Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.5 LAccepted-AOC C 187 NIRMAN VIHAR DELHI 92 | L1 | Accepted-AOC Being a lowest bidder | |
| 2 | L2₹34.9 L+₹4.4 L (14.5%)Rejected-Finance 15 CP COLONY MORAR GWALIOR MP 474 006 | GWALIOR | GWALIOR | MADHYA PRADESH | 474006 | L2 | Rejected-Finance Not a lowest tender | |
| 3 | L3₹39.1 L+₹8.6 L (28.4%)Rejected-Finance 227 NEW GANESH VIHAR ADARSH MILL ROAD GHOSIPURA LASHKAR GWALIOR 474012 M P | GWALIOR | MADHYA PRADESH | 474012 | L3 | Rejected-Finance Not a lowest tender | |
| 4 | L4₹41.9 L+₹11.4 L (37.3%)Rejected-Finance | L4 | Rejected-Finance Not a lowest tender |
Tender Value
₹42 L
EMD Value
₹84,000
Closing Date
27 Mar 2023, 6:00 pmClosed
GE AF TA GWALIOR
GE AF TA GWALIOR 474020
REPAIRS/MAINT OF LT DISTRIBUTION SYSTEMS, POWER FACTOR CONTROL PANELS AND VITAL AIRFIELD DISTRIBUTION SYSTEM IN TECH AREA AT AF STATION GWALIOR
2023_MES_583164_1
8900/1454/GWL/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AF STN Gwalior
As per tender documents
7 documents required · 7 mandatory
₹500
GE AF TA GWALIOR
₹84,000
Yes
11 May 2023
27 Feb 2023
4 Apr 2023
27 Feb 2023
27 Mar 2023
14 Mar 2023
Amount
M&L for fabrication/welding/Jointing work in existing LT Panel by providing new hinges in place of defective hinges, replacement of locking arrrangement of external door, replacement of main door gasket, replacement of rusted sheet cover including cutting, bending, Welding/soldering and refixing properly at site. Servicing and maintenance of the panel by taking out the incoming connection and all outgoing connection and outgoing cables of the panel and fixing a fresh with proper crimping/tapeing, lugs/connector, cable glande including doing all necessary wiring in the panel. Note -Excavation and earth work wherever necessary is deemed to be inculded alongwith the cost and MS Sheet will be measured and paid seperately under respective item
Dismantling, taking down and removing the old existing un serviceable non-functional/broken hinges of any description and in any position of existing feeder pillar boxes/panel boards etc and supply and fixing new cold rolled medium weight mild steel hinges in position as per existing requirement with necessary spot welding, screwing etc including making necessary adjustment for free and smooth movement of panel and locking arrangements complete all as specified and directed.
Taking out old unserviceable insulator from LT panel boards, supply, fixing & testing conical/single bus bar system epoxy insulator including nuts, bolts and washers suitable for LT 415 Volts, 50 Hz AC supply for mounting of bus bars in LT panels/feeder pillar boxes complete all as specified and directed
Replacement of existing unserviceable/damaged part/portion of the existing feeder pillar box/ panel boards with supply and fixing new part or portion fabricated out of 3mm thick MS sheet in position including making necessary adjustments and alignments to make the existing feeder pillar box/panel board body to required shape and size(s) and MS sheet painted both sides with two coats of synthetic enameled paint over a coat of red oxide primer with necessary filler coating complete all as specified ant directed.
Disconnecting and taking out old existing unserviceable Phase indicator lamps and supply, fixing, connecting and, testing LED type Phase indicator lamp with showing red, yellow and green colours of 22.5mm dia fixed to monitor on LT panel board suitable for 240 Volts AC supply and making connections with using suitable size copper cables wires and lugs complete all as specified and directed.
M & L for preparation of old steel surfaces of steel/LT panel boards/feeder pillar boxes of size upto 1000mm x 1100mm x 450mm of any description & any position including removing disintegrated/detoriating part of paint and applying filler coat to obtain smooth surfaces and applying a coat of synthetic enamel paint using spray machine to obtain smooth finish to the entire satisfaction of Engineer-in-Charge complete all as specified and directed.
All as per items No 7 above but of size above 1000mm x 1100mm x 450mm less than 1300mm x 1450mm x 450mm complete all as specified and directed.
All as per item No 7 above do- but size of above 1300mm x 1450mm x 450mm complete all as specified and directed.
Taking down existing old unserviceable LT Panel and Supply, Install, Testing and Commissioning, factory made, CPRI approved, totally enclosed, IP 54 dust, weather and vermin proof, CRCA sheet out door LT Panel for 415V, 3 phase 4 wire , 50 Hz AC system with TPN tinned copper bus bar of rating 1.5 times that of controlling MCCB supported on F class DMC/FRP insulator with short circuit withstand capacity 21 MVA for 1 second, neutral bus bar of capacity of that of phase bus bar , general construction confirming to IS-8623/93, having bottom base channel of MS section not less than 75mm x 75 mm x 5 mm , entire panel having common aluminium earth bar of size 25mm x 5mm at the rear with 2 Nos earth stud, solid connection from main bus bar to switchgears with required size (minimum 1.5 Sqmm) PVC insulated copper conductor cable , cable alleys, cable gland plates in two half inculding LED indicating lamp for all phases and mounted on suitable PCC foundation for the complete panel base with following detailed specification, control and accessories complete all as specified below and as directed:-
The panel board shall be fabricated from the reputed CPRI approved firm and shall be suitable to accommodate the following complete all as specified and directed :- OUTER SHELL :- The outer shell shall be made of min 3 mm thick CRCA sheet supported on MS angle section 75mm x 75 mm x 5 mm frame with openable front & back with concelaed hinges , single door system, lockable/ openable by by keys from both sides, having flush pattern fancy locks, louvers & air vent with gasket for natural flow of air. The bottom of the outer shell contains a detachable plate with hung provision for entry of armoured cable with adequite size glands. Provision of earthing studs at bottom and threaded lifting lugs of suitable size at top to lift the feeder pillar box safely shall be made. Computer cut self adhesive vinly danger notice plate having conventional symbol of bone and skull shall be provided.
INNER SHELL :- Inner shell made of 2.0 mm thick CRCA sheet compartmentalized to accomodate each control gear, front openable, single door system lockable/openable with "U' type gasket to make the inner shell completely vermin proof having chromium plated locks (2 Nos in each compartment.) All control wiring shall be with not less than 1.5 Sqmm multistranded copper conductor and shall be properly bunched. tied, ferruled for proper identification and crimped with adequite size of lugs. The cubical shall have a bottom channel of size 75x75x5 mm duly painted with zinc based primer. A detachable predrilled gland plate of thickness 3.15 mm should be used at the bottom, . An inspection lamp with 10 Watt LED Lamp shall be fitted on top side of inner shell. (A) Incoming :- (i) MCCB 4P, 320A, adjustable thermal and magnetic setting, Ics=100%Icu, 16 KA -01 No. (B) Out going :- (a) MCCB 4P, 100 A,adjustable thermal and magnetic setting, Ics=100%Icu 16 KA - 03 Nos (b) MCCB 4P, 63 A, adjustable thermal and magnetic setting, Ics=100%Icu 16 KA - 02 Nos. (c) The following items are provided in each compartment :- (i) Digital Voltmeter - 01 No (ii) Digital Ammeter - 01 No. (iii) Set of three Indication LED (RYB) Lamp. Note :- All incoming and outgoing feeder shall be marked with rating of MCCB on steel plate.
Taking down existing old unserviceable LT Panel and Supply, Install, Testing and Commissioning, factory made, CPRI approved, totally enclosed, IP 54 dust, weather and vermin proof, CRCA sheet out door LT Panel for 415V, 3 phase 4 wire , 50 Hz AC system with TPN tinned copper bus bar of rating 1.5 times that of controlling MCCB supported on F class DMC/FRP insulator with short circuit withstand capacity 21 MVA for 1 second, neutral bus bar of capacity of that of phase bus bar , general construction confirming to IS-8623/93, having bottom base channel of MS section not less than 75mm x 75 mm x 5 mm , entire panel having common aluminium earth bar of size 25mm x 5mm at the rear with 2 Nos earth stud, solid connection from main bus bar to switchgears with required size (minimum 1.5 Sqmm) PVC insulated copper conductor cable , cable alleys, cable gland plates in two half inculding LED indicating lamp for all phases and mounted on suitable PCC foundation for the complete panel base with following detailed specification, control and accessories complete all as specified below and as directed:-
The panel board shall be fabricated from the reputed CPRI approved firm and shall be suitable to accommodate the following complete all as specified and directed :- OUTER SHELL :- The outer shell shall be made of min 3 mm thick CRCA sheet supported on MS angle section 75mm x 75 mm x 5 mm frame with openable front & back with concelaed hinges , single door system, lockable/ openable by by keys from both sides, having flush pattern fancy locks, louvers & air vent with gasket for natural flow of air. The bottom of the outer shell contains a detachable plate with hung provision for entry of armoured cable with adequite size glands. Provision of earthing studs at bottom and threaded lifting lugs of suitable size at top to lift the feeder pillar box safely shall be made. Computer cut self adhesive vinly danger notice plate having conventional symbol of bone and skull shall be provided.
INNER SHELL :- Inner shell made of 2.0 mm thick CRCA sheet compartmentalized to accomodate each control gear, front openable, single door system lockable/openable with "U' type gasket to make the inner shell completely vermin proof having chromium plated locks (2 Nos in each compartment.) All control wiring shall be with not less than 1.5 Sqmm multistranded copper conductor and shall be properly bunched. tied, ferruled for proper identification and crimped with adequite size of lugs. The cubical shall have a bottom channel of size 75x75x5 mm duly painted with zinc based primer. A detachable predrilled gland plate of thickness 3.15 mm should be used at the bottom, . An inspection lamp with 10 Watt LED Lamp shall be fitted on top side of inner shell. (A) Incoming :- (i) MCCB 4P, 320A, adjustable thermal and magnetic setting, Ics=100%Icu, 36 KA -01 No. (B) Out going :- (a) MCCB 4P, 200 A,adjustable thermal and magnetic setting, Ics=100%Icu 25 KA - 01 Nos (b) MCCB 4P, 100 A, adjustable thermal and magnetic setting, Ics=100%Icu 16 KA - 01 Nos. (c) MCCB 4P, 63 A, adjustable thermal and magnetic setting, Ics=100%Icu 16 KA - 02 Nos (d) The following items are provided in each compartment :- (i) Digital Voltmeter - 01 No (ii) Digital Ammeter - 01 No. (iii) Set of three Indication LED (RYB) Lamp. Note :- All incoming and outgoing feeder shall be marked with rating of MCCB on steel plate.
Taking down existing old unserviceable LT Panel and Supply, Install, Testing and Commissioning, factory made, CPRI approved, totally enclosed, IP 54 dust, weather and vermin proof, CRCA sheet out door LT Panel for 415V, 3 phase 4 wire , 50 Hz AC system with TPN tinned copper bus bar of rating 1.5 times that of controlling MCCB supported on F class DMC/FRP insulator with short circuit withstand capacity 21 MVA for 1 second, neutral bus bar of capacity of that of phase bus bar , general construction confirming to IS-8623/93, having bottom base channel of MS section not less than 75mm x 75 mm x 5 mm , entire panel having common aluminium earth bar of size 25mm x 5mm at the rear with 2 Nos earth stud, solid connection from main bus bar to switchgears with required size (minimum 1.5 Sqmm) PVC insulated copper conductor cable , cable alleys, cable gland plates in two half inculding LED indicating lamp for all phases and mounted on suitable PCC foundation for the complete panel base with following detailed specification, control and accessories complete all as specified below and as directed:-
The panel board shall be fabricated from the reputed CPRI approved firm and shall be suitable to accommodate the following complete all as specified and directed :- OUTER SHELL :- The outer shell shall be made of min 3 mm thick CRCA sheet supported on MS angle section 75mm x 75 mm x 5 mm frame with openable front & back with concelaed hinges , single door system, lockable/ openable by by keys from both sides, having flush pattern fancy locks, louvers & air vent with gasket for natural flow of air. The bottom of the outer shell contains a detachable plate with hung provision for entry of armoured cable with adequite size glands. Provision of earthing studs at bottom and threaded lifting lugs of suitable size at top to lift the feeder pillar box safely shall be made. Computer cut self adhesive vinly danger notice plate having conventional symbol of bone and skull shall be provided.
INNER SHELL :- Inner shell made of 2.0 mm thick CRCA sheet compartmentalized to accomodate each control gear, front openable, single door system lockable/openable with "U' type gasket to make the inner shell completely vermin proof having chromium plated locks (2 Nos in each compartment.) All control wiring shall be with not less than 1.5 Sqmm multistranded copper conductor and shall be properly bunched. tied, ferruled for proper identification and crimped with adequite size of lugs. The cubical shall have a bottom channel of size 75x75x5 mm duly painted with zinc based primer. A detachable predrilled gland plate of thickness 3.15 mm should be used at the bottom, . An inspection lamp with 10 Watt LED Lamp shall be fitted on top side of inner shell. (A) Incoming :- (i) MCCB 4P, 160A, adjustable thermal and magnetic setting, Ics=100%Icu, 16 KA -01 No. (B) Out going :- (a) MCCB 4P, 100 A,adjustable thermal and magnetic setting, Ics=100%Icu 16 KA - 01 Nos (b) MCCB 4P, 63A, adjustable thermal and magnetic setting, Ics=100%Icu 25 KA - 02 Nos. (C) The following items are provided in each compartment :- (i) Digital Voltmeter - 01 No (ii) Digital Ammeter - 01 No. (iii) Set of three Indication LED (RYB) Lamp. Note :- All incoming and outgoing feeder shall be marked with rating of MCCB on steel plate.
Taking down existing old unserviceable LT Panel and Supply, Install, Testing and Commissioning, factory made, CPRI approved, totally enclosed, IP 54 dust, weather and vermin proof, CRCA sheet out door LT Panel for 415V, 3 phase 4 wire , 50 Hz AC system with TPN tinned copper bus bar of rating 1.5 times that of controlling MCCB supported on F class DMC/FRP insulator with short circuit withstand capacity 21 MVA for 1 second, neutral bus bar of capacity of that of phase bus bar , general construction confirming to IS-8623/93, having bottom base channel of MS section not less than 75mm x 75 mm x 5 mm , entire panel having common aluminium earth bar of size 25mm x 5mm at the rear with 2 Nos earth stud, solid connection from main bus bar to switchgears with required size (minimum 1.5 Sqmm) PVC insulated copper conductor cable , cable alleys, cable gland plates in two half inculding LED indicating lamp for all phases and mounted on suitable PCC foundation for the complete panel base with following detailed specification, control and accessories complete all as specified below and as directed:-
The panel board shall be fabricated from the reputed CPRI approved firm and shall be suitable to accommodate the following complete all as specified and directed :- OUTER SHELL :- The outer shell shall be made of min 3 mm thick CRCA sheet supported on MS angle section 75mm x 75 mm x 5 mm frame with openable front & back with concelaed hinges , single door system, lockable/ openable by by keys from both sides, having flush pattern fancy locks, louvers & air vent with gasket for natural flow of air. The bottom of the outer shell contains a detachable plate with hung provision for entry of armoured cable with adequite size glands. Provision of earthing studs at bottom and threaded lifting lugs of suitable size at top to lift the feeder pillar box safely shall be made. Computer cut self adhesive vinly danger notice plate having conventional symbol of bone and skull shall be provided.
INNER SHELL :- Inner shell made of 2.0 mm thick CRCA sheet compartmentalized to accomodate each control gear, front openable, single door system lockable/openable with "U' type gasket to make the inner shell completely vermin proof having chromium plated locks (2 Nos in each compartment.) All control wiring shall be with not less than 1.5 Sqmm multistranded copper conductor and shall be properly bunched. tied, ferruled for proper identification and crimped with adequite size of lugs. The cubical shall have a bottom channel of size 75x75x5 mm duly painted with zinc based primer. A detachable predrilled gland plate of thickness 3.15 mm should be used at the bottom, . An inspection lamp with 10 Watt LED Lamp shall be fitted on top side of inner shell. (A) Incoming :- (i) MCCB 4P, 320A, adjustable thermal and magnetic setting, Ics=100%Icu, 36 KA -01 No. (B) Out going :- (a) MCCB 4P, 160 A,adjustable thermal and magnetic setting, Ics=100%Icu 16 KA - 01 Nos (b) MCCB 4P, 100 A, adjustable thermal and magnetic setting, Ics=100%Icu 16 KA - 01 Nos. (c) MCCB 4P, 63 A, adjustable thermal and magnetic setting, Ics=100%Icu 16 KA - 01 Nos (d) MCCB 4P, 32 A, adjustable thermal and magnetic setting, Ics=100%Icu 10 KA - 05 Nos. (e) The following items are provided in each compartment :- (i) Digital Voltmeter - 01 No (ii) Digital Ammeter - 01 No. (iii) Set of three Indication LED (RYB) Lamp. Note :- All incoming and outgoing feeder shall be marked with rating of MCCB on steel plate.
Taking down existing old unserviceable LT Panel and Supply, Install, Testing and Commissioning, factory made, CPRI approved, totally enclosed, IP 54 dust, weather and vermin proof, CRCA sheet out door LT Panel for 415V, 3 phase 4 wire , 50 Hz AC system with TPN tinned copper bus bar of rating 1.5 times that of controlling MCCB supported on F class DMC/FRP insulator with short circuit withstand capacity 21 MVA for 1 second, neutral bus bar of capacity of that of phase bus bar , general construction confirming to IS-8623/93, having bottom base channel of MS section not less than 75mm x 75 mm x 5 mm , entire panel having common aluminium earth bar of size 25mm x 5mm at the rear with 2 Nos earth stud, solid connection from main bus bar to switchgears with required size (minimum 1.5 Sqmm) PVC insulated copper conductor cable , cable alleys, cable gland plates in two half inculding LED indicating lamp for all phases and mounted on suitable PCC foundation for the complete panel base with following detailed specification, control and accessories complete all as specified below and as directed:-
The panel board shall be fabricated from the reputed CPRI approved firm and shall be suitable to accommodate the following complete all as specified and directed :- OUTER SHELL :- The outer shell shall be made of min 3 mm thick CRCA sheet supported on MS angle section 75mm x 75 mm x 5 mm frame with openable front & back with concelaed hinges , single door system, lockable/ openable by by keys from both sides, having flush pattern fancy locks, louvers & air vent with gasket for natural flow of air. The bottom of the outer shell contains a detachable plate with hung provision for entry of armoured cable with adequite size glands. Provision of earthing studs at bottom and threaded lifting lugs of suitable size at top to lift the feeder pillar box safely shall be made. Computer cut self adhesive vinly danger notice plate having conventional symbol of bone and skull shall be provided.
INNER SHELL :- Inner shell made of 2.0 mm thick CRCA sheet compartmentalized to accomodate each control gear, front openable, single door system lockable/openable with "U' type gasket to make the inner shell completely vermin proof having chromium plated locks (2 Nos in each compartment.) All control wiring shall be with not less than 1.5 Sqmm multistranded copper conductor and shall be properly bunched. tied, ferruled for proper identification and crimped with adequite size of lugs. The cubical shall have a bottom channel of size 75x75x5 mm duly painted with zinc based primer. A detachable predrilled gland plate of thickness 3.15 mm should be used at the bottom, . An inspection lamp with 10 Watt LED Lamp shall be fitted on top side of inner shell. (A) Incoming :- (i) MCCB 4P, 100A, adjustable thermal and magnetic setting, Ics=100%Icu, 16 KA -01 No. (B) Out going :- (a) MCCB 4P, 63 A,adjustable thermal and magnetic setting, Ics=100%Icu 16 KA - 01 Nos (b) MCCB 4P, 32 A, adjustable thermal and magnetic setting, Ics=100%Icu 16 KA - 02 Nos (c) The following items are provided in each compartment :- (i) Digital Voltmeter - 01 No (ii) Digital Ammeter - 01 No. (iii) Set of three Indication LED (RYB) Lamp. Note :- All incoming and outgoing feeder shall be marked with rating of MCCB on steel plate.
Supply and fixing in repair copper bus bar with PVC insulated colour sleeves of suitable capacity and length as per existing at site including nut bolts, washers complete all as specified and directe.
Supply and fixing in repair Aluminium bus bar with PVC insulated colour sleeves of suitable capacity and length as per existing at site including nut bolts, washers complete all as specified and directe.
Supply and fix in repair MCCB 4 Pole 250A, 36 KA (Adjustable thermal & magnetic release) complete all as specified and directed.
Supply and fix in repair MCCB 4 Pole 200A, 36 KA (Adjustable thermal & magnetic release) complete all as specified and directed.
Supply and fix in repair 4 Pole 160A, 25 KA (Adjustable thermal & magnetic release) complete all as specified and directed.
Supply and fix in repair MCCB 4 Pole 100A, 25 KA (Adjustable thermal & magnetic release) complete all as specified and directed.
Supply and fix in repair MCCB 4 Pole 63A, 16 KA (Adjustable thermal & magnetic release) complete all as specified and directed.
Supplying ,Laying, jointing and testing XLPE insulated, armoured, heavy duty, aluminum conductor cable 1100 volts grade ,laid in trenches/ducts, floors, fixed to walls etc. complete all as specified and directed for the following sizes :-. (a) 16Sqmm 4 core
(b) 25Sqmm, 4 Core
(c) 35Sqmm, 3.5 Core
(d) 70Sqmm 3.5 Core
(e) 95Sqmm 3.5 Core
(f) 120Sqmm 3.5 Core
(g) 150Sqmm, 3.5 Core
(h) 185Sqmm, 3.5 Core
(j) 240Sqmm, 3.5 Core
Excavation in trenches n exc 1.5 mtr wide and n exc 1.5 mtr depth for foundation and laying of cable and getting out in any type soil etc complete all as specified and directed.
Returning, filling in, including spreading, levelling watering and well ramming in layers n.exc 25cm in soft/loose soil etc complete as specified and directed
M&L for dry river sand in trenches for cable cushioning & protection including spreading, ramming all as specified and directed.
Removing excavated material to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5 mtr above the starting point.
Supply & Laying precast PCC cable concrete cable cover LV low voltage type -I flat size 250 mm x 150 mm x 40 mm complete all as specified and directed by Engr-in-charge.
M&L for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meter deep below normal ground level) with top edge of the plate not less than 1.5 meter below normal ground level, connected to galvanized iron strip of 25 x 4mm as earth continuity conductor by means of bolts nuts, check nuts and washers of galvanised iron or steel all as shown in electric plate No 5, of SSR Part - I, 2009 & all as specified, testing on completion including provision of earth lead protected by 40 mm dia GI pipe medium grade & watering pipe 20 mm medium grade including all excavation and earth work in any type of soil, PCC pit (1:3:6) type C1 with RCC cover, charcoal, salt, funnel etc complete including making good disturbed surfaces of wall, floor.
Note : ( i ) The rate is inclusive of cost of earthing lead of 25 x 4mm and GI protection pipe 40mm size upto 7.5 m length from the top edge of the GI plate electrode.. (ii) Irrespective of what is shown on plate No 5 of SSR Part-I /2009, the earthing pit shall be precasted PCC (1:3:6) type C1 and the cover of earthing pit shall be of precast RCC (1 :2 : 4) type B1 with suitable handle fushed with surface all as specified. (iii) The rates quoted by the contractor is deemed to be inclusive of cost of MS sheet of size 300mmX 300mmX3mm size, fixed with necessary nuts and bolts on angle iron of size 40X40x5mm & length 60cm and grouted in the ground with PCC (1:3:6) using 20mm grade stone masonery of size 200mmX200mmX250mm including necessary earth work.for marking the result and its purpose of use
M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc, as required of size 32 x 6mm galvanised iron strip complete all as specified and directed.
S&F GI Pipe light grade 50 mm for road crossing/ on pole/ on wall for protection of LT Cable.
M&L bus bar box made out of 2 mm thick MS sheet, 3 phase, 4 wire, 415 Volts AC supply, outdoor cubical type, dust and vermin proof, floor block mounting type suitable for outdoor applications of size 600mmx600mmx450mm, using 40mm x 40mm x 5 mm angle iron frame with shutter and locking arrangement painted with two coats of synthetic enamel paint of approved colour over a coat of red oxide primer(internally and externally)for box, height above ground 600mm and grouted 300 mm below ground, legs of frame shall be grouted in PCC 1:2:4 (size 300x300x300mm block) and complete including 40mmx10mm-04 nos 500mm long aluminium busbar fixed on insulators with proper colour coding, including making connections with cable of size 300 sqmm with necessary lugs and chromium plated glands complete all as specified and directed.
Disconnecting, taking out and removing old existing unserviceable underground, LT cable of any description, any size and in any position complete including taking down protection pipe etc all as specified and directed for the following size of cables :- (a) 10 Sqmm to 35 Sqmm of any core Note :- 1. Excavation, earth work and other works releated to restoration of power supply will be measured and paid separately under relevant item of Sch 'A'.
(b) 50 Sqmm to 95 Sqmm 3.5 core
(c ) 120 Sqmm to 185 Sqmm 3.5 Core
(d) 240 Sqmm to 400 Sqmm 3.5 Core
M&L boring of holes under road, pavement, hard standing by manually depth not less than 75 cm for insertion of GI Pipe of size 80 mm bore light grade for short length complete all as specified and directed. Note :- GI pipe 80 mm dia light grade shall be measured and paid separately under relevant item of Schedule 'A'.
Supply and fixing of GI Pipe 80 mm dia light grade for cable protection complete all as specified and directed. Make:- Surya/Jindal/Tata
Laying only old retrieved serviceable bricks for cable protection with axis of the bricks perpendicular to the axis of the cable of any description as obtained from dismantling of the cable complete all as specified and directed.
Re-laying, jointing and testing of serviceable retrieved LT cable from item No. 1 above (after thorough inspection of cable) XLPE / PVC insulated, armoured, heavy duty, aluminum conductor cable 1100 Volts grade of any description, laid in trenches/ducts, floors, fixed to walls etc. complete all as specified and directed for the following sizes :- (a) 10 Sqmm to 35 Sqmm any core
(b) 50 Sqmm to 95 Sqmm 3½ core
(c) 120 Sqmm to 185 Sqmm 3½ core
(d) 240 Sqmm to 400 sqmm 3½ core
Supplying, fixing, jointing and testing for provision of straight through joints Heat shrinkable type, suitable for XLPE, LT Cable, 1100 Volts grade, for the following sizes of cables all as specified and directed. (a) 25 Sqmm to 50 Sqmm 3½ core
(b) 70 -150 Sqmm 3½ core
(c) 185 -400 Sqmm 3½ core
Carrying out periodical servicing, testing of fire alarm system complete conventional/Addressable for MAFI buildings single or multi stores having many no of detectors and accessores, controled through one or more control panel of anly loop for functioning of the purpose installted with all accessories, such as MCP, Hooter, Detectors etc for finding out defects if any or its serviceablity all as specifed and directed. Note :- Functioning Test will be carried out before and after repair of the system.
Dismantling of air circuit breaker of capacity from 1000 Amps of any pole/make/model from the panel, checking, servicing, cleaning of breaker with CRC-226, removal of old grease and re-greasing with recommended grease, checking the condition of moving and fixed contacts, checking the tripping mechanism, tripping of ACB manually through voltmetric release, adjust freeness of DN and volt metric release trip rod, checking the proper tightening of hardware, checking presence of all circlips, alignment of jaw contact with cradle terminals, checking the condition of ACB wiring, adjusting the gap between hylam sheet and side plate, checking the condition of arc chutes, under voltage relay, shunt release, auxillary contact, checking the release by secondary injection for O/L, S/C, E/F, setting of release as per the load, Checking the healthy ness of the CTs, complete all as specified and directed. Note :- Spares shall be measured and fwd separately under appropriate item in schedule as supply only. Note :- (Make ABB) and the same to be maintained by the techinesion/mechanic of the ABB
M&L for preventive maintenance and routine servicing of Servo Voltage Stabilizer 75/100 KVA, 3 Phase including opening of top enclosure checking the condition/serviceablity of oil, checking di-electric strength of oil, checking the moving contacts, reomiving carbonization, cleaning etc, greasing in moving parts as required, checking of complete electrical system/control wiring, checking of voltage stabilization accuracy complete accessories like Ammeter, Voltmeter, by-pass switch, up/down switches etc all as directed by Engr-in-charge and submit a comprehensive test report on state of stabilizer
M/s Anupam Construction Co.
M/s KKPARASHAR
M/S Pramod Kumar Jain
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .