Tender Value
₹40.7 L
EMD Value
₹81,399
Closing Date
11 Feb 2026, 3:30 pmClosed
Registrar
IISc, Bangalore
Renovation of the proposed ICMR lab in old Organic Chemistry building at IISc Bangalore
2026_IISC_895281_1
IISc/Tender-CIV-19/2025-26
Open Tender
Civil Works
Works
150 days
IISc, Bangalore
As Per The Tender Documents
2 documents required · 2 mandatory
₹0
₹81,399
MS Teams Online
17 Apr 2026
22 Jan 2026
12 Feb 2026
23 Jan 2026
11 Feb 2026
5 Feb 2026
2 Feb 2026
Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material to the appropriate disposal area as per direction of Engineer-in-charge.
Dismantling wooden boardings in lining of walls and wooden partitions, including stacking to the appropriate disposal area as per direction of Engineer-in-charge.Thickness above 25 mm up to 40 mm
Hacking of CC flooring, mosaic flooring including cleaning for surface etc. complete as per direction of the Engineer-in-Charge.
Repairs to plaster in patches of 2.5 m2 and less in walls, ceilings 10 to 20mm thick in cement mortar 1:6 including cutting the patches in proper shape and replastering the surface of the wall including disposal of rubbish with a lead of 50m including curing cost of materials, labour, complete as per specification.
Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound ) content less than 50 g/L of approved brand and manufacture, including applying additional coats wherever required to achieve even shade and colour. Two coats as per specifications and as per directions of Engineer in charge.
Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :One coats on old work as per specifications and as per directions of Engineer in charge.
Removing white wash or colour wash by steel brushing and / or scraping, sand papering and preparing wall surface smooth including repairs to scraches including cost of labour, material complete as per specifications.
Providing Half brick masonry with common burnt clay Non Modular bricks of class designation 3.5 in superstructure above plinth level up to floor level cement mortar 1:3 (1 cement :3 coarse sand) including cost of all materials, labour, scaffolding and usage charges of machinery & other incidental charges complete as per the direction of engineer incharge of work.
Providing 15 mm cement plaster on the rough side of single or half brick wall of mix 1:4 (1 cement: 4 fine sand) including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge.
Cutting out cracks of internal and external walls and roof terrace to V - section cleaning out, wetting, grouting with cement and sand slurry 1:3 (1 cement, 3 sand)/ (Crack filler/ crack sealant) including cost of materials, labour, complete as per specifications.
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete as per specifications and as per directions of Engineer in charge.
Finishing walls with water proofing cement paint of required shade :New work (Two coats applied @ 4.84 kg/10 m²) to give an even shade after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge.
Finishing walls with Acrylic Smooth exterior paint of required shade : Old work (Two coat applied @ 1.67 l/ 10 m²) on existing cement paint surface including preparing the surface after thoroughly cleaning the surface to remove all dirt, dust and foreign matter, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge.
Providing and fixing white vitreous china laboratory sink including making all connections including cost of fittings : Size 450x300x150 mm
Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. Flexible pipe 32mm dia
Providing and fixing PVC (S.W.R) Gully Trap 10cms x 10cms with all fitting arrangements & all necessary accessories complete
Providing and fixing 100 mm sand cast Iron grating for gully trap.
Providing and fixing Sink cock with swivel spout & wall flange, wall mountable made of Stainless steel with all concealed fitting arrangements & all necessary accesories complete - Class
Providing and fixing Angle cock light with wall flange made of Stainless steel with all concealed fitting arrangements & all necessary accessories complete - Class
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases, packing and making good the walls etc. Internal 20 mm nominal dia pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External 20 mm nominal dia Pipes
Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete :20mm nominal bore
Constructing brick masonry chamber for underground C.I. inspection chamber and bends with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover with frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg), R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 fine sand : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand), finished smooth with a floating coat of neat cement on walls and bed concrete etc. complete as per standard design: Inside dimensions 455x610 mm and 45 cm deep for single pipe line : With common burnt clay (non modular) bricks of class designation
Providing and fixing 18 mm thick gang saw cut granite of any color and shade, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch up, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.
Providing and fixing chromium plated brass 100 mm mortice latch and lock with 6 levers and a pair of lever handles suitable for glass doors of approved quality with necessary screws etc. complete.
Supply and Installation of Multicell Standing Seam polycarbonate panels having flux 7.0 as per EN 16153 & EN ISO 10077-2. For min joints, panel shall be 1000 - 1200 mm wide with standing seam on both sides. Panels shall have minimum six-seven layers with truss bridge design for higher flexibility and strength. The system shall be secured using suitable connectors with double tooth grip lock locking mechanism and fixed on purlin(to be paid separately) having a pull out load of min 7000N tested as per ISO 6892-1998 and IS 1608-2005. Panels must satisfy impact test as per IS 14443-97 shall show no sign of breakage which have been exposed to UV for 500 Hours (min) as per ASTM G 155. Panels shall have Yellowness Index of not more than 15 units as per ASTM D 1925 when tested on a sample exposed to UV for 500 Hours as per ASTM G 155. Panel shall be closed at the end with additional Aluminium U profile as required. All aluminium should be factory finished / mill finished. Panel shall be fixed over MS structural steel / MS purlin (to be paid separately) conforming to the details in the specifications as per direction of Engineer in charge of work. 16mm Thick Multicell Polycarbonate Panel having U value of 2.1 W/m2 K (max)
Providing and fixing Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. Hot finished welded type tubes including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge.
Providing and fixing Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In stringers, treads, landings etc. of stair cases, including use of chequered plate wherever required, all complete including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge.
Painting with synthetic enamel paint of approved brand and manufacture to give an even shade :Two coats on new work after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge.
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate sections and other sections of approved make conforming to IS: 733 and IS:1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) :For Fixed Portion: Powder coated aluminium (minimum thickness of powder coating 50 micron) including cost of materials, labour, usage charges of machinery complete as per specifications.
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate sections and other sections of approved make conforming to IS: 733 and IS:1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-incharge. (Glazing, paneling and dash fasteners to be paid for separately) :For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) Powder coated aluminium (minimum thickness of powder coating 50 micron) including cost of materials, labour, usage charges of machinery complete as per specifications.
Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineerin-charge: Pre-laminated particle board with decorative lamination on both sides including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge.
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):With float glass (Translucent, opaque, transparent ) panes of 5 mm thickness (weight not less than 12.50 kg/m²) including cost of materials, labour, usage charges of machinery complete as per specifications.
Providing and fixing Brass 100mm mortice latch and lock with 6 levers without pair of handles (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete including cost of materials, labour, usage charges of machinery complete as per specifications.
Providing and fixing chromium plated brass handles of 100/125 mm with necessary screws etc. complete
Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete
Providing and fixing Stainless Steel Fixtures conforming to 304 graded steel as per direction of engineer in charge SS Door stopper 75mm
Providing and fixing aluminium die cast body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 35 kg and door width upto 700 mm), with necessary accessories and screws etc. complete.
Providing and laying linoleum plain, textured flooring or coloured 3.2mm thick sheet / tiles laid with an approved adhesive on sub floor stretching, cutting and fixing complete , including cost of materials, labour, complete as per specifications. ( Make of Forbo, Armstrong )
Taking out existing wooden door shutter/window, repair by cutting, painting etc. and refixing of repaired door shutters/window to existing door/window frames, including replacement of hinges with screws, etc. as required, all complete as per the direction of the Engineer-in-charge.
Renewing glass panes, with putty and nails and repairing steel windows wherever necessary including racking out the old putty: Float glass panes of nominal thickness 4 mm (weight not less than 10kg/m²)
Providing and Applying PU based Elastomeric Liquid Applied PU Waterproofing Membrane single component, cold applied, water based acrylic PU dispersion with highly elastic and UV resistant water proofing treatment to the Existing Roof surface/Chajjas/Sunken portion of WC:Bathroom applied @ 1.2 l/per m2, having tensile strength greater than 1.5N/mm2, elongation greater than 300% with solid content not less than 60% in 2 coats including surface preparation, priming the surface with water based acrylic primer @0.1 l/m2, and spreading 60 gsm geotextile between two top coats completely as per specification. The finished cost to include surface preparation, making coving at Junction, Bore Packing, treatment of construction joints completely as per specification.
Providing and fixing double scaffolding system (cup lock type) on the exterior side of building/structure, upto 25 metre height, above ground level, including additional rows of scaffolding in stepped manner as per requirement of site, made with 40mm dia M.S. tube, placed 1.5 metre centre to centre, horizontal & vertical tubes joint with cup & lock system with M.S. Tubes, M.S. tube challis, M.S. clamps and staircase system in the scaffolding for working platform etc. and maintaining it in a serviceable condition for execution of work of cleaning and/ or pointing and/ or applying chemical and removing it thereafter. The scaffolding system shall be stiffened with bracings, runners, connecting with the building etc, wherever required, if feasible, for inspection of work at required locations with essential safety features for the workmen etc., complete as per directions and approval of Engineer-in-charge (one-time Qty will be considered for payment)
Cleaning of office floors, toilet floors, corridors, lobbies, partitions, storage units, furnitures,electrical & electronic equipments, doors, windows, curtains, blinds etc., including cleaning of dust, etc., using suitable bombay broom stick, squezers
Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates Including shuttering
Dismantling stone slab flooring laid in cement mortar including stacking of serviceable material and disposal of unserviceable material to the appropriate disposal area as per direction of Engineer-in-charge.
Providing and constructing load bearing wall with Solid Concrete blocks of size 400x150x200mm having block density more than 1800kg/m3 and minimum compressive strength of 4.00 N/mm2 conforming to IS 2185 (Part - I) - 2005 and constructed with CM 1:4 as per IS 2572:2005 including cost of all materials, labour, scaffolding and curing, usage charges of machinery etc complete as per specifications.
Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machinery, curing, and all the other appurtenances required to complete the work as per technical specifications. Mix 1:2:4 Using 20 mm nominal size graded crushed coarse aggregates Including shuttering
Removing & Resetting existing Heavy Duty Cobble/Interlocking stones/Pavers of thickness 60/75/80/100mm using Cement and 40mm thick sand bed ( average thickness ) and compacting with plate vibrator to achieve final desired compaction & setting of paver to its final level , including cost of materials, labour and usage charges of machinery complete as per specifications. (The cost of new paver/stones required shall be added separately)
Providing and laying 100mm thick pre-cast cover slabs over drains & Rain pit of width not exceeding 800 mm using M20 concrete reinforced with Micro Alloyed High carbon steel with 3mm - 3ply wired steel @ 2.00 kg/m2, slabs jointed in CM 1:3 proportion and nicely finished Including providing holes in the Cover slabs wherever necessary for easy drainage of surface water including of labour, materials, scaffolding, usage of machinery, curing, lead and lift charges etc, Complete.
Providing and laying 60mm thick factory made cement concrete paver block of approved shape and colour of M -30 grade made of C&D waste by block making machine with vibratory compaction laid in required pattern and including over 50mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge.
Providing, laying, spreading and compacting graded stone aggregate to wet mix macadam specification including premixing the Material with water at OMC in mechanical mix plant carriage of mixed Material by tipper to site, laying in uniform layers with paver/grader in sub-base / base course on well prepared surface and compacting with vibratory roller to achieve the desired density. Wet Mix Macadam (Plant Mix Method)
Providing Flush/ Ruled pointing: Pointing on stone work with cement mortar 1:3 (1 cement : 3 fine sand) after raking joints to depth nicely lining, including cost of materials, labour, curing as per specifications and as per directions of Engineer-in-charge.
Providing and Supply of semi Skilled helper for various works as per the direction of engineer in charge.
Providing and Supply of Skilled manpower welder/carpenter for various works as per the direction of engineer in charge.
Tractor-Trolley for debris shifting ouside the BBMP limits and etc
Supplying and fixing of PVC casing and capping on the wall or ceiling using necessary materials like bends, junction box, elbows, screws at an interval of 300 mm .... etc. as required. 25 mm
Supplying and fixing of PVC casing and capping on the wall or ceiling using necessary materials like bends, junction box, elbows, screws at an interval of 300 mm .... etc. as required. 50 mm
Supplying heavy gauge PVC Conduit Pipe 25mm dia2mm thick with suitable size bends, metal junction boxes adhesive paste etc., by groove cutting in the wall and fixing by bracing U or J hooks and cement plastering upto the wall surface andrun with 18 SWG GI fish wire run throughout the conduit wherever necessary. 19/20 mm dia 2 mm thick
Supplying heavy gauge PVC Conduit Pipe 25mm dia2mm thick with suitable size bends, metal junction boxes adhesive paste etc., by groove cutting in the wall and fixing by bracing U or J hooks and cement plastering upto the wall surface andrun with 18 SWG GI fish wire run throughout the conduit wherever necessary. 25 mm dia 2 mm thick
Supplying heavy gauge PVC conduit pipe.......dia.......mm thick confirming to IS 2509 with suitable size bends,junction boxes,adhesive paste etc,and fixing using inverted wood plugs in case of RCC ceiling and RCC wall/stone structure or rawl plugs in case of brickwalls and cement plastering the damaged portion using heavy gauge saddles at an interval of 700mm using NF screws. 32 mm dia 2.5 mm thick
Supplying and fixing 20/32 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top along with 20/32 A "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. 6Amps one way Switch
Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. 6A Three Way socket
Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. 16A One Way Switch
Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. 6/16A Universal Socket
Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. TV/Telephone Socket
Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. RJ45/I.O Outlet Cat-6
Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. Stepped Fan Regulator Two Module
Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. 32A DP Switch
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. 1 to 2 Module
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. 3 Module
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. 6 Module
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. 12 Module
Supplying and flush mounting powder coated / galvanizedmetal box suitable for mounting modular switch plates. The boxshould be firmly flush mounted after due groove cutting inBrick/Stone/C.C wall 1 to 2 Way
Supplying and flush mounting powder coated / galvanizedmetal box suitable for mounting modular switch plates. The boxshould be firmly flush mounted after due groove cutting inBrick/Stone/C.C wall 3 Way
Supplying and flush mounting powder coated / galvanizedmetal box suitable for mounting modular switch plates. The boxshould be firmly flush mounted after due groove cutting inBrick/Stone/C.C wall 6 Way
Supplying and flush mounting powder coated / galvanizedmetal box suitable for mounting modular switch plates. The boxshould be firmly flush mounted after due groove cutting inBrick/Stone/C.C wall 12 Way
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or wiring with specified IS-694:confirming to latest amendments including terminations with copper lugs 1.5 mm2
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or wiring with specified IS-694:confirming to latest amendments including terminations with copper lugs 2.5 mm2
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or wiring with specified IS-694:confirming to latest amendments including terminations with copper lugs 4.0 mm2
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or wiring with specified IS-694:confirming to latest amendments including terminations with copper lugs 6.0 mm2
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or wiring with specified IS-694:confirming to latest amendments including terminations with copper lugs 10.0 mm2
Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5mm2 (Phase & Neutral) & 1x1.0 mm2 (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box, the other end of the wires shall be terminated with sufficient loose length and copper lugs in a wood/PVC round block. complete for each outlet. Short point upto 3m from tapping point to out let via switch box
Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5mm2 (Phase & Neutral) & 1x1.0 mm2 (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box, the other end of the wires shall be terminated with sufficient loose length and copper lugs in a wood/PVC round block. complete for each outlet. Medium point above 3m upto 6m from tapping point to out let via switch box
Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5mm2 (Phase & Neutral) & 1x1.0 mm2 (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box, the other end of the wires shall be terminated with sufficient loose length and copper lugs in a wood/PVC round block. complete for each outlet. Long point above 6Mtr upto10Mtr from tapping point to out let via switch box
Supplying and fixing regular MCB distribution boards on wall/ood board / flush mounting using required clA, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase/3 phase/single door with powder coated painting Made out of 14 SWG MS enclosure. 12 Way TP & N-Double door
Supplying and fixing regular MCB distribution boards on wall/ood board / flush mounting using required clA, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase/3 phase/single door with powder coated painting Made out of 14 SWG MS enclosure. 12 Way SP & N-Double door
Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materialsand 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898. 6-32 A SP
Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materialsand 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898. 40 A DP
Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materialsand 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898. 50-63 A SP
Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materialsand 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898. 50-63 A DP
Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materialsand 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898. 50-63 A TPN
Supplying and fixing of AC type RCBO on existing MCB distribution board using necessary fixing materials, C curve, capacity of 10 KA and complete wiring as required confirming ot IEC 60947 63A Four pole (4P) RCBO, 415V, 30mA sensitivity Make: Legrand, L&T, Schneider
Supplying and fixing of AC type RCBO on existing MCB distribution board using necessary fixing materials, C curve, capacity of 10 KA and complete wiring as required confirming ot IEC 60947 40A double pole RCBO, 240 V, 30mA sensitivity Make: Legrand, L&T, Schneider
Supplying and fixing regular MCCB distribution Panel confirming to IS/IEC 61439-3 and IK09 tested as per IS/IEC 62262 with minimum IP43 protection provided with Polyurethane (PUR) gasket, with suitable earthing system, on wall /woodboard/flush mounting using required cl A, bolts, nuts, etc.,with provision for fixing of suitable type capacity MCCB's as an incomer for 3 phase Double door with necessary bus bar completely wired to use on 440V 3phase 4wire powder coated painting etc., complete with a provisionfor fixing of three phase suitable capacity MCB/MCCBs as outgoings confirming to IS/IEC 60898 - 2. 4 Way
Supplying and fixing Moulded Case Circuit Breaker(MCCB)over the existing wood/panel board using necessary screws, bolts, nuts, necessary phase separators, handle and wiring complete. Protection of Overload and Shortcircuit with adjustable therma lmagnetic release,Microprocessor release shall have Earth Fault as per IS/IEC60947-2.(Icu=100%lcs). In 4P MCCB, all Poles should have protection for Short-Circuit/OverLoad. For Microprocessor MCCBS Facility for segregating Priority and Non-Priority loads must be available in the MCCB.MCCB shall be provided with double insulation (insulation between front cover and internal power circuits to avoid any accidenta lcontact with live current carrying path with the front cover open).Multi-pole breakers shall be designed to break all the poles simultaneously and they shall have a single mechanism. 125 A 25 kA
Supplying and fixing Moulded Case Circuit Breaker(MCCB)over the existing wood/panel board using necessary screws, bolts, nuts, necessary phase separators, handle and wiring complete. Protection of Overload and Shortcircuit with adjustable therma lmagnetic release,Microprocessor release shall have Earth Fault as per IS/IEC60947-2.(Icu=100%lcs). In 4P MCCB, all Poles should have protection for Short-Circuit/OverLoad. For Microprocessor MCCBS Facility for segregating Priority and Non-Priority loads must be available in the MCCB.MCCB shall be provided with double insulation (insulation between front cover and internal power circuits to avoid any accidenta lcontact with live current carrying path with the front cover open).Multi-pole breakers shall be designed to break all the poles simultaneously and they shall have a single mechanism. 160 A 25 kA
Supplying and fixing 63A, 415V, TPN industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 63A C curve TPNMCB in sheet steel enclosure on surface or in recess, with chained metal cover for the socket outlet and complete with connections , testing and commissioning as required.
Supplying and fixing of TP sheet steel enclosure on surface/enclosure along with 32A, 415V ,C curve TP MCB complete with connections, testing and commissioning etc. as required
Supplying fixing and wiring earth electrode for grounding of lifts, transformers, DGsets etc.using 40mmdia 2.9mm thick 2.5m long GI pipe with GI funnel with mesh and suitable size reducer fixed on the top of the earth electrode.The funnel should be enclosed in a CC chamber of 400x400x400mm with a cast iron cover.The earth electrode shall have staggered holes of 12mm dia and the electrode should be covered 150mm all-round with alternate layers of salt and charcoal from the bottom of the CC chamber.The connection from the electrode is to be established through GI strip using GI bolts and nuts.
Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required.
Providing and fixing 6 SWG dia GI wire on surface or in recess for loop earthing as required
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 Way(4+12) Double door
1.1 kV, XLPE or Heat resistant PVC insulated, PVC exutruted Inner Seath Armoured LTUG Cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armouring strip thickness and resistivity as per IS-3975 16 Sqmm, 4 Core, (11 GI Strips - 4 x 0.8 mm)
1.1 kV, XLPE or Heat resistant PVC insulated, PVC exutruted Inner Seath Armoured LTUG Cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armouring strip thickness and resistivity as per IS-3975 35 Sqmm, 3.5 Core, (14 GI Strips - 4 x 0.8 mm)
1.1 kV, XLPE or Heat resistant PVC insulated, PVC exutruted Inner Seath Armoured LTUG Cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armouring strip thickness and resistivity as per IS-3975 50 Sqmm, 3.5 Core, (16 GI Strips - 4 x 0.8 mm)
Laying of one number of PVC insulated or PVC sheathed/ XLPE power cable of 1.1kV grade of following size on wall surface as required Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Laying of one number of PVC insulated or PVC sheathed/ XLPE power cable of 1.1kV grade of following size on wall surface as required Upto 35 sq. mm (clamped with 1mm thick saddle)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Upto 35 sq. mm (clamped with 1mm thick saddle)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/XLPE aluminium conductor cable of 1.1kV grade as required. 3½ X 50 sq. mm (35mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/XLPE aluminium conductor cable of 1.1kV grade as required. 4 X 16 sq. mm (28mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/XLPE aluminium conductor cable of 1.1kV grade as required. 3½ X 35 sq. mm (32mm)
Supplyingof 1440rpm heavy duty exhaust fan with bracket blades suitable to operate on 230V 50Hz, AC Supply complete. 12" Sweep (300 mm) Make: Bajaj, Crompton, Havells
Fixing one exhaust fan in the nitch already left in the wall with bolts and nuts and 5A.ceiling rose with sufficient length of 23/0.0076i nch PVC insulated twin core wire.
Supply and fixing of LED Bollard light fitting of ...W with pressure die cast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of anti glare clear diffuser with Injection moulded polycarbonate /clear glass material, delivering superior light output Rated life Burning Hrs 50000 hr @ Lumen Maintenance of 70%, CCT > 5500K, IP 66 optical and electrical compartment & impact resistance of complete luminaire > IK08. Power Factor >0.9 with mains, Surge Protection- Min 5KV along with Over voltage/Overload, short circuit/ miss-wiring protection. Universal Voltage driver to operate wide voltage range from 100V to 270V 50/60Hz application. Compliance to IS 10322/IEC 60598, LM 79 & LM 80 Adherence with RoHS. UL approved MCPCB, with 2 years Warranty against any manufacturing defect working under standard electrical condition. 8W/10W 1m Height Make: Philips, Crompton, Havells, Bajaj, Wipro
Supply of LED Streetlight luminaire with pressure die castaluminium housing body for optimal thermal dissipation.Lamp compartment comprising of anti glare clear diffuser with Injection moulded polycarbonate material, delivering superior light output. Rated life Burning Hrs 50000 hr @ Lumen Maintenance of 70%, maximum light intensity should be between 60 degrees to 70 degrees. CCT > 5500K, IP 66 optical and electrical compartment & impact resistance of complete luminaire > IK08. Power Factor >0.9 with mains, Surge Protection- Min 5KV along with Over voltage/ Overload, short circuit/ miss-wiring protection. Compatible for pole mouting with outer dia of 40mm to 50mm. Universal Voltage driver to operate wide voltage range from 100V to 270V 50/60Hz application. Compliance to IS 10322/IEC 60598, LM 79 & LM 80 Adherence with RoHS. UL approved MCPCB. Top access street light with single screw to ensure ease of maintenance at the sight site location with minimized minimal tools. LED Light fixture with ........W System Power consumption. LED Efficiency>130lm/w, nominal CRI >75. Luminaire manufacturer should have in-house facility accredited by NABL/CPRI & any Government certified agency & Design & Development facility certified by ISO 9001:2008 . Housing with supplier word mark /name shall be Engraved / Embossing on the die cast housing/ Body part. Warranty of 2 Years against any manufacturing defect working under standard electrical conditions as mentioned above should be given by LED manufacturer & Cree/Nichia/ Lumileds/Osram make LED Source LED Streetlight 150 W
Supplying and Fixing of........mm dia class A GI pipe bracket upto 2ms long bent at suitable angle and fixing to this bracket street light fitting of all capacities to GI o rGI or rail or RCC pole / wall using suitable clamps, bolts, and nuts and wiring using suitable capacity wires. Using 32mm dia G.I.Pipe
Supplying and drawing UTP-CAT 6E LAN cable.
Supplying and drawing PVC flexible one pair telephone unarmoured tinned copper cable. 2 Pair
Supplying and fixing of MDF krone junction box with KRONE Module / Telephone cable termination. 10 Pair
Supplying & Fixing of switch mounting rack with power manager & Cable manager. 4U with 450mm depth
Supply of materials- 1.1 kV, XLPE or Heat resistant PVC insulated, PVC exutruted Inner Seath Armoured LTUG Cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armouring strip thickness and resistivity as per IS-3975, Copper Control Cable as per IS- 554 (Part-1) 4c x 2.5 sq mm Cu
Laying of one number of PVC insulated or PVC sheathed/ XLPE power cable of 1.1kV grade of following size direct in ground including excavation and refilling the trench etc. as required, but excluding sand cushioning and protective covering. up to 35 sq mm
Fixing a ceiling / Wall mounting fan of all capacities and all types to the existing 'S'' hook with fan regulator to the existing board together with supplying and fixing 5 A. ceiling rose,necessary length of 23 / 0.0076 inch PVC insulated twin twisted copper wire and wiring.
Supplying of .....feet -PVC Batten with integrated LED tube .... W with high quality diffuser with Life of 25000 burning hours & 70% lumen maintenance with CRI > 80. Power Input: 220-240V@ 50/60Hz & Power factor >0.9 along with CE approved. 2 years Warranty against any manufacturing defect working under standard electrical condition. LED light fitting 1 x 4' - 40 W Note: Equivalent to Model No: StarBright - PWide40W of philips Make: Philips, Crompton, Havells, Bajaj, Wipro
Supply of round/square recess/surface mounted rolling type LED Down light with ...... W GU 10 LED Lamp Rib Fabricated from diecast aluminium with white powder coated prewired to mains connector & has swivelling unit of aluminium die cast eye ball & LED Lamp position retained by circular wire spring, with Life of 25000 burning hours & 70% lumen maintenance with CRI > 80. Power Input: 220-240V @50/60Hz & Power factor >0.9 along with CE approved. 2years Warranty against any manufacturing defect working under standard electrical condition LED square or round down light 15-18W Make: Philips, Bajaj, Crompton
Supplying and fixing of LED bulk head of 10W with IP65 protection and IK08 impact resistance suitable for surface and wall mounting applications. Make: Philips, Crompton
Supplying of .....feet -PVC Batten with integrated LED tube .... W with high quality diffuser with Life of 25000 burning hours & 70% lumen maintenance with CRI > 80. Power Input: 220-240V@ 50/60Hz & Power factor >0.9 along with CE approved. 2 years Warranty against any manufacturing defect working under standard electrical condition. LED light fitting 1 x 4' - 20/22 W
Fixing all types and all capacities of fluorescent / false ceiling / spot light / CFL / LED fittings indoor on the wall / ceiling / rafters / girders using 23/0.0076” twin twisted PVC insulated wires, required Nos of round blocks and clamps. On wall / ceiling / Rafter / Girders
Supplying, installation, Testing & Commissioning of of following capacity at full load (Unity Power Factor) at operating temperature 0 to 40 deg C, Relative humidity 0 to 95%, Online double conversion true sine wave Uninterrupted hot swappable (allow for the replacement or addition of battery modules without shutting down the entire system) modular Power Supply (UPS) system with N+1 modules (N denotes total number of moduels requird for rated capacity). The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch alongwith provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. UPS shall have inbuilt phase sequence correction. The UPS systems offered are to be of the latest technology with Digital Control Microprocessor based for reliable operation using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier & inverter (3 Level) with PWM (Pulse Width Modulation). The quality of design, manufacturing and inspection process should confirm to the relevant International standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >96% while operating on battery mode and delivering quality power to the 100% non-linear loads. Current total harmonic effect(ITHD) on the input grid shall be < 5% at 50 %load. (The required LC (inductor (L) and a capacitor (C)) filters shall be included in UPS cost), extreme power factor kit to be included to limit the input power factor (PF) to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ), however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC : 3Phase 400V +/-20%, 50 Hz +/-5 Hz, AC Output voltage: 3Phase 415 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins, Sine wave output. Non condensing, noise level less than 60db at 1 meter distance, protections: KINLDY REFER TENDER DOCUMENT for full Description of Item Input Under voltage over voltage, abnormal out voltage, battery over charging, output over current, short circuit protection, battery deep discharge protection, 10KV surge. UPS must comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI)-type UPS. Communication RS232/RS485/SNMP port open protocol for BMS integration, all hardware & software for iOT Communication as per approved by Engineering in charge. Required battery racks and interconnecting copper conductor cables of suitable size and connectors and all required accoseries are inclusive of the cost). This system must provide a means for logging and alarming of all monitored points plus email notification. Forced air-cooling with integral inbuilt fans with redundancy (if one fan fail UPS should be able to handle at least 80% of the load, Noise Level 65 DB at 1 meter distance. The system shall be in compliance IEC 62040- 1,2 & 3, IS: 16242 and CPWD Specification. Display Panel (minimum) (In-build 5 inch or more LC Display / LED ) to display : a) Input: Voltage, current, Frequency. b) Bypass: Voltage, Frequency. c) Output: Voltage, frequency, Current. d) Battery: Voltage, Capacity. e) Load: KVA, KW, Percentage. f)Temperature: STS, Inverter, PFC. g) Event Logging & Statistical Data (On LCD/LED): UPS should capture and display up to 3000 events like: Over temperature / DC Bus Fail / Fan Fail / Fuse Fail / Overload / Short-circuit / Device Fail / Inverter Fail / Rectifier Fail / Bypass Fail, etc. h) Statistical Data: No. of power failures / Transfers to Bypass / Total Running time, etc. i) Mains Mode of Operation /Battery Mode of Operation / Bypass feeding the load / UPS Fault /Battery charging and discharging, overload, battery voltage and battery capacity. j) Audible Alarms : Mains Failure, Battery Low Alarm, UPS Overload, Fault, Shutdown, Input Over, Under Voltage, Output Over, Under Voltage, Battery Over, Under Voltage, Over Load and short circuit, Over Temperature. The UPS should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location etc. The UPS should be with isolation transformer. 10KVA (Each Power module shall be < 10 KVA)
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray with cover (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. 150 mm width X 50 mm depth X 1.6 mm thickness
Supply, installation, testing and commissioning of air shower of following specification. The cabin made up of jointless GI sheet of thicness 2mm powder coated both inner and outer side which shall be anti microbuial properties(MOC: GI Powder Caoted Innner & Outer). with Primary filtration (10 Micron), Efficiency – 90%, Grade - EU-4, filter Media - HDPE Washable / cleanable , Non-Woven Synthetic Media Final Filtration (0.3 Micron), Efficiency – 99.997%,Grade - H-13 Media - Micro Glass Fiber Paper, SS 304 Jet Nozels. Motor Blower Assembly, Pressure Differential Gauge Provided to Check Pressure Differential Across HEPA Filter, Electricals , Standard Features, Electromagnetic Interlocking System Connected with Door opening, Buzzer output for door is kept open more than specified time, LED / CFL light will get ON if any door opened, Floor with SS-304.Work area size: 900 (L) x900(D) x1900 (H) mm --for ManEntry
Supplying wall mounting fan suitable to operate at single-phase 230v AC. supply. 400 mm Sweep
Fabricating supplying and mounting MS box made out 14 SWG suitablefor floor /wall mounting, fully weather proof with provision for better heat dissipation, provided with hinged front cover, equipped with tamper proof locking arrangements, with suitable size clamps with necessary cable entry pipe with gland and box should be finished with 7 tanks treatment with powder coated paint and finally finished with approved colour etc., complete.
Supply of LT Brass Cable Gland (for 4CX2.5 Sq mm Cu cable glanding and termination) 25MM
Supply and fixing of DIN RAIL as required -35mm Wide 7.5mm Height
Supply and installation of Loop in -Loop out boxes. Cable Junction Boxes IP 66/67//69 “weather proof”, for outdoor installation (with knockouts for cable entry with terminals)
Supplying and fixing of DP sheet steel enclosure on surface/recess along with 32 A, 240V C curve DP MCB complete with connections, testing and commissioning etc. as required
Supplying of .. TR Invertor type split Air conditioners suitable for operation on A/C supply single phase 50Hz 230V with hermetically sealed inverter compressor with air cooled condenser, latest R410A/R-32 refrigerant fan motor,start & run capacitors, relay & overload protector internal unit, with one indoor & one outdoor unit The condenser unit will be placed outside the room avoid noise including standard length of suitable size copper tubing covered with nitrile rubber insulation tube. suitable capacity 3 core sheathed/ PVC copper cable and a battery operated wireless remote unit 5 star- 1 Ton capacity
Installation charges for split type air conditioner with allied works for one indoor and one out door unit is to be mounted on suitable Angle Iron support upto 3.0 Ton split/cassette type A/C
Supplying and installation of insulated refrigerant copper tubing of 5/8" and 3/8"with polythene foam insulation 3 core 80 stand copper wiring between indoor and outdoor unit Leak testing oil and gas charging for additional piping length of tube. Split
Supply erection, testing, commissioning of Cassette type split Air conditioners suitable for operation on single/three phase AC supply, hermetically sealed compressor with air cooled condenser motor capacitor start, capacitors run relay and over load protection, one ceiling mounted indoor unit and one outdoor condenser unit including standard accessories covered with insulation tube including battery operated cordless unit 2 TR Cassette 1 Ph
stage.html
html • 0.03 MB
technical_941023.pdf
techsummary_941023.pdf
fin_bid_open.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.39 MB
TDICMR.pdf
Tender Documents • 2.24 MB
BOQ_941023.xls
BOQ • 0.51 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .