CONSTRUCTION 4 NOS. DOCTOR ROOM IN CIVIL HOSPITAL AT FATEHABAD (PDG. E.I. INTERNAL ONLY).
2020_HRY_150992_3
PWD/Elect-GGN/Elect-HSR/100081
Open Tender
Electrical Works
Works
120 days
Hisar
Please refer Tender documents.
2 documents required · 2 mandatory
₹500
₹2,010
24 Feb 2021
21 Dec 2020
30 Dec 2020
21 Dec 2020
29 Dec 2020
21 Dec 2020
Amount
Main Switches Supply and erection of metal clad switches / B.D.Bs with rag bolts on wall or on existing angle iron board / pedestal including bonding to earth and necessary connections. (HSR 31.12) (a). i) xvi) Triple pole switch with neutral link 100 amp. 415 Volts Cat-A
Supply & erection of MS angle iron frame duly welded for housing MS sheet & main switches etc. on it, fixed on wall by means of suitable size of rag bolts with cement concrete, duly painted with three coats of approved paint including one coat of red oxide (HSR 31.13). i) ii) Size 40 mm x 40 mm x 6 mm
M.S.Sheet (HSR 31.14): i) Supply and erection of 3 mm thick mild steel sheet duly welded on existing M.S. angle iron frame for fixing the main switches etc. as required, duly painted with three coats of approved paint including one coat of red oxide.
Miniature Circuit Breaker and Isolator: Supply and erection of miniature circuit breaker / isolator 240 /415 V in the existing distribution board including making necessary connections. (HSR 31.17) ii) SP MCB 6 amp. To 32 amp
x) TPN MCB 40 amp. to 63 amp.
Supply and erection of Fittings and Accessories. (HSR 31.18) xi) Bakielite angle/ straight button holder large size
xii) Switch 5 amp. On existing sheet.
xiii) Wall socket 5 amp. On existing sheet.
xxiv) Erection only of 1x40 watts or 2x40 watts 1220 mm long / 1x20 watts or 2x20 watts ,610 mm long fluorescent tube fitting directly on wall including necessary connections with 0.75 sqmm ( 24 / 0.20 mm ) PVC copper flexible cable for connecting the tube with the adjacent point.
xxvi) Supply and erection of hexegonal M.S. box 1.60 mm thick having each side 8 cms, 7.5 cms deep, top covered with M.S. lid by means of screws including 10mm dia 30cm long mild steel rod made into suitable suspension hook and erected in R.C.C. slab for erection of fan, the bottom covered with 3mm thick bakelite sheet with suitable holes, painting etc. complete with all labour and material required to complete the job.
Erection and carriage of fans. (HSR 31.20): i) Erection of ceiling fan complete with necessary earthing of fan and regulator including carriage from local railway station/Goods transport/PWD store to the site of work
Pipe Laying: Supply and erection of pipe for wiring purposes including bends inspection boxes etc. where necessary and painting as required.(HSR 31.21). i) xxi) Heavy gauge welded conduit pipe 20 mm dia 1.60 mm thickness flushed.
xxii) Heavy gauge welded conduit pipe 25 mm dia 1.60 mm thickness flushed.
Earthing (HSR 31.22): i) Earthing with GI earth pipe 4.5 m long and 40 mm dia with masonry enclosure on the top etc. as required . .
ii) Extra for using salt and charcoal / coke for pipe earth electrode as required.
xi) Pdg. and fixing 25 mm x 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode as required
xii) Pdg. and laying earth connections from earth electrode with 4.00 mm dia G.I. wire in 15 mm dia G.I. pipe from earth electrode as required .
PVC Insulated wiring in recessed conduit: Wiring in 1.5 sqmm PVC insulated copper conduct cable in 1.6 mm thick conduit pipe. (HSR 31.36). i) Fan Point b) Medium Point
c) Long Point
ii) Light Point a) Short Point
b) Medium Point
c) Long Point
vi) Call bell point including MS box of size 180mmx 60 mm deep for call bell. c) Long point
vii) 3 pin 5 amp. Plug point including earthing the 3rd pin etc. a) Short Point
c) Long point
viii) 3 pin 15 amp. Plug point with 4 amp. PVC insulated copper conductor cable including earthing the 3rd pin etc. c) Long point
S/E of PVC unsheathed copper conductor cable single core 1100 volts grad in pipe of suitable size excluding cost and erection of pipe. (HSR 31.40). i) Cable size 1.5 sqm (3/0.81 mm)
iii) Cable size 4 sqm(7/0.85 mm)
iv) Cable size 6 sqm(7/1.05 mm)
S/E of double door sheet steel enclosure distribution board suitable for MCBs and ELCBs recessed in wall including bonding to earth with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-in-Charge of the work. (HSR 31.41). i) vi) 8-way,TP&N (Horizontal)(8+24)
Supply & erection of Socket size rotary step type Electronic regulator for A.C. ceiling fan Anchor make Deluxe model No. 50440 ISI / SSK make PC 561 operated on 120/280 V A.C. Supply complete including cutting of existing Bakelite sheet and making necessary connection etc. upto the entire satisfaction of the Engineer-in-Charge of the work. (HSR 31.55).
Non Schedule items Supply only of AC ceiling fan of 48" (1200 mm) sweep double ball bearing with three nos. aluminium blades with standard acessories supplied by the manufactures of approved make without regulator complete in all respect. Bajaj/ Crompton/ Usha/ Khaitan.
Non Schedule items Supply of 20 W LED batten 4' long complete in all respect.Make: Philips/ Surya/ Bajaj/ Hallonix.
stage.html
html • 0.04 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .