CWE Wellington
Headquarters Commander Works Engineers Wellington, Barracks Post The Nilgiris PIN 643 231
SPECIAL REPAIRS AND ALTERATION OF FOUR POLE STRUCTURE AND CONNECTED ITEMS TO LBS WITH INTERRUPTION CHAMBER AT STABLE HILL SUBSTATION UNDER GE WELLINGTON
2026_MES_797674_1
83097/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Wellington
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE WELLINGTON
₹48,240
Yes
6 Nov 2026
6 Nov 2026
30 Nov 2026
6 Nov 2026
27 Nov 2026
20 Nov 2026
7 Nov 2026 - 12 Nov 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply, Install, Commissioning and TestIing of outdoor type HT, 12 KV, 630 Amps, SF 6 insulated RING MAIN UNIT (RHS EXTENSIBLE) CRCA material duly powder coated RAL 7032 with min 80 Micron Thickness and thckness of material 2 to 2.5 mm thick for load bearing and 1 to 1.6 mm for non load bearing, Degree of protection for Tank-IP 67 (SS Tank Thckness 2mm), Mechanism Chamber IP 2X in Canopy door open condition, cable Chaber IP 3X in Canopy door open condition, Outdoor IP 54 in Canopy door close condition, Busbar rating 630 A, STC 21 kA/3s, dielectric withstand 28kV AC/1 minute, Impulse Withstand 75 kVP, Rated Peak Current 52.5kAP, Rated Frequency 50 Hz with 01 No. VCB for incomer of capcity 12 kV, 3 phase 630 A, 21kA/3s and 03 Nos LBS of capacity 12 kV, 3 phase 400 A, 21 kA/3s vin single panel, as per manufacturer design and comprising of the followings parameters complete all as specified and directed. (Make : Schneider/ ABB /SIEMENS/CG):- Incommer :- (i) Vaccume circuit breaker 12 kV, 21 kA/3s, 3 pole with 3 pole manual disconnector, 3 pole manual Earth switch, low energy trip coil, mechanical emergency push button and counter with current rating of breaker 630 A - 01 No Outgoing:- (i) LBS 12 kV, 21 kA/3s, 3 pole with 3 pole manual disconnector, 3 pole manual Earth switch, low energy trip coil, mechanical emergency push button and counterwith current rating of breaker 400 A. - 01 No (ii) Load Break switch, 12 kV, 21kA/3s, 3 pole with 3 pole manual earth switch - 03 Nos | |||||
| 1.01 | (iii) Voltage presence Indicator:- suitable for 10-24 kV LED type as per IEC 61958.
(iv) Manometer:- Multiscale to cover 1.3 Bar (absolute ) or 0.3 Bar (relative) @ 20 deg C.-02 Nos.
(v) Cable Boot:- Push on type suitable for XLPE cable Al 1 Rx3C upto 300 Sqmm- 05 Sets.
(vi) Relay: Base mounted LED display 3 pole overcurrent + earth fault relay with selectable characteristics for breaker feeder with RS 485 port on MODBUS protocol and following setting ranges :-
I>: 0.2 to 2.5, t>: 0.1-150s in steps of 0.01s & ti>: 0.01-1.500 in steps of 0.005:I>>: 0.5 to 30, t>>:0.03-20s in steps of 0.01s
Ie>: 0.05 to 2.5, te>0.05-150s in steps of 0.01s & tie >: 0.01-1.500 in steps of 0.005:Ie>>: 0.5 to 15, te>>: 0.04-20s in steps of 0.01s (02 Nos)
(vii) Indication lamp : All LED lamps .
(viii) Current Transformer : CT1 Tape Wound Core 1: 50-100/1A, Class: SP10, 2.5VA Core 2: 50-100/1A, Class:1.0, 2.5VA for protection and metering - 02 Sets
(ix) Current Transformer : CT2 Core 1: 100-200/1A, Class:SP10, 2.5VA for metering - 01 Set
(x) TVM : 3 PH, 4 Wire, 110 VAC, 1 AMP for incoming feeder CT ratio-100-200/1A, PT Ratio-11kV/rt3/110/rt3, Accuracy Class 0.5 base mounted incl RS 485 port on MODBUS protocol - 01 No | - | - | - | - |
| 1.02 | (xi) Digital Ammeter: 96x96 Sqmm, 3Phase digital Ammeter with Aux supply :90to 300 V AC accuracy class 1- 02 Nos
(xii) Potential Transformer: 11 kV /rt3/110V/rt3, resin cast PT with fuse on primary, Voltage factor -1.2 cont. & 1.9 for 8 Hrs, 3Phase, accuracy Class-05 Burden 50 VA - 01 No for metering
(xiii) Space Heater: Strip Type 230V AC 80 W - 01 No
(xiv) Thermostat: Spring Type 230V AC, Range 30-110 Deg C, 10 A, SUN-110 - 01 No
(xv) Phase indicating LEDs - 63.5 V AC (L-N), 23 mm dia LEDs - 01 Set
(xvi) Ambient temperature - 5 to + 40 deg
(xvii) GAS Pressure: Operating: 1.3 Bar (Absolute) or 0.3 Bar (Relative) at 20 deg C.
(Note : RMU Shall be mounted on PCC platform of suitable height as per OEM direction including necessary grouting arrangements all as specified. Rate quoted by the contractor shall deemed to be inclusive of PCC platform and all other necessary work for the satisfactory commissioning of RMU with HT supply) | - | - | - | - |
| 2Taking down existing four pole structure, cross arms, channels & MS Nut and Bolts, including opening the HT cable/ ACSR conductor etc complete all as specified and as directed. | |||||
| 3Taking down Air break switch GOD, including opening the HT cable/ACSR conductor etc complete all as specified and as directed. | |||||
| 4S & F in repair Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and as directed. | |||||
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.50 MB
tmrgd_83097.pdf
Tender Documents • 1.51 MB
BOQ_894796.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .