Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.1 LAccepted-AOC | L1 | Accepted-AOC L1 accepted | |
| 2 | L2₹39.0 L+₹93,326 (2.45%)Rejected-Finance | L2 | Rejected-Finance L2 accepted |
Tender Value
₹38.1 L
EMD Value
₹29,100
Closing Date
25 Mar 2025, 3:00 pmClosed
Superintending Engineer PWD
Office of the Superintending Engineer PWD Buildings Construction and Maintenance Circle Chepauk Chennai 5
Provision of LT panel for Medical equipments including power mains arrangements in New Super Speciality Block building at Government Peripheral Hospital, Periyar Nagar, Chennai-82.
2025_PWD_534816_1
TNPWD/50-1 BCM/2024-25
Open Tender
Electrical Works
Lump-sum
Periyar Nagar
Please refer Tender documents.
7 documents required · 7 mandatory
₹0
₹29,100
26 May 2025
22 Mar 2025
25 Mar 2025
22 Mar 2025
25 Mar 2025
22 Mar 2025
Amount
Supply and Erection of 630A capacity dust and vermin proof cubical panel board made up of 16 SWG CRCA sheet steel with supply and fixing of the following interior mounting switches with centre bus chamber and vertical covers, cable chamber on both side of the bus bar chamber at the extreme ends on both side and confirming in I.S specifications INCOMER 630A 4P MCCB -1 No OUTGOING 400A TP MCCB – 3 Nos (MRI, Cath, Spare) 250A TP MCCB - 5 Nos (3 Nos x-ray, 2 Nos spare)160A TP MCCB - 2 Nos The bus bar chamber with consist of 4 Nos 2” x 3/4” tinned copper flat for phase and neutral buses on epoxy moulded bus insulated at proper and sufficient spacing between the buses as per IE rules.This bus bar chamber should be segregated from the adjacent chamber by providing hylem sheet of suitable thickness as partisans .2Nos 1/4” tinned copper flats should be provided all round the panel of earth bus. The fuse switches should be connected with the phase and neutral buses with suitable size of rigid copper flat/rod with suitable lugs phase and neutral tinned buses should be tinned properly.
The panel should be powder coat paint of approved colour approved by the site officer and also the danger board. The capacity of the switches size of incoming and out going cable the place to which the supply is fed should be mounted on switch chamber. The panel board should be mounted on 100mm x 50mm x MS channel provided all around the bottom of the panel. The whole arrangement should be erection of a angle iron frame pedestal to be constructed with suitable foundation bolts and nuts such that the lowest switch handle is at a height of 1.0 m from the ground level and with necessary earth connection
Supply and clarnping of 3 run of 3.5 x 240 sq.mm. PVC LTUG armoured cable on post or on wall with MS clamps
Supply and fixing of brass cable gland for 3-1/2 x 240 sq.mm. PVC armoured LTUG cable with earth connection
Supply and providing cable end termination of 3-1/2 X 240 Sqmm PVC LTUG Cu.armoured cable with necessary sockets by crimping etc with electrical connection complete
Supply and fixing of GI Hot Dip / Powder Coated 14 SWG Cable Tray with 300mm width and 50mm height on wall/ceiling with necessary supports complete
Supply and fixing of GI Hot Dip / Powder Coated 18 SWG Cable Tray cover with 300mm width and 50mm height on cable trays complete
Supply,Fabrication and Erection of MS Section like 5mm thick plates, angles, rods as per IS standards having Yield strength of E-250 as per approved connections including hardwares like Anchor Bolts, Foundation Bolts etc., required machineries and equipments. structure shall be sand blasted SA2.5 ginish and coated by two coats of primer and two coats of Synthetic Paint of approved colour and make including transportation,Cutting, threading, machineries etc.,complete
GST at 18%
Sathyanarayana Electricals (BID ID -1277851)
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .