Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.3 LAccepted-AOC A 303 VEENA CGHS LTD PLOT NO 5D SECTOR 22 DWARKA NEW DELHI 110077 | NEW DELHI | SOUTH WEST DELHI | DELHI | 110077 | L1 | Accepted-AOC Being L1 Bidder | |
| 2 | L2₹17.6 L+₹93,730 (5.64%)Rejected-AOC 205 PARSHAV VIHAR PLOT NO 50 1 P EXTN PATPARGANJ DELHI 110092 | DELHI | EAST DELHI | DELHI | 110092 | L2 | Rejected-AOC Not L1 Bidder | |
| 3 | L3₹18.5 L+₹1.9 L (11.1%)Rejected-AOC | L3 | Rejected-AOC Not L1 Bidder | |
| 4 | L4₹20.0 L+₹3.4 L (20.3%)Rejected-AOC BUILDING NO FLAT NO 19 6TH CROSS ROAD SANJEEVINI NAGAR MUDALAPALYA BANGALORE 560072 | BANGALORE | BANGALORE | KARNATAKA | 560072 | L4 | Rejected-AOC Not L1 Bidder | |
| 5 | L5₹20.0 L+₹3.4 L (20.3%)Rejected-AOC NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | L5 | Rejected-AOC Not L1 Bidder |
Tender Value
Refer Docs
EMD Value
₹54,980
Closing Date
21 Apr 2021, 6:00 pmClosed
GE U WATER SUPPLY DELHI CANTT 10
GE U WATER SUPPLY DELHI CANTT 10
REPAIR REPLACEMENT OF LT PANEL BOARD UNSERVICEABLE MCCBS CHANGEOVER SWITCHES POWER CONTACTOR AMMETER VOLMETER AND ALLIED WORKS IN THE AREA OF AGE U WATER SUPPLY NO III UNDER GE U WATER SUPPLY DELHI CANTT 10
2021_MES_433158_1
GE/WS/D-170 of 2020-21
Open Tender
Civil Works
Item Rate
180 days
GE U WATER SUPPLY DELHI CANTT 10
Please refer Tender documents.
5 documents required · 5 mandatory
₹500
GE U WATER SUPPLY DELHI CANTT 10
₹54,980
Yes
13 Aug 2021
26 Mar 2021
23 Apr 2021
26 Mar 2021
21 Apr 2021
9 Apr 2021
Amount
Maintenance repair of LT Control panel including cleaning in side the panel, tightening of all connection complete installed at bore well at different locations and replacement of spare parts as required during the maintenance (spare parts will be measured and paid of seperately under relevent item
Maintenance/repair at LT Control panel including cleaning in side the panel, tightening of all connection complete installed at pump house for centrifugal pump set at different places in the area and replacement of spare parts as required during maintenance (Spare part will be measured and paid seperately under relevent item) complete upto 25 HP motor pump set (once in a month) with FASD starter and MCCB.
Material and labour for removing old paint by paint removers or burning off by blow lamps and cleaning with scrapers, any number of coats, any width or girth from the existing suction/ delivery pipe line including headers of any size complete all as specified and as directed
Material and labour for painting to existing surcface by using spray gun with one coat of red oxide and two coat of synthetic enamel paints 1st quality on existing suction/ delivery pipe lines, including Headers of any size using Blue/Red/Black colour as per site requirement complete all as specified and as directed
S&F in replacement moulded case circuit breakers 3 Pole 415 Volt adjustable type 320 Amp with breaking capacity 36 KA
S&F in replacement moulded case circuit breakers 3 Pole 415 Volt adjustable type 250 Amp with breaking capacity 36 KA.
S&F in replacement moulded case circuit breakers 3 Pole 415 Volt adjustable type 200 Amp with breaking capacity 25 KA.
S&F in replacement moulded case circuit breakers 3 Pole 415 Volt adjustable type 160 Amp with breaking capacity 25 KA.
S&F in replacement moulded case circuit breakers 3 pole 125 Amps having breaking capcity 25 KA at 415 volts.
S&F in replacement moulded case circuit breakers 3 pole 100 Amps having breaking capcity 25 KA at 415 volts.
S&F in replacement moulded case circuit breakers 3 pole 63 Amps having breaking capcity 10 KA at 415 volts type DU-100
S&F in replacement onload changeover switch 4 pole 200 Amps panel mounted compete all as specified and as directed
S&F in replacement onload changeover switch 4 pole 250 Amps panel mounted compete all as specified and as directed
S&F in replacement onload changeover switch 4 pole 320 Amps panel mounted compete all as specified and as directed
S&F in replacement onload changeover switch 4 pole 400 Amps panel mounted compete all as specified and directed
S&F in replacement offload changeover switch 4 pole 250 Amps in sheet enclosure compete all as specified and as directed
S&F in replacement offload changeover switch 4 pole 320 Amps sheet enclosure compete all as specified and directed
S&F in replacement 3 pole power contactor ML-02,32 Amps 415 volts, 50 HZ suitable for fixing in existing panel
S&F in replacement 3 pole power contactor ML-1.5, 25 Amps suitable for fixing in existing panel
S&F in replacement of fully automatic star - delta straters in sheet enclosure type ML-1.5 FASD
Supply and fixing in replacement of fully automatic star delta starter type ML-2
M&L in replacement of single phase preventor type VSP-II complete all as specified and as directed
S & F in replacement of Amp Meter 0 to 100 Amp of size 96 mm x 96 mm Analog Type complete all as specified and directed
S & F in replacement of Volt Meter 0 to 500 Volts of size 96 x 96 mm Analog Type complete all as specified and as directed
S & F in replacement of Amp Meter 0 to 100 Amp of size 96 mm x 96 mm Digital Type complete all as specified and as directed
S & F in replacement of Volt Meter 0 to 500 Volts of size 96 x 96 mm Digital Type complete all as specified and as directed
S & F in replacement of phase indicator lamp LED type assembly as per site requirement
M&L PVC insulated multistranded copper conductor wire, 1100 Volts in replacement, single core of size 1.5 Sq mm complete all as specified and as directed
M&L PVC insulated multistranded copper conductor wire, 1100 Volts in replacement, single core of size 2.5 Sq mm complete all as specified and as directed
S&F in replacement of thermal over load relay type ML-2/3 relay range 10-16 Amps
S&F in replacement of thermal over load relay type ML-2/3 relay range 20-32 Amps
Material and labour for removing any type of old paint by paint removers or burning off by blow lamps and cleaning with scrapers, any number of coats, any width or girth from the existing Centrifigal Motor and pump of cap 15 to 75 HP complete all as specified and as directed
Material and labour for painting to existing surface of Centrifugal motor and pump Sets of capacity 15 to 75 HP by using spray gun with one coat of red oxide and two coat of synthetic enamel paints as per colour code as mentioned below of make Burger/Asian/Nerolac of first quality complete all as specified and as directed
Motor colour - Dark Grey
Pump colour - Blue
Coupling - Black
Material and labour for painting to existing surcface of NRV,sluice valves/Strainers valves of capacity 80 mm to 150 mm by using spray gun with one coat of red oxide and two coat of synthetic enamel paints 1st quality as per colour code as mentioned below complete all as specified and as directed
NRV colour - Black
Sluice Valve colour - Black
Disconnecting, taking out and removing old existing unserviceable underground, LT XLPE/PVC insulated Aluminium conductor cable of any description and in any position complete including taking down existing protection pipe etc, for the size of 35 Sqmm to 50 Sqmm of any core from ducts / trenches / poles /pipes etc complete all as specified and as directed
supply and Laying XLPE insulated, heavy duty electric cable with aluminium conductor 1100 Volts grade, cross-sectional area 35 sqmm 3.5 core laid in trenches/ducts, floors, fixed to walls etc complete all as specified and as directed
supply and Laying XLPE insulated, heavy duty electric cable with aluminium conductor 1100 Volts grade, cross-sectional area 50 sqmm 3.5 core laid in trenches/ducts, floors, fixed to walls etc complete all as specified and as directed
supply and Laying XLPE insulated, heavy duty electric cable with aluminium conductor 1100 Volts grade, cross-sectional area 70 sqmm 3.5 core laid in trenches/ducts, floors, fixed to walls etc complete all as specified and as directed
M&L cable jointing kit for 1.1 KV grade cable for straight through heat shrinkble type joint complete with jointing material suitable 3.5 core XLPE aluminum conductor cable size 35 sqmm to 50 Sqmm complete all as specified and as directed
Excavation in trenches not exc 1.5 Mtr wide and not exc 1.5 Mtr deep for pipe line/cable in any type of soil getting out and levelling of bottom surface to required level complete all as specified and as directed.
Returning filling in, including spreading, leveling, watering and well ramming in layers not exc 25Cum thick complete all as specified and as directed.
Removing excavated material from site to a distance not exc 50 mtr away and depositing where directed not exc 1.5mtr from the starting point complete all as specified and as directed.
Supplying and laying of Sub class 'B' bricks in trenches for protection to cable complete all as specified and as directed.
Supplying and laying in trenches Jamuna Sand for cushioning complete all as specified and as directed.
Dismantling and taking out old unserviceable LT panel of any desiption and deposited to MES store yard complete all as specified and as directed.
Design, fabricate, supply, install, test and commissioning of factory made floor mounted LT cubical panel board Indoor type made out of 2.00 mm thick CRCA sheet totally enclosed with necessary ventilations, weather, dust and vermin proof with front opening and locking arrangement on front side 415 Volts, 3 phase, 50 Hz having copper bus bar of capacity 630 Amps and full neutral duly colour coded and for neutral supported with DMC/SMC insulators colour coded with heat shrinkable sleeve hearing short circuit current with stand minimum 50 KA for one second complete connection from bus bar to breakers with suitable copper cable, panel board shall be grouted in the ground with suitable size of foundation in PCC 1:2:4 type B1, MS channels for base frame 50x50x6 mm and supports, GI nut, bolts, washers etc. The panel board shall be powder coated and red oxided primed. The panel board shall be fabricated and suitable to accommodate and supply and fixing of the following complete all as specified and directed :-(A) Incoming :- (a) MCCB 4P, 200A, 35KA -01 Nos (B) Out going :- (a) MCCB 3P, 100A, 35KA - 02 Nos.
Design, fabricate, supply, install, test and commissioning of factory made floor mounted LT cubical panel board Indoor type made out of 2.00 mm thick CRCA sheet totally enclosed with necessary ventilations, weather, dust and vermin proof with front opening and locking arrangement on front side 415Volts, 3 phase, 50 Hz having copper bus bar of capacity 1000 Amps and full neutral duly colour coded and for neutral supported with DMC/SMC insulators colour coded with heat shrinkable sleeve hearing short circuit current with stand minimum 85 KA for one second complete connection from bus bar to breakers with suitable copper cable , panel board shall be grouted in the ground with suitable size of foundation in PCC 1:2:4 type B1, MS channels for base frame 50x50x6 mm and supports, GI nut, bolts, washers etc. The panel board shall be powder coated and red oxided primed. The panel board shall be fabricated and suitable to accommodate and supply and fixing of the following complete all as specified and directed :- (A) Incoming :- (a) Changeover switch 250 Amp, 4 pole -01 No. (b) MCCB 4P, 250A, 36KA -02 Nos.
Material and labour for plate earthing with galvanised steel earth plate electrode 60cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanised earth lead 32mm x 6mm strip by means of bolts, nuts, check nuts and washers of galvanised iron or steel all surrounded by adequete quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, earth strip encased in 40 mm bore GI medium grade pipe, including providing watering pipe 20 mm bore GI pipe medium grade from bottom of the earth pit to the top of the electrode complete with earth pit in PCC 1:2:4 type B - 1 using 20 mm graded crushed stone aggregate, earth work and RCC cover complete all as specified and as directed shown in electrical plate number 3 of SSR part -1, incl taking down.
M&L in replacement of bus bar box made out of 2mm thick MS sheet, 3 phase, 4 wire, 415 volts AC supply, outdoor cubical type, dust and vermin proof, floor block mounting type suitable for outdoor applications of size 600mmx600mmx450mm, using 40mmx40mmx5mm angle iron frame with shutter and locking arrangement, painted with two coats of synthetic enamel paint of approved colour over a coat of red oxide primer (internally and externally) for box, height above ground 600mm and grouted 300mm below ground, legs of frame shall be grouted in PCC 1:2:4 (size 300x300x300mm block) including 40mmx10mm-04 nos 500mm long aluminium busbar fixed on insulators with colour coding complete all as specified and as directed.
An amount of Rs 31470.00 shall be deducted from BOQ on account of schedule of credit
SANJEEV ENTERPRISES
somyaenterprises
Rahul Enterprises
Vijay Electricals
Surjit and Sons
BLUE HILL ELECTRICAL AND ELECTRONICS
ACR ENTERPRISES
KISHORE ENTERPRISES
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .