| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.5 LAccepted-AOC A 63 ELDECO COUNTY PHASE II RAJGARH JHANSI U P 284135 | JHANSI | JHANSI | UTTAR PRADESH | 284135 | L1 | Accepted-AOC Being lowest bidder | |
| 2 | L2₹42.5 L+₹1.8 L (4.44%)Rejected-Finance 840 1B MADHUR VIHAR COLONY CIVIL LINES JHANSI UP 284 001 | JHANSI | JHANSI | UTTAR PRADESH | 284001 | L2 | Rejected-Finance Not lowest bidder | |
| 3 | L3₹43.2 L+₹2.5 L (6.06%)Rejected-Finance | L3 | Rejected-Finance Not lowest bidder | |
| 4 | L4₹47.0 L+₹6.2 L (15.3%)Rejected-Finance CIVIL LINE MATATILA ROAD TALBEHAT DISTT LALITPUR U P | TALBEHAT | LALITPUR | U P | L4 | Rejected-Finance Not lowest bidder | |
| 5 | L5₹51.2 L+₹10.5 L (25.8%)Rejected-Finance | L5 | Rejected-Finance Not lowest bidder |
Tender Value
₹55.3 L
EMD Value
₹1.1 L
Closing Date
12 Oct 2024, 6:00 pmClosed
CWE JHANSI
HQ CWE JHANSI
PROVN OF SECURITY LIGHT, 20 X FLAME PROOF SECURITY LIGHTS, 07 X 2.0 TON SPLIT TYPE INVERTER AIR CONDITIONER ACCESSORIES AND CERTAIN SPL REPAIR UNDER AGE E/M AT GE JHANSI
2024_MES_672382_1
CWE/JHA/J/TOKEN/41 OF 2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
JHANSI
As per tender documents
9 documents required · 9 mandatory
₹1,000
GE JHANSI
₹1.1 L
Yes
15 Feb 2025
5 Sept 2024
14 Oct 2024
5 Sept 2024
12 Oct 2024
30 Sept 2024
Amount
Supply and erection of Hot dip galvanized tapered octagonal pole of height 7.0 mtrs in single or double section having top dia 70mm and bottom dia 130mm made up of 3mm thick sheet and welded with a base plate of size 220mm x 220mm x 12mm thick and provided with 1000mm long single arm bracket with 15 degree of angle 02 Nos for mounting street light fitting complete with provision of 04 Nos of ‘J’ type foundation bolts of size not less than 20mm dia, 600mm long embedded in RCC foundation concrete as per manufacturer’s recommendation including necessary earth work in any type of soil returning filling and removal of extra earth upto 50m etc complete. A door should be provided at a height of 500mm from the base plate for accommodating and including provision of TPN aluminium bus bar system suitable for connecting up to 4 core, 16 sqmm aluminium cable and 01 No. of 6A SP MCB for street light protection inside the pole shaft including provision of 3 core, 1.50 sqmm PVC insulated PVC sheathed copper conductor cable 1100 volts grade confirming to IS:694 from pole junction box to street light fitting drawn through inside of pole . Radium reflector band / strips of 5cm wide in Green (02 Nos) & White (01 No.) colour shall be provided at a height of 1.25mtr from base plate. Numbering of pole shall be done in black colour on yellow background at suitable place on the pole complete as specified and directed. Note: The quoted rate shall deemed to be inclusive of RCC foundation concrete type 1:2:4 type B-1, necessary excavation, erth work & RFR etc complete as per manufacturer's recommendation. Contractor shall submit the pole drawing and foundation drawing as per manufacturer's recommendation for approval of GE before procurement.
Supply and fixing of 60 Watt LED street light fitting made up of Pressure die-cast aluminium alloy housing with toughened glass, IP66 protection and impact resistance of IK07 and individual high power LEDs with secondary optics having system lumen efficacy ≥100 lm/W, Inbuilt potted electronic LED driver with APFC (SMPS based constant current supply), lower THD, Open Circuit protection, Over Voltage protection, Surge Voltage protection & other safety test as per IS 15885 Part-2/Sec 13 and BIS complying complete all as specified and directed.
Suppply , laying and testing cable XLPE insulated , screened, PVC Bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with standerd aluminium conducter of size 16 sq mm 4 core complete all as specified and directed.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth and getting in hard / dense soil for laying of cables complete all as specified and directed.
Returning, filling in trenches including spreading, leveling watering well ramming layers not exceeding 25mm complete all as specified and directed.
Removing surplus excavated material to a distance not exc 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
Material and labour for Double wall corrugated HDPE pipe, ISI marked of outer dia 50mm, inner dia 38mm with smooth internal and profiled external surface, non-pressure type, laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends, etc for protection of LT cable XLPE grade 1100 volts complete all as specified and directed.
S&F of Ceiling rose, three terminals, bakelite body, 240 volts, complete all as specified and directed.
Material and Labour for sub main wiring 2runs x 1.5 sqmm (Ph & N) + 1run x 1.5 sqmm (earth wire) along with earth wire with FRLSH insulated copper conductor, single core cable drawn through and including medium grade rigid steel conduit conforming to IS:9537 (Pt-III) and its all accessories/junction boxes/ inspection covers etc of suitable size but not less than 20mm concealed in wall/ floor etc complete all as specified and directed for the following sizes:- Note: Three runs of copper cable and one run of rigid steel conduit shall be measured as one RM unit length.
Supply and fix of Flame Proof SSPL /1233 or EquvelentLED street/security light fitting 60 watts with high efficiency long life LEDs with In-built electronic driver and surge protection upto 10 Kv complete housed in pressure die-cast aluminium housing covered with polycarbonate cover with IP66 degree of protection including provision of GI pipe bracket made up of 25mm dia medium grade GI pipe of length 1.50m bent to required shape and fixing on walls with suitable MS clamps(02Nos) made up of 25mmx4mm MS flat, nuts, bolts and washers and provision of 3 core twisted flexible copper cable of size 0.5 sqmm from ceiling rose to connector of fitting complete all as specified and as directed.
Supply and fix of flame proof MCCB / MCB distribution board, SPN, 6 way, 230 Volt, Single phase, AC and MCBs(Incoming MCB, 2 pole;32A-01 No and outgoing MCB 1P, 6 Amp-4 Nos) in sheet steel powder painted enclosure(300 x 300 x 190 mm) with minimum IP 43 degree of protection with built in copper bus bar, neutral link and earth link complete including cutting the wall surfaces for flush mounting of DB and making good with cement plaster, putty and paint to match with the existing surface complete all as specified and directed.
Supply and fixing steel tubler swaged pole completed with cast iran base plate, finial tapper plug, bolts, nuts and screws as specified type 410 SP-22(8.5) Mtr long including necessary excavation in any type soil, returning filling and removal of extra/surplus earth, concerete bed in PCC 1:3:6 type C-2 using 40mm crushed stone aggregate upto ground level and above ground level 450x450x450mm PCC coping 1:2:4 type B-1 by using 20mm aggregate complete all as specified and directed.
Supply and fixing of 120 Watt Flame Proof SSPL /1233 or Equvelent WattnLED street light fitting made up of pressure die-cast aluminium alloy housing with toughened glass, IP protecgtion and and indivisual high power LEDs with secondary optics having system lumen efficacy ≥100 Im/W Inbuilt potted electronic LED driver with APFC (SMPS based constant currently supply), lower THD, open circuit protection, over Voltage protection, surge Voltage protection & other Safety test as per IS 15885 Part-2/Sec 13 and BIS Complying complete all as specified and directed.
Supply and fix in replacement of GI pipe bracket made out of 40mm dia medium grade GI pipe of 1.50mtr long bent to required shape and fixed to steel tubular / PCC pole with flat iron clamp nuts, bolts and washers etc complete all as specified and directed.
Spply and fix SMC (sheet moulded compound) outdoor type junction box of size 240mm X 130mm X 95mm (Outside Dimensions) with 63Amps rated four pole connector, one single pole MCB of 6 Amps rating mounted on DIN rail, stainless steel cable glands of suitable size for incoming and outgoing cables including fixing on steel tubular poles / PCC poles with 25mm X 4mm MS clamps (02 Nos), nuts & bolts etc complete all as specified and as directed.
M & L for making holes (02 Nos in each pole - one near cable junction box and other near street light bracket) on existing steel tubular poles of any type, thickness & height through drilling / gas welding work having smooth and chamber edge of hole, for drawing street light control cable through inside of pole complete all as specified and directed.
Supply and fix an replacement of 40mm dia bore tubes, 'light grade' galvanized, with a lfitting and fixed complete to wall/ pole or laid in trenches/ floors for cables protection complete all as specified and directed.
Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated stranded aluminium conductor served with an inner sheathing of PVC tape armoured with galvanized steel wire or strip and overall PVC sheathed, 10 sq. mm nominal cross section, 2 core in service connections as per IS 7098(Part 1) including connecting on LT OH line / LT panel /DB with suitable lugs, glands, binding wire etc complete all as specified and directed.
Suppply , laying and testing cable XLPE insulated , screened, PVC Bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with standerd aluminium conducter of size 25 sq mm 4 core complete all as specified and directed.
M&L for PCC 1:3:6 type C-2 ( using 40mm graded stone aggregated) as in foundation filling and mass concerting complete all as specified and directed.
Supply, installation, testing and commisioning of air cooled split type Air conditioner ( Cooling and heating type) of 2TR capacity comprising of one indoor and one outdoor unit, wall mounted type comprise of copper pipe heat exchangers, having non CFC refrigerant, electric driven, 230 Volts AC, single phase, 50 Hz, having Five Star rated / inverter technology with and including inlet/outlet copper pipe for refrigerant between indoor & outdoor unit with flexible copper wire of suitable size as recommended by manufacturer, complete all as specified and directed. Note: The cost of making hole / opening for passing inlet/ outlet copper pipes and clectrical cord and making good surface as original by plastering / applying putty/ whitewash/colour/distemper etc is included in quoted rate and no extra payment will be made to contractor in this effect. Make: LG, Voltas, Hitachi, Daikin, Carrier, Blue Star.
Supply, connect & testing of automatic voltage stabilizer, 4 KVA capacity wall mounted type for low voltage cut-off, single phase, AC, 50 Hz, 15 Amps rating ,suitable for input voltage range 160V-280V AC with 3min±20 sec delay for Air Conditioner Complete all as specified and directed.
M&L for Circuit/submain wiring alongwith earth wire 2 runs x 4.0 sqmm + 1 run x 4.0 sqmm with FRLS insulated copper conductor, single core cable drawn through and including medium grade rigid PVC conduit conforming to IS:9537 (Pt-III) and its all accessories/junction boxes/ inspection covers etc of suitable size but not less than 20mm concealed in wall/ floor etc complete all as specified and directed. Note: Three runs of copper cable and one run of PVC conduit shall be measured as one RM unit length.
S&F, Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole20 Amp MCB, 240 volts, complete all as specified and directed.
Supply and fix MCB distribution board, SPN, 4 way, 240 Volt in sheet steel powder painted enclosure double door type with IP 43 degree of protection with built in copper bus bar, neutral link and earth link complete including cutting the wall surfaces for flush mounting of DB and making good with cement plaster, putty and paint to match with the existing surface all as specified and directed.
S& F MCB SPN 40- 63 Amp, 10 KA, 'C' curve, 240 V, 50 Hz complete all as specified and directed.
S& F MCB SP 6-32 Amp, 10 KA, 'C' curve, 240 V, 50 Hz complete all as specified and directed.
Supply and fixing in replacement of 90 WattnLED street light fitting made up of pressure die-cast aluminium alloy housing with toughened glass, IP-66 protecgtion and and indivisual high power LEDs with secondary optics having system lumen efficacy ≥100 Im/W Inbuilt potted electronic LED driver with APFC (SMPS based constant currently supply), lower THD, open circuit protection, over Voltage protection, surge Voltage protection & other Safety test as per IS 15885 Part-2/Sec 13 and BIS Complying complete all as specified and directed.
Material and labour for earthing complete with galvanized iron earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connecting to GI wire 4mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel and earth wire protected by 15mm dia GI pipe medium grade and connected to pole structure/ panel board/earthing test point all as shown in electrical plate No. 3 of SSR Part-I(2009) and testing on completion complete all as specified and directed. Note :- The unit rate quoted shall also include for excavation, earth work in any type of soil, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bras @ 150mm C/C both ways, GI funnel with watering pipe, wire mesh, protection pipe, earth strip up to 7.50m long complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub heading earthing, specified in SSR Part II (ii) Earthing test report with value less than 2 Ohm should be submmited by contractor before claiming the payment.
Taking down carefully the Ceiling fan of any discription from its installed position by disconnecting all electric supply connections and shall be deposited to AGE E/M yard for necessary repairs/replacment complete all as specified and directed.
Supply and fix of ceiling fans complete with blades, down rods and accessories, 230 V, 1200 mm sweep 3 blade, white colour,. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated, copper winding with brushless direct current motor (BLDC)(with remote) and connecting up with 3 core x 0.5 sqmm flexible copper conductor cable from ceiling rose all as specified and directed. Note: Old Ser/ UNSV fans removed from the site shall be the properety of Department, which shall be deposited as directed by Engr-in-Charge.
M/S Kumar Contractors (BID ID -3129029)
M/s Sohanil Construction (BID ID -3127141)
HARNAM SINGH ANIL SINGH (BID ID -3137390)
Raja enterprises (BID ID -3129432)
Flint India (BID ID -3136247)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .