S.No. DESCRIPTION AMOUNT IN Rs. DSR AMOUNT IN Rs. NS
B ELECTRICAL WORKS 889681.00 520825.00
D SANITARY INSTALLATION 116442.30 24313.00
E ACCESS CONTROL, CCTV, FIRE FIGHTING SYSTEM 165750.00 1391695.00
G GRAND TOTAL 9088765.70
G GRAND TOTAL 9088765.70
Digitally signed by AMIT
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
Earth work in excavation by mechanical means (Hydraulic excavator) I manual means in foundation trenches or
drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift up
to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding
20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.
Supplying and filling in plinth with Jamuna sand under floors including, watering, ramming consolidating and
dressing complete.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering -
All work up to plinth level :
4.1.3 1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) Cum. 3.00 7365.15 22095.45
4.1.8 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) Cum. 12.00 6326.05 75912.60
1:5:10 (1 cement : 5 fine sand derived from natural sources : 10 graded stone aggregate 40 mm nominal size derived
from natural sources)
Providing and laying damp-proof course 50mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III)
derived from natural sources : 4 graded stone aggregate 20mm nominal size derived from natural sources).
Providing & applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7kg per
7 4.13 square metre on damp proof course after cleaning the surface with brushes and finally with apiece of cloth lightly Sqm. 22.00 113.85 2504.70
soaked in kerosene oil.
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from
natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75mm thick bed
of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including
necessary excavation, levelling & dressing & finishing the top smooth.
9 5.9 Centering and shuttering including strutting, propping etc. and removal of form for
5.9.1 Foundations, footings, bases of columns, etc. for mass concrete Sqm. 51.40 307.95 15828.63
5.9.3 Suspended floors, roofs, landings, balconies and access platform Sqm. 177.40 766.55 135985.97
5.9.5 Lintels, beams, plinth beams, girders, bressumers and cantilevers Sqm. 199.26 608.35 121217.33
5.9.6 Columns, Pillars, Piers, Abutments, Posts and Struts Sqm. 87.00 804.25 69969.75
Providing, hoisting and fixing above plinth level up to floor five level precast reinforced cement concrete in lintels,
beams and bressumers, including setting in cement mortar 1:3 (1 cement : 3 coarse sand), cost of required centering
and shuttering but , excluding the cost of reinforcement, with 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived
from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources)
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all
complete above plinth level.
5.22A.6 Thermo-Mechanically Treated bars of grade Fe-500D or more. Kg 7856.00 89.65 704290.40
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement
concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana /
Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate /
retard setting of concrete, to improve durability and workability without impairing strength; including pumping of
Digitally signed by AMIT
concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and
reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. AMIT SINGH
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In
case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor
shall have discretion to either re-design the mix or bear the cost of extra cement.
5.33.1 All works upto plinth level
5.33.1.1 Concrete of M25 grade with minimum cement content of 330 kg /cum Cum. 23.00 7997.30 183937.90
5.33.2 All works above plinth level upto floor V level
5.33.2.1 Concrete of M25 grade with minimum cement content of 330 kg /cum Cum. 51.00 10080.15 514087.65
Add/ deduct for using extra/ less cement in the items of design mix over and above the specified cement content
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in :
Cement mortar 1:4 (1 cement : 4 coarse sand)
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above
plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:4 (1 cement : 4 coarse sand)
Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure
16 6.13 above plinth level and at all level.
6.13.2 Cement mortar 1:4 (1 cement :4 coarse sand) Sqm. 8.23 1018.05 8373.46
Extra for providing and placing in position 2 Nos. 6mm dia. M.S. bars at every third course of half brick masonry.
Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for
kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour
18 8.2 and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white
cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges
to give high gloss finish etc. complete at all levels.
8.2.2.1 Granite stone slab colour black, Cherry/Ruby red : Area of slab upto 0.50 sqm Sqm. 10.00 4679.35 46793.50
Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to
give high gloss finish etc. complete as per design approved by Engineer-in-Charge. Granite work
Designing, fabricating, testing, installing and fixing in position Curtain Wall with Aluminium Composite Panel
Cladding, with open grooves for linear as well as curvilinear portions of the building , for all heights and all levels etc.
(a) Structural analysis & design and preparation of shop drawings for pressure equalisation or rain screen principle as
required, proper drainage of water to make it watertight including checking of all the structural and functional
(b) Providing, fabricating and supplying and fixing panels of aluminium composite panel cladding in pan shape in
metalic colour of approved shades made out of 4mm thick aluminium composite panel material consisting of 3mm
thick FR grade mineral core sandwiched between two Aluminium sheets (each 0.5mm thick). The aluminium
composite panel cladding sheet shall be coil coated, with Kynar 500 based PVDF / Lumiflon based fluoropolymer
resin coating of approved colour and shade on face # 1 and polymer (Service) coating on face # 2 as specified using
stainless steel screws, nuts, bolts, washers, cleats, weather silicone sealant, backer rods etc.
Digitally signed by AMIT
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
(c) The fastening brackets of Aluminium alloy 6005 T5 / MS with Hot Dip Galvanised with serrations and serrated
washers to arrest the wind load movement, fasteners, SS 316 Pins and anchor bolts of approved make in SS 316,
Nylon separators to prevent bi-metallic contacts all complete required to perform as per specification and drawing
The item includes cost of all material & labour component, the cost of all mock ups at site, cost of all samples of the
individual components for testing in an approved laboratory, field tests on the assembled working curtain wall with
aluminium composite panel cladding, cleaning and protection of the curtain wall with aluminium composite panel
cladding till the handing over of the building for occupation. Base frame work for ACP cladding is payable under the
relevant aluminium item.s The Contractor shall provide curtain wall with aluminium composite panel cladding,
having all the performance characteristics all complete , as per the Architectural drawings, as per item
descriptiincluding fixing fffffffffffffffffffffffffffffffffffffffffffffffff
Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed
21 9.1 in position with hold fast lugs or with dash fasteners of required dia & length ( hold fast lugs or dash fastener shall be
paid for separately).
9.1.1 Second class teak wood Cum. 0.14625 131576.95 19243.13
Providing and fixing lSl marked flush door shutters conforming to IS: 2202 (Part I) non-decorative type, core of block
22 9.21 board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical
grains or cross bands and face veneers on both faces of shutters:
9.21.1 35mm thick including lSl marked Stainless Steel butt hinges with necessary screws. Sqm. 10.00 2015.75 20157.50
Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush door
shutters (over all area of door shutter to be measured).
24 9.78 Providing and fixing bright finished brass night latch of approved quality including necessary screws etc. complete. Each 3 1004.80 3014.40
25 9.74 Providing and fixing bright finished brass tower bolts (barrel type) with necessary screws etc. complete :
26 9.82 Providing and fixing bright finished brass hanging type floor door stopper with necessary screws, etc. complete. Each 3 109.60 328.80
Providing and fixing aluminium die cast body tubular type universal hydraulic door closer (having brand logo with ISI,
27 9.83 IS : 3564, embossed on the body, door weight upto 35 kg and door width upto 700 mm), with necessary accessories Each 3 1025.65 3076.95
and screws etc. complete.
Providing and fixing bright finished brass 100 mm mortice latch and lock, ISI marked, with six levers and a pair of
28 9.103 anodised (anodic coating not less than grade AC 10 as per IS : 1868) aluminium lever handles of approved quality Each 2 739.80 1479.60
with necessary screws etc. complete.
Digitally signed by AMIT
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
Providing and fixing partition upto ceiling height consisting of G.I. frame and required board, including providing and
fixing of frame work made of special section power pressed/ roll form G.I. sheet with zinc coating of
120gms/sqm(both side inclusive), consisting of floor and ceiling channel 50mm wide having equal flanges of 32 mm
and 0.50 mm thick, fixed to the floor and ceiling at the spacing of 610 mm centre to centre with dash fastener of 12.5
mm dia meter 50 mm length or suitable anchor fastener or metal screws with nylon plugs and the studs 48 mm wide
having one flange of 34 mm and other flange 36 mm and 0.50 mm thick fixed vertically within flanges of floor and
ceiling channel and placed at a spacing of 610 mm centre to centre by 6 mm dia bolts and nuts, including fixing of
29 9.105 studs along both ends of partition fixed flush to wall with suitable anchor fastener or metal screws with nylon plugs
at spacing of 450 mm centre to centre, and fixing of boards to both side of frame work by 25 mm long dry wall
scincluding fixing oor and ceiling channels at the spacing of 300 mm centre to centre. The boards are to be fixed to
the frame work with joints staggered to avoid through cracks, M.S. fixing channel of 99 mm width (0.9 mm thick
having two flanges of 9.5mm each) to be provided at the horizontal joints of two boards, fixed to the studs using
metal to metal flat head screws, including jointing and finishing to a flush finish with recommended jointing
compound, jointing tape, angle beads at corners (25 mm x 25 mm x 0.5 mm), joint finisher and two coats of primer
suitable for board as per manufacture's specification and direction of engineer in charge all complete
75 mm overall thickness partition with 12.5 mm thick double skin fire rated Glass Reinforced Gypsum (GRG) plaster
board conforming to IS: 2095: part 3 (Board with BIS certification marks)
Providing & Fixing decorative high pressure laminated sheet of plain / wood grain in gloss / matt/ suede finish with
30 9.127 high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S,
including cost of adhesive of approved quality.
Providing and fixing frame work for partitions/ wall lining etc. made of 50x50x1.6 mm hollow MS tube, placed along
the walls, ceiling and floor in a grid pattern with spacing @ 60 cm centre to centre both ways (vertically &
horizontally) or at required spacing near opening, with necessary welding at junctions and fixing the frame to wall/
ceiling/ floors with steel dash fasteners of 8 mm dia, 75 mm long bolt, including making provision for opening for
doors, windows, electrical conduits, switch boards etc., including providing with two coats of approved steel primer
etc. complete, all as per direction of Engineer-in-charge.
Providing and laying Vitrified tiles in different sizes (thickness to be specified by the manufacturer), with water
absorption less than 0.08% and conforming to IS: 15622, of approved brand & manufacturer, in all colours and shade,
32 11.47 in skirting, riser of steps, laid with cement based high polymer modified quick set tile adhesive (water based)
conforming to IS: 15477, in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be
made separately).
Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated
33 11.48 filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing
complete as per direction of Engineer-in-charge.
Providing and laying Vitrified tiles in floor with different sizes (thickness to be specified by the manufacturer), with
water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and
shade, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS : 15477,
in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately).
Digitally signed by AMIT
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear
portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20mm
35 11.56 (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing
with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all
complete as specified and as directed by the Engineer-in-Charge.
11.56.1 Polished Granite stone slab colour of Black, Cherry/Ruby Red or equivalent Sqm. 5.00 3908.80 19544.00
Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2
coarse sand : 4 stone aggregate 10mm and down gauge) including finishing with cement mortar 1:3 (1 cement : 3 fine
sand) as per standard design : ) including finishing with cement mortar 1:3 (1 cement :3 fine sand ) as per standard
12.21.1 In 75x75mm deep chase Metre 75.00 260.20 19515.00
Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand :
4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet lmxlmx400micron, finished with 12mm cement
plaster 1:3 (1 cement: 3 coarse sand) and a coat of neat cement rounding the edge sand making and finishing the
outlet complete.
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections,
power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277
and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm
centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts,
other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required
size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of
1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of
26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I.
intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction,
including fixing
perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed
to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval,
including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5
x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board
with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto
150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and
also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter
channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but
excluding the cost of painting with :
12.45.3 12.5 mm thick tapered edge gypsum moisture resistant board Sqm. 68.00 1300.50 88434.00
39 13.4 12 mm cement plaster of mix:
40 13.5 15 mm cement plaster on rough side of single or half brick wall of mix:
41 13.45 Finishing walls with textured exterior paint of required shade :
New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied
@ 2.20kg/10 sqm
Digitally signed by AMIT
42 13.5 Applying priming coat:
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel galvanised iron/ steel
43 13.62 Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :
Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer,
over the plastered wall surface to prepare the surface even and smooth complete.
Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound )
45 13.83 content less than 50 grams/ litre of approved brand and manufacture, including applying additional coats wherever
required to achieve even shade and colour.
Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic
Compound ) content.
13.85.3 With water thinnable cement primer on wall surface having VOC content less than 50 grams/litre. Sqm. 359.00 64.45 23137.55
Polishing in high gloss/matt finish melamine clear polish on wood work in required color/wooden shade texture with
following process in the sequence as detailed below:
1 The surface to be polished is rubbed with sand paper 80/120 no. and then with sand paper of 160/180 nos.
Applying two coats of sealer with spray gun and allowing sufficient drying time for 1st coat and 2nd coat is allowed to
dry for 8 to 12 hrs.
On drying of sealer coat, wet rubbing with emery cloth of finer grading with ample water to remove excess sealer
layer and make the surface further smooth after this wet rubbing, then surface is applied with special grade
melamine fillers to fill all the small and big holes/grooves etc. Filler coat to be allowed to dry for 4 to 6 hrs on which
again a light wet rubbing is done this surface is further allowed to dry for 12 hrs.
On this, 1st coat of melamine polish is applied with spray gun using melamine clear polish and melamine thinner in
required proportion. This 1st coat is allowed to dry for 24 hrs then this dry surface is again fine wet rubbed smooth,
4 which is further allowed to dry for 12 hrs. The final melamine polish is applied with compressor pressure spray gun Sqm. 8.32 1156.55 9622.50
using melamine clear polish and melamine thinner mixed in required proportion complete as per direction of
Engineer-in-Charge. (Final coat to be done in 1 or 2 layers without gap of time.)
Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead
as per direction of Engineer - in - charge
15.2.1 Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix) Cum. 2.00 2007.10 4014.20
Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of
unserviceable material within 50 metres lead as per direction of Engineer - in- charge.
Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of
unserviceable material within 50 metres lead as per direction of Engineer-in-charge.
15.7.4 In cement mortar Cum. 5.00 1698.45 8492.25
Dismantling doors, windows and clerestory windows (glass, steel or wood) shutter including chowkhats, architrave,
holdfasts etc. complete and stacking within 50 metres lead :
15.12.1 Of area 3 sq. metres and below Each 4 302.70 1210.80
15.12.2 Of area beyond 3 sq. Metres Each 1 414.55 414.55
Dismantling steel work in built up sections in angles, tees, flats and channels including all gusset plates, bolts, nuts,
cutting rivets, welding etc. including dismembering and stacking within 50 metres lead.
Digitally signed by AMIT
Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead.
For thickness of tiles 10 mm to 25 mm Sqm.
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
Dismantling stone slab flooring laid in cement mortar including stacking of serviceable material and disposal of
unserviceable material within 50 metres lead.
Dismantling aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of
unserviceable material and stacking of serviceable material with in 50 meters lead as directed by Engineer-in-charge.
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard
tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285,
fixing with dash fasteners ofrequired dia and size, including necessary filling up the gaps atjunctions, i.e. at top,
55 21.1 bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free,
straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for
glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of
Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) :
21.1.1 For fixed portion
Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating
of grade AC 15)
Filling the gap in between aluminium frame & adjacent RCC /Brick/ stone work by providing weather silicon sealant
over backer rod of approved quality as per architectural drawigns and direction of Engineer in charge complete.
21.8.1 Up to 5mm depth and 5mm width Metre 50.00 85.25 4262.50
Providing and laying water proofing treatment on roofs of slabs by applying cement slurry mixed with water
proofing cement compound consisting of applying:
after surface preparation, first layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement
compound @ 0.253 kg/sqm.
laying second layer of Fibre glass cloth when the first layer is still green. Overlaps of joints of fibre cloth should not be
less than 10 cm.
third layer of 1.5 mm thickness consisting of slurry of cement @ 1.289 kg/sqm mixed with water proofing cement
compound @ 0.670 kg/sqm and coarse sand @ 1.289 kg/sqm. This will be allowed to air cure for 4 hours followed by
water curing for 48 hours. The entire treatment will be taken upto 30 cm on parapet wall and tucked into groove in
parapet all around.
(d) fourth and final layer of brick tiling with cement mortar (which will be paid for separately.
(For the purpose of measurement the entire treated surface will be measured.) Sqm. 203.414934 585.55 119109.61
Providing and fixing mineral fibre false ceiling tiles at all heights of size 595X595mm of approved texture, design and
pattern. The tiles should have Humidity Resistance (RH) of 99%, Light Reflectance > 85%, Thermal Conductivity k =
0.052 - 0.057 w/m K, Fire Performance as per (BS 476 pt - 6 &7)in true horizontal level suspended on interlocking T-
Grid of hot dipped all round galvanized iron section of 0.33 mm thick (galvanized @120 gsm) comprising of main T
58 26.27 runners of 15x32 mm of length 3000 mm, cross T of size 15x32mm of length 1200 mm and secondary intermediate
cross T of size 15x32 mm of length 600 mm to form grid module of size 600x600 mm suspended from ceiling using
galvanized mild steel item (galvanised@80gsm) 50 mm long 8mm outer diameter M-6 dash fasteners, 6 mm diameter
fully threaded hanger rod up to 1000 mm length and L-shape level adjuster of size 85x25x2 mm, spaced at 1200 mm
centre to centre along main ‘T’.
The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size24x24X3000 mm
made of 0.40 mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450 mm centre to centre & 40
mm long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall
be pre-painted with polyester baked paint, for all heights. The work shall be carried out as per specifications,
drawings and as per directions of the engineer-incharge.
Digitally signed by AMIT
26.27.2 With 20 mm thick beveled tegular mineral fibre false ceiling tile (NRC 0.7) Sqm.
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
Provinding and fixing 8mm thick Heat Reflective Toughened Tinted Glass in aluminium door, window, ventilator
59 NS-1 shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and Sqm. 31.302 2777.00 86925.65
the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):
Providing and fixing in position glazed partition with 12mm thick clear toughened glass fixed with top & bottom in
Aluminium 'U' channel to existing RCC slab/floor/wall. The vertical joint of glass shall be polished and butt joint,
filled with clear silicon sealant including required other hardwares. The vendor should ensure stability of partition
complete in all respects as shown in the detailed drawing or as directed by the Enigineer-in-charge. The Cost of
wooden frame/ M.S. framefrom ceiling to slab shall be paid in basic item. (Measurement of partition shall be taken
up to clear ceiling height)
Providing and fixing in position 3M make film of approved colour, design & texture over glass wherever required
61 NS-3 complete in all respects as shown in the deatiled drawing and as directed by Engineer-in-charge. ( Rate of film from Sqm. 22 2554.00 56188.00
manufacturer is up to Rs 150/- per sqft. + GST). The film should be fixed by 3M company representative only.
Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture,
including providing and fixing top & bottom pivot & double action hydraulic floor spring type fixing arrangement,
Door handle, lock and stopper etc and making necessary holes etc. for fixing required door fittings, all complete as
per direction of Engineer-incharge.
Designing , providing and fixing of structural glazed curtain wall system using speclally designed aluminium extruded
sections duly anodized in approved coloured and said with mullions fixed to RCC beams/ columns through
adequately designed epoxy coated M.S brackets, insert plates etc including providing and fixing 6mm thick heat
reflective to match Existing tinted glass at site (of thickness not less than 6 mm designed thickness to be indicated
by tenderer at he time of tendering itself) of approved make including approved silicon sealant gaskets etc. complete
to make the structural glazing air tight and water tight as per IS/BS standards including scaffolding etc.complete as
per architectural drawings and specifications as directed by the Engineer-in-charge. (Shop drawings to be prepared
by the tenderer & take approval from Engineer-in-charge.
Removing and Refixing of existing structural glazed curtain wall available at site including required aluminium
extruded sections duly anodized in existing coloure, epoxy coated M.S brackets, insert plates, silicon sealan, gaskets
etc. complete to make the structural glazing air tight and water tight as per IS/BS standards including scaffolding
etc.complete as per architectural drawings and as directed by the Engineer-in-charge.
TOTAL A CIVIL WORKS 4279878.81 902912.79
B DSR 2018 ELECTRICAL WORKS
WIRING IN STEEL CONDUIT
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper
1 1.30 conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box
and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for twin control light point with 1.5 sqmm FRLS PVC insulated copper conductor single core cable in surface/
2 1.40 recessed steel conduits, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sqmm Pts 5 1290.00 6450.00
FRLS PVC insulated copper conductor single core cable etc as required.
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ Digitally signed by AMIT
3 1.50 recessed steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop Meter
earthing as required.
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper
conductor, single core cable in surface/ recessed steel conduit as required.
1.7.1 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire Meter 125 208.00 26000.00
1.7.2 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire Meter 200 229.00 45800.00
1.7.3 2 X 4 sq. mm + 1 X 4 sq. mm earth wire Meter 127 263.00 33401.00
1.7.4 2 X 6 sq. mm + 1 X 6 sq. mm earth wire Meter 76 356.00 27056.00
1.7.10 4X 10 sq. mm + 2 X 6 sq. mm earth wire Meter 30 670.00 20100.00
1.7.11 4 X 16 sq. mm + 2 X 6 sq. mm earth wire Meter 30 946.00 28380.00
Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored
telephone cable in the existing surface/ recessed steel/ PVC conduit as required.
Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine
tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required.
Supplying and fixing of following sizes of steel conduit alongwith the accessories in surface/recess including painting
in case of surface conduit or cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including
connections but excluding modular plate etc. as required.
1.24.4 3 pin 5/6 A socket outlet Each 5 111.00 555.00
1.24.5 6 pin 15/16 A socket outlet Each 5 175.00 875.00
1.24.6 Telephone socket outlet. Each 15 119.00 1785.00
1.24.7 TV antenna socket outlet. Each 2 119.00 238.00
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in
recess etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess including
11 1.31 providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connections, etc. as Each 15 401.00 6015.00
required.(for ligt plugs to be used in no residental building).
Digitally signed by AMIT
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess including
providing and fixing 6 pin 5/6 &15/16 amps modular socket outlet and 15/16 amps modular switch, connections, etc. Each AMIT
as required. Date: 2022.09.10
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
13 1.38 Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. Each 2 92.00 184.00
Providing and fixing plain 16/0.20mm (0.50sqmm) twin flat flexible, FRLS PVC insulated, copper conductor cable, in
PVC sleeve of suitable size on the floor/ wall, or side of the table/ door etc. as required.
Providing and fixing plain 16/0.20mm (0.50sqmm) twin circular flexible FRLS PVC insulated, PVC sheathed copper
conductor cable direct on the wall with PVC clips etc. as required.
Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types,
16 1.41 complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS Each 48 168.00 8064.00
PVC insulated, copper conductor, single core cable and earthing etc. as required.
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing,
commissioning etc. as required.
1.50.1 Upto 450 mm sweep Each 2 363.00 726.00
18 1.51 Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes Each 2 168.00 336.00
19 1.53 Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent
switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel
conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as
Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including
21 1.57 providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting Each 2 639.00 1278.00
etc. as required.
Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V "C" curve DP MCB
complete with connections, testing and commissioning etc. as required.
Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32 A 415 V "C" curve TP MCB
complete with connections, testing and commissioning etc. as required.
Supplying and Fixing 20 A 240 V, SPN industrial type socket outlet, with 2 pole and earth, metal enclosed plug top
24 2.18 along with 20 amps "C" curve , SP, MCB, in sheet steel enclosure, on surface or in recess with chained metal cover for Pts. 2 1232.00 2464.00
the socket outlet and complete with connection, testing and commissioning etc. as required.
Supplying and fixing 20 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top
25 2.19 alongwith 20 A "C" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the Each 2 1690.00 3380.00
socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and Fixing 30 amps, 415 volts, TPN industrial type socket outlet, with 4 pole and earth, metal enclosed plug
26 2.20 top along with 30 amps "C" curve, TP MCB, in sheet steel enclosure on surface or in recess with chained metal cover Pts 2 3048.00 6096.00
for the socket outlet and complete with connection, testing and commissioning etc. as required.
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/
27 2.30 recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted
including earthing etc. as required. (But without CB/RCCB/Isolator)
2.3.1 6 way , Double door Each 1 1661.00 1661.00
2.3.2 8 way , Double door Each 1 1760.00 1760.00
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415
28 2.40 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, Digitally signed by AMIT
powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). AMIT SINGH
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive
29 2.10 load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as
2.10.2 Single pole and neutral. Each 1 544.00 544.00
2.10.3 Double pole. Each 5 556.00 2780.00
2.10.4 Triple pole. Each 1 826.00 826.00
2.10.5 Triple pole and neutral. Each 10 1092.00 10920.00
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker
30 2.14 (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and
commissioning etc. as required.
Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V "C" curve DP MCB
complete with connections, testing and commissioning etc. as required.
Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32 A 415 V "C" curve TP MCB
complete with connections, testing and commissioning etc. as required.
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top
33 2.18 alongwith 20 A "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the Each 1 1232.00 1232.00
socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing 20 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top
34 2.19 alongwith 20 A "C" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the Each 1 1690.00 1690.00
socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top
35 2.20 alongwith 30 A "C" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the Each 1 3048.00 3048.00
socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation
36 4.10 not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S.
suspenders including bolts & nuts, painting suspenders etc as required.
4.1.1 100 mm width X 50 mm depth X 1.6 mm thickness. Meter 30 476.00 14280.00
4.1.2 150 mm width X 50 mm depth X 1.6 mm thickness. Meter 30 531.00 15930.00
Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete
with mounting base complete as required.
Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED,
metallic cover complete with all connections etc as required.
Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as
40 17.2.7 Supplying, installation, testing & commissioning of fault isolator complete with base as required. Each 2 3257.00 6514.00
Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum
fixed tempreature thermistor complete with base as required. Digitally signed by AMIT
42 17.2.10 Supplying, installation, testing & commissioning of addressable fire control module complete as required. Each AMIT
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
43 17.2.11 Supplying, installation, testing & commissioning of addressable phone control module complete as required. Each 1 3255.00 3255.00
44 17.3.3 Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required. Each 10 1780.00 17800.00
Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor
having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following
46 7.4 size direct in ground in the same trench in one tier horizontal formation including excavation and refilling the trench
etc as required, but excluding sand cushioning and protective covering
7.4.4 Above 185 sq. mm and upto 400 sq. mm RM 150 178.00 26700.00
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC
47 9.1 insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV
grade as required.
9.1.30 3.5 C x 300 sq.mm. Al Ar. XLPE cable Set. 2 936.00 1872.00
Supply, Unloading, Receiving, Storing, Assembling, Fixing, Termination, Testing and Commissioning of the following
Type LED Lighting Fixtures with all fitting, driver, housing & reflector, wiring complete with providing of all necessary
hardware’s like raw plugs, hangers, support plates as required for fixing etc. Complete in all respect.
All toll & tackles, Hardware, required for successful installation, testing & commissioning shall be in scope.
Recessed type LED 2x2 luminaire with CRCA housing suitable with fully diffused prismatic diffuser for general lighting
in office areas. The luminaire should have a color consistency SDCM < 5, CRI > 80 and CCT of both 4000K. The
luminaire shall be compliant with IP20 and IK02 classification. Luminaire shall be designed to emit at least 4000
nominal lumens and an outstanding backlit solution efficacy of at least 124 lumen/watt and maximum system
wattage of 32W. The luminaire shall be designed so as to ensure lumen depreciation of up to 30% over 50k burning
hours @ design ambient temp 45 deg C. The electronic driver used shall have a power factor >0.95 and THD <10%
The fixture should comply with the parameters as per IS10322. Similar to RC380B LED42S-4000 G5 L60W60 PSU OD
IP20 Recessed LED Downlighter made of pressure die cast aluminum housing, Fixture should have minimum efficacy
at System level (Not Chip Level) >=110lumens/watt with Minimum system Lumens 2000 with maximum system
wattage of 18W. Life of fixture (Including Driver) : 50000 burning Hrs. @ L70B50 Lumen maintenance, CCT of 6500K
(SDCM<5), CRI >80, PF >0.95, working temp range - 0°C < Ta < 45°C, and operating Voltage Range of 130 - 320 VAC. it
should has a Minimum Internal Surge Protection of 2.5KV. Electronic Switchable ballast. The fixture design should
comply with EMC / EMI compliance along with BIS certification for LED Driver & Luminaire.Luminaire manufacture
shall provide LM79report from NABL accredited lab & LM80 report issued by LED manufacturer. BIS approved with R-
Code, Similar to DN296B LED20S PSU WH.
Supply of following sizes of 1.1kV grade XLPE insulated, PVC type ST-2 inner & outer sheath, FRLS, Aluminium / CU
conductor, Armoured / Unarmoured cables as per IS:7098 Part-I.
3.5 Cores. (FRLS Cable)
Digitally signed by AMIT
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
Design, fabrication, assembly, wiring and supply of front operated, dead front cubicle type compartmentalised as per
Form 3B, rear / front access free standing, dust and vermin proof (IP-42 Indoor and IP-55 Outdoor Type) main
switchboards suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system suitable for a symmetrical fault level of 50
kA at 415 volts, fabricated from 2 MM thick CRCA MS sheets with hinged, gasketted (metal based neoprene) and
53 MR-5 lockAble doors having structural reinforcement with suitable angle/channel/T/flat sections including 3 mm thick
gland plates on top and bottom and including lifting hooks and including Al earth strip of required size based fault
level of respective panel with 2 Nos earthing terminals and including powder coated paint finish of approved shade
over metal surface cleaned and treated with 11 tank process complete with interconnections etc as per
specifications, as required and as below.
(Note:The contactor may select the next higher fault rating of MCCB if it is not readily available, without any extra
cost, as the figure indicated within the bracket are required maximum fault level of the panel to with stand.)
All the Outdoor Type Panel / FP shall have double door and canopy arrangement on the top. The Feeder pillars shall
be compartmentalized construction conforming to IS specification.
54 MR-5.1 Sub-Distribution Board.
Location _ Ground Floor (IndoorType).
1 No.100 A TPN MCCB (25 kA) with thermal Magnetic release.
Incomer shall be equipped with.
1 Set of R,Y,B phase indicating and Trip lamps each with 3 Nos. 2A MCB.
MFM with 3 Nos. 100/5A CT's, CL -1 15 VA, 3 Nos. 2 A MCB.
1 Set- of ON/OFF/Trip/ Spring Charged & Trip circuit healthy indicating lamps.
Phase sequence relay as per SLD
1 - 24 volts DC shunt trip coil
4 Nos NO/NC contacts for remote opening & closing
Class / Type – II, as per IEC 61482-1-2, three phase AC Power line Surge Protection Device / Transient Voltage Surge
Suppressor as per specification, with inbuilt fuse.
1 No. reverse power relay.
Suitable size of Terminals to receive XLPE insulated Aluminium cables as per SLD.
Electrolytic high conductivity Aluminum three phase and neutral bus bar having color code heat shrinkAble PVC
sleeves with earthing rated at 125 amps having a maximum current density of 0.75 Amp per sq mm suitable to with
stand symmetrical fault level of 25 kA at 415 volts. The neutral bus bar is to be of 50% capacity.
2 Nos. 63 A TPN MCB (10 kA).
2 Nos. 40 A TPN MCB (10 kA).
1 No. 32 A TPN MCB (10 kA).
5.1 Supply of Sub-Distribution Board as described above. Set 1 150000.00 150000.00
TOTAL B ELECTRICAL WORKS 889681.00 520825.00
Digitally signed by AMIT
Variable Refrigerant Flow Air-conditioning System AMIT SINGH
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
DSR. No. Outdoor Units
Supply ,Installation,Testing & Commissioning of modular type Variable Refrigerant Flow/ Variable Refrigerant
Volume air cooled Outdoor units suitable for cooling and heating, having all hermetically sealed inverter type Scroll
Compressor(s) , minimum two compressors for above 14HP modules, microprocessor based Controller, top discharge
type condensing unit(s), with R410A Refrigerant,vibration isolators, with suitable foundation etc.complete as
required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature
without tripping. The unit shall be suitable to work on 400V+/-10%, 3Phase, 50HzAC power supply. The unit shall be
filled with first charge of the refrigerant andready for use as required. The COP at AHRI conditions shall not be less
than 3.1 and IEER not less than 6.5 .
Indoor Units - Cassette Units
Supply, installation, testing and commissioning of following minimum capacity 4-way flow VRV/VRF Cassette Type
Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fansection with low noise fan/
dynamically balanced blower,multi speed motor,coil section with DX Copper coil,electronic expansion valve,outer
56 cabinet, drain pump, grill, necessary supports,vibration isolation, cordless remote control etc., suitable for operation
on single phase 230V ± 10%,50Hz AC supply, complete, as required.The unit shall have automatic force shut down
provision incase offire on receiving signal from BMS System.Thecooling capacity of indoor unit will be at airinlet
conditions of 27 DegreeC D Band 19 Degree CWB temperature.
Copper Refrigerant Piping
Supply,Installation,testing and commissioning including vaccumiazation and Nitrogen testing of following nominal
sizes of soft/hard drawn copper refrigerant piping for VRV/VRF or Non VRV/VRF system, complete with fittings,with
57 suitable adjustable ring type hanger supports, jointing/brazing including accessories,insulated with XPLE Class-O
tubular insulation/withClass-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness
as given below for Suction and Liquid lines,all accessories as per specifications
NOTE:-1)The Copper Piping & Piping Circuit should be with Minimum Number of joints, which shall be attained by : (i)
Using One End Expanded Tubes (ii) Bending the tubes instead of using elbow joints wherever 90 degree bending is
required. (2)Piping should be routed at site in such a manner, that brazed joints in the refrigeration piping are kept to
a minimum. (3) The makes of tube fittings shall be same as that of tubes.(4) The thickness of fittings used shall be
same as that of the pipe.
5.1 6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation M 18.00 245.00 4410.00
5.2 9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation M 35.00 331.00 11585.00
5.3 12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation M 25.00 466.00 11650.00
5.4 15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation M 30.00 588.00 17640.00
5.5 19.0 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation M 10.00 707.00 7070.00
5.6 22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation M 10.00 865.00 8650.00
5.8 28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation M 12.00 1108.00 13296.00
DSR - 18.7 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,having thermal stability for hot & cold water supply,
including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This
58 Digitally signed by AMIT
includes jointing of pipes & fittings with one step PVCsolventcement and testing of joints complete as per direction
of Engineer in Charge.
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
18.7.3 25 MM Nominal Outerdia Pipes M 40.00 408.55 16342.00
18.7.4 32 MM Nominal Outerdia Pipes M 24.00 500.95 12022.80
Insulation material for Drain Pipe
Supplying, laying, fixing, testing and commissioning of following thickness closed cell elastrometric nitrile rubber of
class 'O' applied by suiatable adhesive, as per specifications and as required complete in all respect.
DSR Supply & Fixing of Cable end Termination of following sizes 1.1 kV grade XLPE insulated, PVC type ST-2 inner & outer
sheath, FRLS, Aluminium / CU conductor, Armoured/ Unarmoured cables as per IS:7098 Part-I including cost of tinned
copper, heavy duty crimpping lugs, double compression glands, insulation tape and all necessary material to
complete the termination.
7 Hot Dip Galvanised Cable Tray for Copper Piping & Cabling Works
Supply, fabrication and installation of Hot dip galvanised factory built perforated type double banded cable trays
complete with all bends, tees, elbows, reducers, supports & fixing arrangement etc. of various widths in single
tier/two tier/ three tier/ five tier fashion either on one side of the wall or on two sides of the wall or
ceiling/wall/floor. (All bends & tees shall be of factory built of same make as that of tray). Cable tray supports
are supposed to be included in the rate of the trays. Nothing extra to be paid for cable tray supports. Cable trays and
supports shall be as per specifications.
4.6.1 100 mm width X 50 mm depth X 1.6 mm thickness RMT 25 599.00 14,975.00
62 DSR Earthing Strip / Wires.
5.17 Providing and fixing 4.00 mm dia copper wire on surface or in RMT 50 128.00 6,400.00
recess for loop earthing as required.
63 Supply of Main Central Remote controller system with LCD panel suitable for above indoor units to operate,
monitor, on/off, temperature setting etc.
Electrical Panel for ODU
Supply, Installation, testing & commissioning of Indoor Type IP 42 Cubical type main MV panel board suitable for 3
phase, 415 volts, 50 Hz and of 25 KA rupturing capacity at 415 volts, fabricated from minimum 2 mm thick and doors
of 1.6 mm thick CRCA sheet powder coated through Ten tank process facility for prickling and degreasing complete
with mountings, interconnections, earthing etc including mechanical and Electrical Inter locking as required.
Note: The AC contractor shall provide fire shunt relay contact in his panel wherever necessary along with auto /
manual mode selector switch in the outgoing feeder to take fire input signal (Potential Free Contact).Cost shall be
included in the panel price quoted by him.
Potential free contact shall be provided with necessary modbus protocol compatible to BMS and energy
management system.
01 No. 63 AMP MCB TP + NL 25 KA incoming Micro inbuilt O/L, S/C, E/F
1 No. Digital VAF meter and CTs of rating 63/5A.
3 Nos.phase indicating lamps.
Main bus bar rated at 100 amps TPN, 36 KA with heat shrinkable sleeve and shall be of aluminium.
Digitally signed by AMIT
Outgoing: AMIT SINGH
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
01 No. 63 A TP MCCB-25KA Micro inbuilt O/L, S/C, E/F For VRF Outdoor Units
All outgoing feeder shall have following accessories.
02 Nos. ON/OFF indicating lights with protection switch.
1 No.125 A MCCB as spare Set 1.00 41708 41,708.00
Supply of XLPE Insulated Al / Cu conductor Ar. Cable.
65 Supply Receiving, loading & unloading at site, Laying, Fixing, Testing & Commissioning of following sizes of 1.1kV
grade XLPE insulated, PVC type ST-2 inner & outer sheath, FRLS, Aluminum / CU conductor, Armoured /
Unarmoured cables as per IS:7098 Part-I on existing cable trays / in existing hume pipes / PVC pipes / GI pipes / on
surface of slabs, walls or masonry / RCC trenches / ducts including cables ties, GI saddles, clamps and necessary
4 C x 10 sq.mm. Cu. Ar. XLPE cable RM 20.00 350 7,000.00
66 Supply,laying,testing and commissioning of following copper PVC insulated, sheathed flexible cable for indoor
unit/inline fans.Cabling between 6/16 amp Switch socket outlet and each of the indoor units (splits/ ductables / fans
/etc..) alongwith plug top at socket outlet side
Supply & Laying ,testing and commissioning of control cum transmission wiring of Copper conductor shielded cable
for looping between indoor & outdoor VRF system & to main Central remote controller system
68 Hot Dip Galvanised Cable Tray for Copper Piping & Cabling Works
Supply, fabrication and installation of Hot dip galvanised factory built perforated type double banded cable trays
complete with all bends, tees, elbows, reducers, supports & fixing arrangement etc. of various widths in single
tier/two tier/ three tier/ five tier fashion either on one side of the wall or on two sides of the wall or
ceiling/wall/floor. (All bends & tees shall be of factory built of same make as that of tray). Cable tray supports
are supposed to be included in the rate of the trays. Nothing extra to be paid for cable tray supports. Cable trays and
supports shall be as per specifications.
50 x 50mm x 50mm x 2mm thick RMT 10.00 180 1,800.00
TOTAL C HVAC WORK 640308.80 156959.00
D SANITARY INSTALLATION
Detail of sanitary fixtures are for information, however the final choice shall be by Architect/Owner and the same
shall be binding for execution if sanitary fixtures and accessories, CP-fittings are supplied by Owner, the contractor
shall supply all accessories required to install the fixture/fittings in a neat workman like manner.
No extra cost shall be paid for change in type of sanitary fixture or fittings if any extension piece is required for final Digitally signed by AMIT
connection the same shall be supplied and installed by the contractor. AMIT SINGH
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low
level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I. brackets, 40 mm flush bend, overflow
arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete,
including painting of fittings and brackets, cutting and making good the walls and floors wherever required :
17.3.1 W.C. pan with ISI marked white solid plastic seat and lid Each 2 6,941.30 13,882.60
Providing and fixing white vitreous china flat back half stall urinal of size 580x380x350 mm with white PVC automatic
flushing cistern, with fittings, standard size C.P. brass flush pipe, spreaders with unions and clamps (all in C.P. brass)
with waste fitting as per IS : 2556, C.I. trap with outlet grating and other couplings in C.P. brass, including painting of
fittings and cutting and making good the walls and floors wherever required :
17.5.1 Single half stall urinal with 5 litre P.V.C. automatic flushing cistern Each 1 10,128.30 10,128.30
Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard
71 17.7 pattern, including painting of fittings and brackets, cutting and making good the walls
wherever require:
17.7.1 White Vitreous China Wash basin size 630x450 mm with a pair of 15 mm C.P. brass pillar taps Each 1 3,392.85 3,392.85
White Vitreous China Angle back wash basin size 400 x
400 mm with single 15 mm C.P. brass pillar tap
72 17.35 Providing and fixing soil, waste and vent pipes :
17.35.1.2 Centrifugal cast (spun )iron socketed pipe as per IS: 3989 Mtr 35 1,077.40 37,709.00
Providing and fixing bend of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts
17.38.1.2 Sand cast iron S&S as per IS - 3989 Each 2 597.60 1,195.20
74 17.39 Providing and fixing plain bend of required degree.
17.39.1.2 100 mm dia sand cast iron S&S as per 3989. Each 5 439.75 2,198.75
Providing and fixing single equal plain junction of required degree with access door, insertion rubber washer 3 mm
75 17.43 thick, bolts and nuts complete.
17.43.1.2 Sand cast iron S&S as per IS - 3989 Each 1 731.40 731.40
76 17.50 Providing and fixing single equal plain invert branch of required degree
17.50.1.2 Sand cast iron S&S as per IS - 3989 Each 2 613.65 1,227.30
77 17.56 Providing and fixing terminal guard
17.56.1.2 Sand cast iron S&S as per IS - 3989 Each 2 439.75 879.50
Digitally signed by AMIT
78 17.57 Providing and fixing collar AMIT SINGH
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
17.57.1.2 100 mm sand cast iron S&S as per IS 3989 Each 4 439.75 1,759.00
79 17.58 Providing lead caulked joints to sand cast iron/centrifugally cast (spun) iron pipes and fittings of diameter :
80 17.59 Providing and fixing M.S. stays and clamps for sand cast iron/centrifugally cast (spun) iron pipes of diameter
Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm
complete, including cost of cutting and making good the walls and floors:
17.60.1.1 100 mm inlet and 100 mm outlet -cast iron S&S as per IS 3989. Each 2 1,604.10 3,208.20
Painting sand cast iron/centrifugally cast (spun) iron soil, waste vent pipes and fittings with paint of any colour such
as chocolate grey, or buff etc. over a coat of primer (of approved quality) for new work.
17.65.1 100 mm diameter pipe Mtr 25 69.55 1,738.75
Internal work- Exposed on wall.
Providing and fixing G.I. Pipes complete with G.I. fittings and clamps, i/c making good the walls etc. concealed pipe,
83 18.11 including painting with anti corrosive bitumastic paint, cutting chases and making good
18.11.2 20 mm dia nominal bore Meter 20 541.10 10,822.00
Providing and fixing G.I. pipes complete with G.I. fittings including
trenching and refilling etc.
18.12.4 32 mm dia nominal bore Meter 20 457.70 9,154.00
85 18.18 Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete.
Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover
86 18.48 and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings per Ltr 1000 9.70 9,700.00
and the base support for tank.
Providing, fixing, jointing, testing and commissioning of UPVC pipe conforming to IS:4985 of 6 Kg/Sq. cm rating
cut to required lengths including all necessary fittings as IS:7834(moulded) & IS:10124 (fabricated) and specials
such as Bends, junctions, offsets. Fixing at wall/ceiling level supported by galvanized steel clamps & hangers etc.
Cutting, chases/holes in floors / walls / slab
Providing & fixing rain water `Khurras' size 450x450 mm required depth with lead flashing around the pipe with one
88 piece lead sheet of 3 mm thick set on a layer of cold bitumen. Including Heavy duty CI/MS grating as per drawing Each 3 1,527.00 4,581.00
Digitally signed by AMIT
complete as required.
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
89 Providing, fixing, testing & commissioning of eurometic self closing pillar cock. Each 2 559.00 1,118.00
90 Providing & Fixing Towel ring. Each 2 637.00 1,274.00
Providing, Fixing beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board
ground fixed to wooden cleats with C.P. brass screws and washers complete.
92 Providing & Fixing Recessed type toilet paper holder Each 2 654.00 1,308.00
93 Providing & Fixing liquid soap Dispenser with glass bottle. Each 2 698.00 1,396.00
94 Providing & fixing twin coat hook. Each 2 250.00 500.00
95 Providing,Fixing, testing and commissioning of 15 mm dia bib cock with C.P. wall flange of approved quality Each 4 198.00 792.00
Providing,Fixing, testing and commissioning of angle valve with C.P. wall flange, Nut and Washer etc. complete as
Providing,Fixing, testing and commissioning of C.P Copper connection 450 mm long including nuts and washers and
making connection to fixtures and fittings complete as required.
Providing,Fixing Heavy class SS grating with Cockroach proof SS strainer of approved design including setting in floor
with cement motor to match with floor finish as per architect requirement suitable for waster and FT.
Providing & fixing C.P. brass hand shower (Health faucet) with I M tube and hook, fixed to wooden clits with CP brass
screw complete in all respects.
100 Providing,Fixing, testing of white vitreous china large urinal partition complete as required. Each 1 1,663.00 1,663.00
E ACCESS CONTROL, CCTV, FIRE FIGHTING SYSTEM
101 1.22.1 Supply and fixing of 75mm x 75mm x 60mm deep metal box on surface or in recess Nos 15 140 2100
102 1.53 Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. Mt 2400 49 117600
Supplying and fixing of 25mm medium class PVC conduit along with accessories in surface/recess including
cutting the wall and making good the same in case of recessed conduit as required.
Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor
104 17.5.1 having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) Mt 100 328 32800
insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required
Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like
105 17.5.4 Mt 85 50 Digitally signed by AMIT
coupler etc. as required.
SINGH 14:13:04 IST
Reconstruction of the Main Gate Reception at CBI HQ Building, New Delhi
S.No. Description of item Unit Qty DSR Rate DSR Amount NS Rate NS Amount
106 MR Suply and Installation, testing and commissioning of new Biometric Turnstile Gate Nos 4 161070 644280
107 MR Dismantling of Existing turnstile Gates and keeping it in store safely Nos 5 1550 7750
108 MR Shifting and reinstallation and programming of Turnstile gates Nos 5 10740 53700
109 MR Configuration of existing Turnstile gates Nos 5 10739 53695
Supply, Installation, Testing and Commissioning of 600x600 18 U Networking Rack , lockable Door unit,, Powder
110 MR Coated Rack, Side panel openable with latch & Key having Fan (2 Nos.), Cable Manager (1Nos), 6 way PDU (1Nos.) Nos 1 15900 15900
complete in all respect as required.
Fabricating supplying installation of factory fabricated 50mm wide GI Sheet Raceways height 38 mm and of totally
enclosed with 2mm thick cover. Two lengths of channel / channel and junction box shall be joined together to make
111 MR it dust and water proof. Chipping and removing screed to install the raceways in floor, including removal and Mt 70 350 24500
disposing of debris as per PMC instructions, finishing with PCC, providing chicken mesh and making good as per
Engineer in charge
Supplying to site of installation, fixing in position GI Junction Boxes of 100mmx100x50mm 2 mm thick complete with
112 MR 3 mm thick GI Covers duly , providing rubber gaskets between the cover and the Junction Box, screws etc. as required Nos 35 350 12250
Supply, Installation, Testing & Commissioning of CAT 6 Infornmation Outlet,Universal label permits T568A or B wiring,
UL® Listed, meets all TIA and ISO requirements.Complete in all respect as required by the site.
Supply, Installation, Testing and comissioning of single face plate having provision for one I/O along with spring type
shutter for dust proof, made of ABS PVC plastic complete as required
Supply, Installation, Testing & Commissioning of Network Gigabyte switch with 24 port PoE ports + 4 Gigabyte SFP
ports Web Smart Switch
Supply, Installation, Testing and Commisioning of 24 Port Modular Gigabit Cat 6 Patch Panel, Moduler Type and Label
Plate. Complete in all respect as requied by site.
117 MR Supplying and fixing GI box with modular type telephone (RJ-11) outlet complete as required. Nos 12 270 3240
118 MR Supply, Installation, Testing & Commissioning of 2mt Cat 6 Patch Cord. Complete in all respect as requied by site. Nos 50 270 13500
Providing, fixing connecting and testing of 100 pair of solderless telephone tag block Krone make in surface/recess in
wall required size of M.S. box with hinged lockable cover duly stove enamel painted.
120 MR Supply, Installation, Testing & Commissioning of 2 MP Dome Network Camera all complete as required Nos 5 13500 67500
121 MR Supply, Installation, Testing & Commissioning of 2 MP Bullet Network Camera all complete as required Nos 5 14700 73500
122 MR SITC of 16 port NVR to manage upto 16 cameras all complete as required Nos 1 44250 44250
Supply, Installation, Testing & Commissioning of 6 TB Hard disk storage capacity complete with all accesories as per
site as required.
SITC of 49” Flat Screen HD LED (24x7) with interfaces include HDMI, DVI, D-sub, Component and Composite input as
124 MR well as RS-232C and RJ-45 for extensive connectivity, remote control and wall mount unit/ floor stand complete with Nos 1 74300 74300
making connections etc complete as required
125 MR Supply & Installation of single loop Addressable Fire panel Nos 1 81500 81500
126 MR Supply & Installation of Addressable Smoke Detectors Nos 15 4150 62250
127 MR Supply & Installation of MCP Nos 1 4850 4850
128 MR Supply & Installation of Hooter Nos 1 6895 6895
129 MR Configuration fo Fire Alarm System Job 1 7500 7500
Digitally signed by AMIT
SINGH 14:13:04 IST
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT.pdf
Tender Document
CS_cover_2_Quote_Sheet.xlsx
Tender Document
BOQ.pdf
Tender Document
SCC.pdf
Tender Document
Tentative Drawings.pdf
Tender Document
GCCamendupto17merged.pdf
Tender Document
InstructiontoBidderforonline Bid Submission.pdf
Tender Document
corrigendum-1037-CORRIGENDUM.pdf
pdf • 0.52 MB
corrigendum-988-Corrigendum I.pdf
pdf • 0.13 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .