Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.2 LAdmitted-Finance BHAGWATI NAGAR JAMMU | L1 | Admitted-Finance | |
| 2 | L2₹4.4 L+₹23,280 (5.59%)Admitted-Finance INDUSTRIAL ESTATE DIGIANA JAMMU | L2 | Admitted-Finance | |
| 3 | L3₹4.5 L+₹28,380 (6.81%)Admitted-Finance | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | M/S V.N ENGG WORKS L2 | Goutam Industrial Agencies L3 | PERFECT ELECTRICAL WORKS L1 |
|---|---|---|---|---|---|---|
| 1.00 | Providing, Lowering, Installation, Testing and Commissioning of Submersible Pumpset at Tubewell mentioned above having capacity of (15,000 GPH) x (40m Head) coupled with 3 phase,400 V ± 10%, 50 Hz ± 3% AC supply, copper wound squirrel cage induction submersible motor of20H.P. along with 02 No. 150mm dia. flanged column pipes assembly along with other allied materials/equipments required during lowering of submersible pumpset. The job also includes P/L of 25 mtr-35 mm sq. 3.5 core aluminum armored cable for connection of control panel to electric transformer and 45 mtr-10 mm sq 3 core submersible cable for connection of panel to the submersible pumpset. The job also includes utilizing the existing 03 No. 150 mm dia. flanged column pipes, bend and delivery pipe at site after necessary priming and painting with black enamel paint.The job also includes providing and fitting of 200 Amp, 415 Volt main switch with HRC Fuse of reputed make. The job includes cost of material, labour, carriage, tools and tackles (Complete Job in all respects). Electro-mechanical accessories used should beof genuine/reputed make conforming to latest IS code. | 1 | Job | 1,79,900 ₹1,79,900 | 1,49,000 ₹1,49,000 Lowest | 1,88,700 ₹1,88,700 |
| 2.00 | Design, fabrication, installation, testing and commissioning of Electric Control Panel with built in fault analyzer suitable for running 20 H.P. Submersible Pumpset. The panel should be dust and vermin proof fabricated out of 14/16 SWG CR sheet and provision for fixing it on the wall or the ground with the help of anchoring bolts should be made. The Panel should be sturdy enough for vibration free operation and should be equipped with suitable locking / sealing arrangements. The structure should be provided suitable entry and exit holes for incoming and outgoing cables. The panel is to be given two coats of anti-rust primer and two coats of steel grey enamel paint. The panel should have equipped with following components / features: -
1. The panel should be fitted with 100 Amps MCCB and a set of RYB indicators at incoming side.
2. Star delta starter: - The panel should be fitted with 01 No. star delta starter comprising of 01 No. 40 Amps. contactor for main supply, 01 No. 40 Amps. contactor for delta supply and 01 No. Air break 40 Amps. contactor for star operation, 01 No. timer for changing over the supply of motor from star to delta, 02 No.s push buttons for start and stop operation of motor. 01 No. MCB 10 Amps. for the protection of internal control wiring. A neat and clean internal control wiring should be made with flexible, copper cables to complete the star delta circuit of outgoing supply.
3. Protection device: - The panel is fitted with protection devices like relay, CT/PT, timer, fault analyzer with capacity to protect motor by isolating the power supply of motor de-energizing the starter/ panel from electro-mechanical faults which may otherwise damage the motor windings like single phasing, under voltage, over voltage, unbalanced voltage, reverse phasing, over current / over load, unbalanced current / load, short circuiting.
The panel shall also be provided with ammeter and voltmeter of appropriate capacity. All the equipments used i.e. contactors, relays, MCCB etc. used should be of standard make. | 1 | Job | 75,000 ₹75,000 | 57,000 ₹57,000 Lowest | 66,600 ₹66,600 |
| 3.00 | Providing, installation, testing and commissioning of 63 kVA copper wound, oil cooled, manually operated voltage stabilizer with input voltage range (160 V to 400 V) and output voltage range (400 V ± 10%) and frequency 50 Hz ± 3% for irrigation Tubewell. The stabilizer should be mounted on unidirectional wheels. The stabilizer assembly should comprise of core made of silicon steel wound with copper coil conductor of appropriate quality confirming to BIS with di-electric oil of proper value for cooling stabilizer assembly. The job also includes P/F 01 No. changeover/by-pass switch of 100 Amps for by-passing the voltage regulation mechanism and to run the system on main incoming supply in case there is a problem in voltage stabilizer. The job also includes P/F of 01 No. 100 Amp M.C.C.B. on output side & other required fittings. The job also includes providing and laying of 16 mm sq. multi strand single core copper cable as per site requirement for making connection of Voltage Stabilizer to Electric Control Panel after thimbling the cable ends. The job includes cost of material, labour, carriage, tools and tackles. | 1 | Job | 1,50,000 ₹1,50,000 | 1,86,000 ₹1,86,000 | 1,29,500 ₹1,29,500 Lowest |
| 4.00 | Recapitalization of63 kVAElectric Transformer to restore its operational capacity by way of dismounting it from its installed position and then shifting it to workshop by means of manual / mechanical transport. The job includes dismantling of transformer at workshop andextractionof old burnt out/damaged parts and then P/F with new L.V. Bush= 02No., L.V. Bush Rod= 01No., H.V. leg coil with insulation (Al)= 02No., L.V. leg coil with insulation (Al) = 02 No., Gasket Set, Sundry items andInsulation Material. The job also includes assembling the transformer and topping up with transformer oil in the oil tank and then shifting back to site and remounting it back and then making the connections and testing it on full load. The job includes cost of material, labour, carriage, tools and tackles.(Complete Job). | 1 | Job | 35,000 ₹35,000 | 53,000 ₹53,000 | 31,820 ₹31,820 Lowest |
Tender Value
₹5.6 L
EMD Value
₹11,260
Closing Date
20 Dec 2025, 2:00 pmClosed
Executive Engneer TWID, jammu
Executive Engneer TWID, jammu
Providing Fitting of New Submersible Pumpset (15000 GPH 40 m Head 20 H.P induction motor Voltage Stabilizer 63 kVA and Electric Control Panel 20 HP 3 Phase Star Delta and Recapitalization of 63 kVA Electric Transformer at Tube Well Chatha D in Bloc
2025_IFC_297936_1
eNit no. 23 of 2025-26
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
45 days
jammu
Please refer Tender documents.
2 documents required · 2 mandatory
₹600
Executive Engneer TWID, jammu
₹11,260
Yes
1 Jan 2026
12 Dec 2025
22 Dec 2025
12 Dec 2025
20 Dec 2025
12 Dec 2025
Select, Excess (+), Less (-) Less (-)
Tender Inviting Authority: Executive Engineer, Tube-Well Irrigation Division, Jammu.
Name of Work: Providing/Fitting of New Submersible Pumpset (15000 GPH X 40 m Head, 20 H.P. induction motor), Voltage Stabilizer (63 kVA) and Electric Control Panel (20 H.P., 3 Phase Star Delta), and Recapitalization of 63 kVA Electric Transformer at Tubewell Chatha-D in Block Satwari, Jammu
Contract No: e-NIT No. 23 of 2025-26.
Name of the Bidder/ Bidding Firm / Company :
Sl. No. Item Description Item Code / Make Quantity Units Estimated Rate in Rs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT in Rs. P TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words
1 Providing, Lowering, Installation, Testing and Commissioning of Submersible Pumpset at Tubewell mentioned above having capacity of (15,000 GPH) x (40m Head) coupled with 3 phase,400 V ± 10%, 50 Hz ± 3% AC supply, copper wound squirrel cage induction submersible motor of20H.P. along with 02 No. 150mm dia. flanged column pipes assembly along with other allied materials/equipments required during lowering of submersible pumpset. The job also includes P/L of 25 mtr-35 mm sq. 3.5 core aluminum armored cable for connection of control panel to electric transformer and 45 mtr-10 mm sq 3 core submersible cable for connection of panel to the submersible pumpset. The job also includes utilizing the existing 03 No. 150 mm dia. flanged column pipes, bend and delivery pipe at site after necessary priming and painting with black enamel paint.The job also includes providing and fitting of 200 Amp, 415 Volt main switch with HRC Fuse of reputed make. The job includes cost of material, labour, carriage, tools and tackles (Complete Job in all respects). Electro-mechanical accessories used should beof genuine/reputed make conforming to latest IS code. BI01010001010000000000000515BI0100001112222 1 Job 0 Excess(+) Full Conversion INR 1.01 Supplying, Conveying and fixing spls. Including eart item1 123.223 Nos
2 Design, fabrication, installation, testing and commissioning of Electric Control Panel with built in fault analyzer suitable for running 20 H.P. Submersible Pumpset. The panel should be dust and vermin proof fabricated out of 14/16 SWG CR sheet and provision for fixing it on the wall or the ground with the help of anchoring bolts should be made. The Panel should be sturdy enough for vibration free operation and should be equipped with suitable locking / sealing arrangements. The structure should be provided suitable entry and exit holes for incoming and outgoing cables. The panel is to be given two coats of anti-rust primer and two coats of steel grey enamel paint. The panel should have equipped with following components / features: - 1. The panel should be fitted with 100 Amps MCCB and a set of RYB indicators at incoming side. 2. Star delta starter: - The panel should be fitted with 01 No. star delta starter comprising of 01 No. 40 Amps. contactor for main supply, 01 No. 40 Amps. contactor for delta supply and 01 No. Air break 40 Amps. contactor for star operation, 01 No. timer for changing over the supply of motor from star to delta, 02 No.s push buttons for start and stop operation of motor. 01 No. MCB 10 Amps. for the protection of internal control wiring. A neat and clean internal control wiring should be made with flexible, copper cables to complete the star delta circuit of outgoing supply. 3. Protection device: - The panel is fitted with protection devices like relay, CT/PT, timer, fault analyzer with capacity to protect motor by isolating the power supply of motor de-energizing the starter/ panel from electro-mechanical faults which may otherwise damage the motor windings like single phasing, under voltage, over voltage, unbalanced voltage, reverse phasing, over current / over load, unbalanced current / load, short circuiting. The panel shall also be provided with ammeter and voltmeter of appropriate capacity. All the equipments used i.e. contactors, relays, MCCB etc. used should be of standard make. BI01010001010000000000000515BI01000011123333 1 Job 0 Excess(+) Full Conversion INR 1.01 Supplying, Conveying and fixing spls. Including eart item1 123.223 Nos
3 Providing, installation, testing and commissioning of 63 kVA copper wound, oil cooled, manually operated voltage stabilizer with input voltage range (160 V to 400 V) and output voltage range (400 V ± 10%) and frequency 50 Hz ± 3% for irrigation Tubewell. The stabilizer should be mounted on unidirectional wheels. The stabilizer assembly should comprise of core made of silicon steel wound with copper coil conductor of appropriate quality confirming to BIS with di-electric oil of proper value for cooling stabilizer assembly. The job also includes P/F 01 No. changeover/by-pass switch of 100 Amps for by-passing the voltage regulation mechanism and to run the system on main incoming supply in case there is a problem in voltage stabilizer. The job also includes P/F of 01 No. 100 Amp M.C.C.B. on output side & other required fittings. The job also includes providing and laying of 16 mm sq. multi strand single core copper cable as per site requirement for making connection of Voltage Stabilizer to Electric Control Panel after thimbling the cable ends. The job includes cost of material, labour, carriage, tools and tackles. BI01010001010000000000000515BI010000111244442332 1 Job 0 Excess(+) Full Conversion INR 1.01 Supplying, Conveying and fixing spls. Including eart item1 123.223 Nos
4 Recapitalization of63 kVAElectric Transformer to restore its operational capacity by way of dismounting it from its installed position and then shifting it to workshop by means of manual / mechanical transport. The job includes dismantling of transformer at workshop andextractionof old burnt out/damaged parts and then P/F with new L.V. Bush= 02No., L.V. Bush Rod= 01No., H.V. leg coil with insulation (Al)= 02No., L.V. leg coil with insulation (Al) = 02 No., Gasket Set, Sundry items andInsulation Material. The job also includes assembling the transformer and topping up with transformer oil in the oil tank and then shifting back to site and remounting it back and then making the connections and testing it on full load. The job includes cost of material, labour, carriage, tools and tackles.(Complete Job). BI01010001010000000000000515BI0100001112444425486 1 Job 0 Excess(+) Full Conversion INR 1.01 Supplying, Conveying and fixing spls. Including eart item1 123.223 Nos
Total in Figures 4 Construction of chamber for 100mm sluice plates item5 10 Nos
Quoted Rate in Figures Select
Quoted Rate in Words
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.44 MB
BOQ_965597.xls
BOQ • 0.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .