicing of switchgear including checking the fixed / moving contacts of all the 3 phases adjusting electrical/electronic/mechanical components all as per mfg instruction manual and standard practice including testing, charging of SF6 gas and rectifying the gas leakages issues and calibration of relay any make (e.g. Earth Fault ralay / Over current relay/ Master trip relay etc) of 11 KV HT RMU. The fault level setting of these relays shall be as per the MSEB Norms so that individual breaker will activate / trip to arrest the fault in local circuit and fault will not travel to main breakers at MRS and subsequently to MSEB Power Feeder. This Job must be carried out through OEM or authorised personnel including maintaining and submitting the testing report to entire satisfaction of Engr-in-Charge. Make of RMU : Schneider as OEM Note :- Spares and SF6 gas used during servicing will be measured and paid separately under respective item of BOQ.
Supply only in replacement including testing and commissioning of spring charging motor for RM-6 Breaker, 630 A, 50 Hz, 110 VDC, suitable/compatible to existing Ring Main Unit (RMU) including dismantling of existing one complete all as specified and directed. Make of RMU : Schneider as OEM.
Supply only in replacement including testing and commissioning of Coil Closed & Tripped Coil, 110 Volts, suitable/compatible to existing 11 KV HT RMU, 630A, 50 Hz, RMU Model : RM6 Type Breaker including dismentaling of existing one complete all as directed. Make : Schneider as OEM.
Supply only in replacement including testing and commissioning of instantaneous O/C & E/F protection relay 30V DC supply, numerical 4 Pole, 3 O/C & E/F non directional protection relay, model ADR241A including relay testing by injecting fault current and calibration, taking down existing one complete all as directed.
Preventive Maintenance & Servicing of 11 KV HT RMU (Ring Main Unit), type - "FLUOFIX-GC", cleaning from inside and outside by using CRC-26 spray and applying petrolium jelly to all moveable parts, male /female bushing/terminals/spouts of RMU. Complete servicing of switchgear including checking the fixed / moving contacts of all the 3 phases adjusting electrical/electronic/mechanical components all as per mfg instruction manual and standard practice including testing, charging of SF6 gas and rectifying the gas leakages issues and calibration of relay any make (e.g. Earth Fault ralay / Over current relay/ Master trip relay etc) of 11 KV HT RMU. The fault level setting of these relays shall be as per the MSEB Norms so that individual breaker will activate / trip to arrest the fault in local circuit and fault will not travel to main breakers at MRS and subsequently to MSEB Power Feeder. This Job must be carried out through OEM or authorised personnel including maintaining and submitting the testing report to entire satisfaction of Engr-in-Charge. Make of RMU : C & S as OEM Note :- Spares and SF6 gas used during servicing will be measured and paid separately under respective item of BOQ.
Supply only Operating Handle made up of high tensile galvanised iron, suitable/compatible to "FLUOFIX-GC" type RMU Breaker, 630 A, 50 Hz, 110 VDC, complete all as specified and directed. Make of RMU : C & S as OEM.
Supply only in replacement including testing and commissioning of Coil Closed & Tripped Coil, 110 Volts, suitable/compatible to existing 11 KV HT RMU, 630A, 50 Hz, RMU Model : "FLUOFIX-GC" Type Breaker including dismentaling of existing one complete all as directed. Make : C & S as OEM.
Supply only in replacement including testing and commissioning of instantaneous O/C & E/F protection relay 30V DC supply, numerical 4 Pole, 3 O/C & E/F non directional protection relay, model ADR241A including relay testing by injecting fault current and calibration, taking down existing one complete all as directed.
Supply only in replacement 11 KV HT Cable terminal Protector right angle boot to prevent flashover/short circuit due to intervention by reptiles/insects etc, suitable / compatible to existing 11 KV HT VCB/OCB/RMU including taking down existing one complete all as directed. Make : 3M/Mseal/Raychen/Denson
Supply and charging / Refilling onsite SF6 Gas, required for 22/11 KV VCBs/RMUs etc including finding out leakage issues and rectification of leakage complete all as directed.
M & L including testing and commissioning of Power Pack unit incoming voltage 230 Volts and outgoing voltage 24 Volts DC suitable/ compatible to existing 22/11 KV VCB Panel including dismantling of old one complete all as directed. Make : Alan/ABB/Schneider
M & L for disconnecting carefully Eelectrical Power Cable (approx No of Cable 8-10 per Trench) any type/size from any type/capacity of ACB/VCB/RMU, keeping them at safe side and taking out the ACB / VCB / RMU trolley of any make for carrying out cleaning of cable duct, size (9 x 0.8 x 1.0) Mtr (LxWxD) (by removing mud, foreign mtaterial or other waste acrticles etc and thrown away atleast 100 mtr from working site) including re-installing the ACB/ VCB / RMU including reconnecting the all cable connections etc according to existing system complete all as directed by Engr-in-Charge.
S & F in replacement Aluminium Busbars electrolytic grade suitable for 11KV/440Volts, Current rating and KA rating as per site requirement and interconnected links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in a dedicated compartment. The size and thickness of busbars shall be as per sample including drilling, cutting and suitable size of galvanised or cadmium plated high tensile nuts, bolts and washers etc complete all as directed.
M & L for repair of Battery Charger, Input : 220/250 Volts, AC, 1-ph, Output : 6 to 72 Volts, DC, 10 Amps complete with taking down burned core and coil winding and made it serviceable by change and re-winding the coil with new copper wire as per existing gauge including core assembly etc complete all as specified and directed by Engr-in-Charge. Note :- The rates quoted against the item is deemed to be included for cost of Labour, cost of T & P required for servicing and cost of handling / transportation of defective item to and from Civil workshop for repair / servicing. Make of charger : Nana
Supply and Installation in replacement of lead acid DC battery 12 Volts, 180 Ah complete with electrolyte and initial charge with required size of lugs and terminal cap etc including taking down existing one complete all as specified and directed.
M & L for repair of Lead Acid DC battery, 12V, 180Ah capacity complete with electrolyte and initial charge installed at various Sub Stns inside NDA Campus complete all as specified and directed by Engr-in-Charge. Note :- The rates quoted against the item is deemed to be included for cost of Labour, cost of T & P required for servicing and cost of handling / transportation of defective item to and from Civil workshop for repair / servicing. Make : Exide/Amaron
Supply and Installation in replacement of Inverter potable type of 950VA/760W capacity, Busbar rating 12V DC 58+/- 2A, Input : 220V/5.32A AC, 50 Hz, 1-ph. Output : 220 V/4.32A AC, 50 Hz, including complete electrical connection according to existing system and taking down existing one complete all as specified and directed by Engr-in-Charge. Make : Microtek/M-Guard/Liminous /Su-kam
M & L for repair of Inverter potable type of 950VA/760W capacity, Busbar rating 12V DC 58+/- 2A, Input : 220V/5.32A AC, 50 Hz, 1-ph. Output : 220 V/4.32A AC, 50 Hz by replacing its unserviceable parts andmade it serviceable and re-installed according to existing system complete all as specified and directed by Engr-in-Charge. Make : Microtek, Model No. HB 950, V2. Note :- The rates quoted against the item is deemed to be included for cost of Labour, cost of T & P required for servicing and cost of handling / transportation from work site to Civil workshop and vice-versa for repair / servicing.
Supply and toping up of distilled water in batteries as per site reqirement at various sub/stns inside NDA campus complete all as specified and directed by Engr-in-Charge. Note : Distilled water supply in sealed container or bottles.
Preventive maintenance and servicing of 11 KV HT, 400 Amp Load Break Switch, cleaning from inside and outside by using CRC-26 spray applying petrolium jelly to moveable parts, Male /female bushing/ terminals/ Spouts of switchgear. Complete servicing of switchgear including checking the fixed / moving contacts of all the 3 phases adjusting electrical/ electronic/mechanical components all as per mfg instruction manual and standard practice including testing. This job must be carried out through OEM or authorised personnel including maintain and submit the testing report to entire satisfaction of Engr-in-Charge. Make of Switchgear : GC Lucy as OEM
M & L in replacement for Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed on HT Poles/Transformer/Sub Stn Fencing/VCB Penaletc with M.S. clamps, bolts and nuts of required size, for 22 KV HT of size 250 X 200mm complete including taking down existing one complete all as directed.
M & L in replacement for Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed on HT Poles/Transformer/Sub Stn Fencing/VCB Panels etc with M.S. clamps, bolts and nuts of required size, for 11 KV HT of size 250 X 200mm complete including taking down existing one complete all as directed.
M & L in replacement of warning board, written as "Don't Switch On Men work on Line" size (300x300) mm and 1.6mm thickness made up of MS Sheet and welded with suitable size of MS angle stand and hanging arrangement also including painting on both side with Post Office Red Colour make as per sample given by Engr-in-Charge.
S & Fix including testing in replacement of Digital Multifunction Meter LED, Accuracy Class 5, suitable for 11/22 KV VCB Breaker Panel with RS 485 Parameters V,A,F,PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On Hours, Phase angle, Interrupts,THD, Events (High-Low), Neutral Current suitable for 11/22 KV VCB Panel including cutting & drilling of required size of panel sheet without disturbing to other accessories and taking down old unsv meters etc complete all as specified and directed at site.
Supply only in replacement control wiring of 1.5 Sqmm single core multi-stranded FRLS copper conductor insulated with heat shrinkable PVC sleeve tagged and secured for indicators / meters including suitable size of copper lugs, PVC cable ducts, galvanised or cadmium plated high tensile nuts, bolts and washers etc complete all as specified and directed.
S & F in replacement of PVC insulated 50 Sqmm FRLS single core bright annealed bare copper conductor heavy duty unsheathed multistranded cable 650/1100 Volts grade with suitable size of copper lugs including taking down existing one complete all as specified and directed.
S & F in replacement LED Indicator lamp Red/Yellow/Blue size as per site requirement including suitable size of nuts, bolts including drilling and cutting in panel without disturbing other existing fitments complete all as specified and directed at site.
S & F in replacement of 11 KV CT Ratio 150/5 Amp (Current Transformer), Nominal system voltage (KV rms) : 11 KV, frequency 50 Hz, Rated output (VA burden) : 10 VA, Class of accuracy : 0.5S, Resin Cast, Ring Type CT, Termination S1 & S2 shall be clearly marked including all required controll wiring and dismentaling of 11 KV cable by taking proper shutdown with all safety aspects of any size and refixing it after installation of CT's complete all as directed by Engr-in-Charge.
S & F in replacement of 11 KV CT Ratio 100/5 Amp (Current Transformer), Nominal system voltage (KV rms) : 11 KV, frequency 50 Hz, Rated output (VA burden) : 10 VA, Class of accuracy : 0.5S, Resin Cast, Ring Type CT, Termination S1 & S2 shall be clearly marked including all required control wiring and dismantling of 11 KV cable by taking proper shutdown with all safety aspects of any size and refixing it after installation of CT's complete all as directed by Engr-in-Charge.
M&L in replacement of GI strip 25 x 4 mm as earth continuity conductor or main earthing lead fixed to Transformer/VCB/ OCB/ etc wall batten or recess or chases or buried in ground or fixed to poles or any other indicated situation with suitable size of shaddle at suitable gaps, nut, bolts and washers etc complete all as specified and directed.
M & L for servicing and repairing of 22 KV HT (GOD) Gang Operating Device by taking proper shutdown and applying petrolium jelly on male female contacts, tightning Nut, Bolts and washers and also Jumpers, lightning arrestors, etc including preparation of surfaces of complete Two Pole structure with MS Channels, Cross Arms, Operating Handle etc and applying two coat of Aluminium paint on complete 2 pole structure including MS Channel, Cross Arms, Operating Handle etc complete all as specified and directed
Labour for tree branch cutting of high rise trees, overhanging/interferences to the Two/Four Pole Structure GODs (size of tree branch approx 80 mm to 300 mm dia and 5 to 8 mtr long) without damages to the Two/Four Pole Structure/GODs etc including thrown away the same alteast 100 Mtr away from the Sub Stn Yard complete all as directed. Note : Suitable arrangement i.e ladder, scafolding or any other working plateform required for climbing on high rise trees for carryout said work is the responsibility of vendor/contractor and the rates are deemed to be included in this quoted rate.
S & F in replacement of 22 KV PT unit with PT fuse, Ratio 22000/rt3/110/rt3 Volts (Potential Transformer), Nominal system voltage (KV rms) : 22 KV, frequency 50 Hz, burdaden 100 VA, Class 1, Voltage Factor : 1.2 Continuous & 1.9 for 8 hrs conforms to IS : 3156 or suitable/ compatible to existing system, termination S1 & S2 shall be clearly marked including disconnecting of 22 KV cable by taking proper shutdown with all safety aspects and reconnecting it after installation of PTs complete all as specififed and directed by Engr-in-Charge.
Labour for taking down both side HT/LT Cable and shifting 100 KVA, 11000/433 Volts, 50 Hz, AC Outdoor type Distribution Transformer from Sub Stn 'E' to MES Store Yard and keeping inside shed (distance not more than 2.0 km one way) and lifting 200 KVA, 11000/433 Volts, 50 Hz, AC Outdoor type Distribution Transformer from MES Store Yard to Sub Stn 'E' (distance not more than 2.0 km one way) and Install at Transformer plinth including termination of its both HT /LT side with HT/LT Power Cables by taking proper safety precautions for working personnel complete all as directed by Engr-in-Charge. Note : (a) The contractor shall be responsible and cost for loading, unloading, shifting of above said Transformers by suitable mode of transport/vehicle etc is deemed to be included in this job. (b) If any damage occured to the transformer during this course of action, the damaged parts of the Transformer shall be replaced by the contractor without any extra cost to the Deptt.
S & F in replacement of transparent tuffend glass of 2.5 mm thickness & size 300 mm x 450 mm including taper all corners of the glass and fixed with the help of neoprane rubber gaskets etc to Existing 11 KV HT VCB Panel complete all as specififed and directed by Engr-in-Charge.
Supply only in replacement of PT fuse link of capacity 22 KV, 2 A rating cylindrical type or suitable/compatible to existing 22 KV VCB Breaker including testing after re-fixing and taking down existing old one complete all as directed.
S & F in replacement of PT fuse link of capacity 11 KV, 1 A rating cylindrical type or suitable/compatible to existing 11 KV VCB Breaker including testing after re-fixing and taking down existing old one complete all as directed.
S & F in replacement of PT fuse link of capacity 11 KV, 16 A rating cylindrical type or suitable/compatible to existing 11 KV OCB Breaker including testing after re-fixing and taking down existing old one complete all as directed.
S & F in replacement of old broken cold rolled mild steel Hinges, suitable/compatible to existing 22/11 KV VCB/OCB Breaker including welding and painting to match with existing colour etc complete all as specified and directed.
SONU ENTERPRISES
Tejas Enterprises
PAMS ENTERPRISES
GRAND SERVICES
CHAITANYA WINDWELL
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .