Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.0 LAccepted-AOC 58 CHANDRALOK BLDG MAYO HOSPITAL ROAD NAGPUR 440018 | NAGPUR | NAGPUR | MAHARASHTRA | 440018 | ₹32.0 L Quoted ₹33.1 L | L1 | Accepted-AOC Lowest |
| 2 | L2₹37.6 L+₹4.4 L (13.4%)Rejected-Finance | ₹37.6 L+₹4.4 L (13.4%) | L2 | Rejected-Finance Not Lowest |
| 3 | L3₹38.0 L+₹4.9 L (14.7%)Rejected-Finance | ₹38.0 L+₹4.9 L (14.7%) | L3 | Rejected-Finance Not Lowest |
Tender Value
₹37 L
EMD Value
₹74,000
Closing Date
3 Jun 2023, 6:00 pmClosed
Garrison Engineer
Garrison Engineer, Cantt Area, Kamptee 441001
REPAIRS REPLACEMENT TO SWITCH GEAR SUCH AS MCCBS, MAIN SWITCH,FEEDER PILLAR BOX,CAPACITOR BANK AT OTA NCC, MICTS,MH,GRC, APS, AND 52 COY SUPPLY DEPOT AND LIGHTNING CONDUCTOR, EARTHING, SURGE ARRESTOR OF VARIOUS ---STN KAMPTEE UNDER GE KAMPTEE
2023_MES_593590_1
8518/E8
Open Tender
Civil Works
Item Rate
180 days
Kamptee
Class D Cate d (i)
5 documents required · 5 mandatory
₹500
Yes
Kamptee
₹74,000
Yes
20 Jun 2023
6 May 2023
5 Jun 2023
6 May 2023
3 Jun 2023
20 May 2023
Amount
Taking down the unserviceable LT cable of any size from tranches/ walls /floor etc complete all as specified and as directed. Note :- laying of cable route is same as old cable route .
Excavation in trenches in any type of soil not exceeding 1.5 meter wide and not exceeding 1.5M in depth for laying of Cables,poles, stay and getting out of excavated material complete all as specified and directed.
Excavation in trenches in any type of hard/dense soil/hard standing not exceeding 1.5 meter wide and not exceeding 1.5M in depth for laying of Cables,poles, stay and getting out of excavated material complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested complete all as specified and directed.
Removal of surplus soil to a distance not exc. 50m and deposited where directed at a level not exc. 1.5 m above the starting point all as specified and as directed.
Supply and fix Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 63 mm outer diameter and 51 mm inner Diameter with IS 14930 (part 2):2001 laid in trenches,wall,floor,pole including bends, sockets and other connected accessories complete all as specified and directed Make:- Dura. Line/Tijaria/REX/Ketron
Supply and fix Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 90 mm outer diameter and 76 mm inner Diameter with IS 14930 (part 2):2001 laid in trenches,wall,floor,pole including bends, sockets and other connected accessories complete all as specified and directed Make:- Dura. Line/Tijaria/REX/Ketron
Supply and fix Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 120 mm outer diameter and 103.5 mm inner Diameter with IS 14930 (part 2):2001 laid in trenches,wall,floor,pole including bends, sockets and other connected accessories complete all as specified and directed Make:- Dura. Line/Tijaria/REX/Ketron
M&L for Precast RCC Slab Type B0 1:2:4 for cable route indicators of size Length 0.9 mtrx0.3mtrx0.065 mtr duly writing"MES LT/HT Cabe" duly painted with Weather coat paint embeded in PCC 1:4:8 under ground at depth 0.45 mtr complete all as specified and directed.
Supply and laying in trenches or fixing in walls / poles or drawing through pipe XLPE insulated, screened,PVC bedded, galvanised steel strip, electric power cables ( heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 150 sq mm, 3.5 core including testing after laid and jointed all as specified and as directed Make :- Gloster/ Polycab/Havells Note:- Excavation and earth work,cable protection shall be measured and paid separetely.
All as per item No. 10 but cable size 185 sq mm 3.5 core complete all as specified and as directed.
All as per item No. 10 but cable size 240 sq mm 3.5 core complete all as specified and as directed.
All as per item No. 10 but cable size 70 sq mm 3.5 core complete all as specified and as directed.
Earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground vertically to a depth not less than 2.25m below ground level with top edge of earth plate not less than 1.5m below ground level connected to galvanized iron earth strip 32x6 mm by means of bolts, nuts, check nuts, washers of galvanized iron and connected to main switch/control board upto 7.5m away from the earth electrode including excavation earth work, PCC chamber, RCC cover slab char coal, watering pipe, wire mesh lugs, earth lead protection pipe 40mm bore, light grade 7.5m long as applicable and as per plate No. 5 of SSR 2009 and all as specified. (a) Excavation and earth work in any type of soil. (b) Drilling of holes in electrode (c) PCC pit in cement concrete (1:2:4) type B-1 (d) 40 mm thick Pre-cast RCC cover with suitable handle. (e) Funnel with watering pipe of GI 20 mm nominal bore ,medium grade & copper lug etc. (f). 40mm nominal bore medium grade GI protection pipe 7.50 m long for protection of earthing lead. (g) Requisite quantity of charcoal and common salt. (h) Connection to earthing test point and testing on completion.
Supply and fix Heat shrinkable straight through cable jointing kit for 1100 Volts grade cable joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 150 to 185 Sq mm complete all as specified and as directed. Note :- Any Excavation and earth work ,Returning and filling, Removing involved shall be measured and paid seperatelay
All as per item No. 15 but cable size 70 - 120 sq mm cable size complete all as specified and as directed.
All as per item No. 15 but cable size25 - 50 sq mm cable size complete all as specified and as directed.
Supply,and Fix power factor correction Capacitor heavy duty cylindrical type toughest construction highest dependable up to 70 deg cel ambient temp withstable, for 440 Volt 50 Hz AC supply system for capacity 10 KVAR complete all as specified and as directed. Cat No LTCCH of L&T of equivalent in ABB/Siemens
Supply,and Fix power factor correction Capacitor heavy duty cylindrical type toughest construction highest dependable up to 70 deg cel ambient temp withstable, for 440 Volt 50 Hz AC supply system for capacity 20 KVAR complete all as specified and as directed. Cat No LTCCH of L&T of equivalent in ABB/Siemens
Supply,and Fix power factor correction Capacitor heavy duty cylindrical type toughest construction highest dependable up to 70 deg cel ambient temp withstable, for 440 Volt 50 Hz AC supply system for capacity 25 KVAR complete all as specified and as directed. Cat No LTCCH of L&T of equivalent in ABB/Siemens
S&Fmulti function meter with accuracy 1.0 input voltage 50-520 Volt, Aux supply 80-300 VAC, CT secondary siide 1A/5A, flush mounting 96x96 mm withpara meter Volt,Amp,Frequency,Poer factor,KW/KVA,KVAR,KWH etc for 440 Volt 50 Hz Ac system Cat No WL441010OOOO of LT or equivalent of ABB/Siemens
S&F Current Transformer for 100/5A,Burden 5VA Ring type for LT Panel 440 Volt 50 Hz complete all as specified and as directed.
S&F Current Transformer for200/5A,Burden 5VA Ring type for LT Panel 440 Volt 50 Hz complete all as specified and as directed.
S&F Ammeter digital type 96x96 mm Aux supply 230 Volt accuracy class 1 for LT Panel 440 Volt 50 Hz system complete all as specified and as directed.
S&F Volt Meter digital type 96x96 mm Aux supply 230 Volt accuracy class 1 for LT Panel 440 Volt 50 Hz system complete all as specified and as directed.
Taking down the unserviceable LT Panel of any size complete with all accessories complete all as specified and as directed.
Supply, install, test and commissioning of LT panel board / feeder pillar box, outdoor cubicle type, vermin proof, dust proof (of CPRI approved manufacturer), fixed on 50x50x5mm MS angle iron frame fixed 300mm above ground level and 450mm below the ground level grouted in and including PCC 1:3:6 type C1 (using 20mm grade stone aggregate) and plane made out of 3.00 mm thick CRCA sheet for both outer shell and 2.00mm hick for inner shell both side open able supported on and including ISMC 75 X 40mm powder coated steel frame and totally powder coated with epoxy siemen grey colour from inside and outside with locking arrangement and fixing arrangement i.e nuts, bolts, washers, clamps etc, with naturally air cooled epoxy insulated aluminium busbar TPN suitable for 300 Amps with detachable gland plate for incoming and outgoing cable including termination of cable ends both incoming and outgoing with sufficient working space inside complete,all control cables shall be of 2.5 Sqmm copper multi stranded conductors and shall be properly bunched with suitable size binding materials , ferruled for proper identification of colour codes and crimped with adequate size of lugs also to accommodate and consisting of the following items, all as specified and as directed . (a) Busbar chamebr for 3 phase & nuetral of capacity 300 Amps (30mm x 10mm) alumunium bus bar duly insulated, (b) Multifunctioning meter to measure Voltage, ampere, KWH, PF -1 Nos (c) one set of pilot lamp. (d) Incoming MCCB 160 amps 4 Pole 415 volts 25 KA, Ics=100% of Icu thermal magnetic setting type- 1 Nos (e) Outgoing MCCB 63 amps 3 pole 415 volts 10 KA thermal magnetic setting - 5 Nos (f) Outgoing Type MCB 63 amps 3 Pole 415 volts 10 KAIcs=100% of Icu - 2 Nos
S&F MCCB 4 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 36 KA, Ics=100% of Icu complete all as specified and as directed.
S&F MCCB 4 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA Ics=100% of Icu complete all as specified and as directed.
S&F MCCB 4 Pole, 415 V, Adjustable type, 320 Amps with breaking capacity 36 KA Ics=100% of Icu complete all as specified and as directed.
S&F Stainless steel MCCB Enclosures for 3 pole/4 pole MCCBs , inbuilt neutral link for TPN Systems , mounting holes, IP 30,for upto 125 A MCCB 36 KA Cat No DU100D-125D of L&T of equivalent
Cleaning of sub station area by uprooting all types vegitation,shrubs,weeds,saplings and creepers of unwanted trees complete with the help of spade,axes,crowbars and other mechanical means after taking necessary electrical shutdown from concerned incharge of various sub stns of Military stn Kamptee complete all as specified and as directed.
Trimming of tree branches touching of Over head Elecctrical Lines upto 2.5 mtr distance from conductors after taking necessary shutdown from concerned incharge all as directed . (Note : Space beteen poles will be measured as one unit irrespective of nos of conductors .)
M&L for horizontal boring in road/hard surface not exceeding 20 mtr in one strech and not exceeing 1.5 mtr depth for passing LT cable including HDPE pipe 150 mm dia all as directed.
Fabrication, Supplying Installing, testing & Commissioning outdoor type feeder pillar box with rain cowl weather / vermin proof, Indoor type, factory made LT panel, from any CPRI approved manufacturer having dismensions of Suitable size with sufficient space between MCCB cable coonection place and body of panel for easily working to workers including necessary incoming & outgoing cable connections, cable glands thimbles of required sizes, made out of CRCA sheet 3.00 mm thick for outer shell and 2mm thick for inner shell duly powder coated paint with inner shutter & outer double door, the cubical shall have a bottom channel of size 75x40x5mm duly coated with zinc metal coating with satinless steel locking handle arrangement both side openable fixed on 50 x 50 x 5 mm MS angle frame fixed 300mm above groud level & 300 mm below the ground grouted in & including PCC 1:3:6 type C1 (using 20mm graded stone aggregate) complete all as specified, directed & comprising of following including refixing existing cables to new panels by proper lugging & cable gland as required. (a) Busbar chamebr for 3 phase & nuetral of capacity 450 Amps (45mm x 10mm) alumunium bus bar duly insulated, (b) Multifunctioning meter to measure Voltage, ampere, KWH, PF -1 Nos (c) one set of pilot lamp. (d) Incoming MCCB 320 amps 4 Pole 415 volts 35 KA Ics=100% of Icu thermal magnetic setting type- 1 Nos (d) Outgoing MCCB 200 amps 3 Pole 415 volts 35 KA Ics=100% of Icu thermal magnetic setting type- 1 Nos (e) Outgoing MCCB 160 amps 3 Pole 415 volts 35 KAIcs=100% of Icu thermal magnetic setting type- 2 Nos (f) Outgoing MCCB 63 amps 3 Pole 415 volts 35 KA Ics=100% of Icu thermal magnetic setting type- 3 Nos
Taking down unsv earthing any type
M&L for Earthing complete with copper earth plate electrode 900x600x5mm thick buried directly in ground vertically to a depth not less than 3 m below ground level with top edge of earth plate not less than 2.1 m below ground level connected tocopper earth strip 50x10 mm by means of bolts, nuts, check nuts, washers of brass and connected to main switch/control board upto 7.5m away from the earth electrode including excavation earth work, PCC chamber, RCC cover slab char coal, watering pipe, wire mesh lugs, earth lead protection pipe 80mm bore, light grade 7.5m long as applicable and as per plate No. 5 of SSR 2009 and all as specified. (a) Excavation and earth work in any type of soil. (b) Drilling of holes in electrode (c) PCC pit in cement concrete (1:2:4) type B-1 (d) 40 mm thick Pre-cast RCC cover with suitable handle. (e) Funnel with watering pipe of GI 20 mm nominal bore ,medium grade & copper lug etc. (f). 80mm nominal bore medium grade GI protection pipe 7.50 m long for protection of earthing lead. (g) Requisite quantity of Back fill compound (25 kgs bags x 3 Nos minimum) (h) Connection to earthing test point and testing on completion.
M&L for Earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground vertically to a depth not less than 2.25m below ground level with top edge of earth plate not less than 1.5m below ground level connected to galvanized iron earth strip 25 x 4 mm by means of bolts, nuts, check nuts, washers of galvanized iron and connected to main switch/control board upto 7.5m away from the earth electrode including excavation earth work, PCC chamber, RCC cover slab char coal, watering pipe, wire mesh lugs, earth lead protection pipe 40mm bore, light grade 7.5m long as applicable and as per plate No. 5 of SSR 2009 and all as specified. (a) Excavation and earth work in any type of soil. (b) Drilling of holes in electrode (c) PCC pit in cement concrete (1:2:4) type B-1 (d) 40 mm thick Pre-cast RCC cover with suitable handle. (e) Funnel with watering pipe of GI 20 mm nominal bore ,medium grade & copper lug etc. (f). 40mm nominal bore medium grade GI protection pipe 7.50 m long for protection of earthing lead. (g) Requisite quantity of charcoal and common salt. (h) Connection to earthing test point and testing on completion.
Materials and labour for earth continuity conductor or main earthing lead fixed to wall or batten or recess or chases as required 25X3 mm Aluminium strip complete all as specified and directed.
Materials and labour for earth continuity conductor or main earthing lead fixed to wall or batten or recess or chases as required 32x6 mm GI strip complete all as specified and directed.
M&L Air termination, single pointed aluminium rod 12 mm dia and 300 mm long complete all as specified and directed
Material and labour for test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 Nos 8mm dia 25mm long hex. Head screw.complete all as specified and directed
S&L for cutting existing steel tubing for alterration or additions ( each cut measurd) of dia 40 or 50 mm complete all as specified and as directed.
M&L for screwing existing sreel tubing for alterations or additions (or lengthening screw on pipe to from connection) of dia 50mm complete all as specified and as directed.
S&L complete pipes, galvanised, medium grade including fittings 40 mm dia complete all as specified and as directed.
S&L complete pipes, galvanised, medium grade including fittings 20 mm dia complete all as specified and as directed.
S&L complete pipes, galvanised, medium grade including fittings 15 mm dia complete all as specified and as directed.
S&F Straight plain brass ferrules 50 mm dia (or connecting screws) screwed both ends and fixed complete all as specified and as directed.
S&F stop valves, cast copper alloy, screwed down, high pressure, with crutch or buttrrfly handle, screwed both ends for iron pipe or for unions & fixed of dia 40 mm complete all as specified and as directed.
Supply and fix plug type bib taps 20mm, cast iron, screwed for iron pipe and fixed complete all as specified and as directed.
M&L PCC 1:2:4 with 40 mm B2 aggregate in lintels upto 1.5m clear span, cills, steps; seismicand other similar bands,plinth courses, string courses,lacing courses, parapets andrailings upto 60 cm in height,copings, complete all as specified and as directed.
M&L for Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp 11000 Volt grade complete all as specified and as directed.
M&L for Fire extinguisher ball made of rigid plastic foam with an abrason resistant exterior red colour of capacity 1.3 Kg capacity complete all as specified and as directed . Make - Elide Fire or equivalent
M&L for complete removal of old paints surface and spray painting to existing LT Panel/Sub stn Gate/Fencing Angles/Chequered plates/Feeder Pillar Electric sub stn of any capacity with two coats of approved colour synthetic enamel paint complete including dusting, cleaning of existing dust before applying synthetic enamel paint after applying redoxide primer and writing feeder name with approved colour synthetic enamel paint complete all as specified and directed.
Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium conductor, 4 sqmm 2 core , served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire complete all as specified and as directed .
NOTE:- SCHEDULE OF CREDIT (Amount shall be deducted offline from the total quoted amount to workout the net contract sum to be considered for acceptance.) [(-) Rs. 1,10,050.00]
Vaidehi E Link
Chinmaya Enteprises
Bidder Name
Paragon Electrotechnics
Chinmaya Enteprises
Vaidehi E Link
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .