Superintending Engineer, SWEC, PWD
OFFICE OF THE SUPERINTENDING ENGINEER (P.W.Dte) South-Western Electrical Circle PWD Compound,Midnapore,Paschim Medinipur
Construction of 50 Bedded Critical Care Block (CCB) in the campus of Bankura Sammilani Medical College and Hospital, Bankura----SITC of UPS.
2024_WBPWD_775022_1
WBPWD/SE/SWEC/NIQ58/2024-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
BANKURA
Please refer Tender documents.
3 documents required · 3 mandatory
₹28,603
O/O of SE, SWEC,PWD, PWD Compound, Midnapur
21 Feb 2025
3 Dec 2024
19 Dec 2024
3 Dec 2024
17 Dec 2024
5 Dec 2024
5 Dec 2024
Amount
SITC of 30 KVA UPS including Battery Bank of (20160 ~ 24960) VAH or higher (SMF Battery 12 Volt, 42AH ~ 65AH) 3ph Input /3ph Output, Static by-pass arrangement, compitable with D.G.Set, DSP controlled IGBT based rectifier with minimum 90% efficiency on 100% Load. The UPS shall be provided with active input P.F. Correctional system to obtain 0.9 lag at 100% resistive Load, Wave form - Pure sine wave. Crest Factor- 3:1 It Should be capable of operating in 50'c above ambient temprature, Built in Solid State float cum boost charger with automatic boost / trickel charge mode with current Limiting features. The charger should be designed for at least 15% of the total battery current. The UPS Should have current limiting protection, built in over load /Short circuit protection with snubber circuits for current limit. Soft start arrangement, Over voltage / under voltage protection, mains ON, Inverter ~ON/ OFF/ FAULTY/ TRIP (Reason), Charger ON/ FAULTY or TRIP, Battery Low, Static by-pass ON, Over temperature. Inbuilt Isolation Transformer of 1:1 ratio connected in Delta Star Mode. Battery set Complete with self-standing cubicle or cabinet. The UPS should have external automatic load transfer switch for parallel operation.
Regulated Sealed Lead Acid Battery, Construction type : AGM or VRSLAB in ABS Flame Retardant Rating (12V SMF Battery - 42AH ~ 65AH) (Battery Make Amararaja /Quntra/Exide Power Safe. Back-up time: 30 Min at full load. Warranty : One Year on UPS and One Year on SMF Battery on-site against any manufacturing defects. Certificate : 1SO 9001:2015, 1SO 14001:2015, ISO 18001,0HSAS 18001. CE Certification: IEC/EN 62040-1- 1, IEC/EN50091- 1,IEC/EN 60950(Safety),IEC/ EN 5009 I-2,IEC/ EN 62040-2 (EMC Emmission), IEC/EN 62040-3 (Performance & Design), IEC/EN 61000-4(EMC Emmunity) & IEC/ EN 60146 (Design & Manufacture) (Make: APC-Schneider Electric/ NUMERIC/ VERTIV/ Delta )
MITRA ELECTRONICS (BID ID -5859465)
ASIM KRISHNA MODAK (BID ID -5859646)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .