Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance 102 R RESIDENCY PLOT 39 SEC 19 BEHIND HOTEL MALWAN ULWE NODE NAVI MUMBAI | NAVI MUMBAI | MAHARASHTRA | Admitted-Finance |
| 3 | Admitted-Finance PUNE | PUNE | MAHARASHTRA | 410301 | Admitted-Finance |
Tender Value
₹47 L
EMD Value
₹94,000
Closing Date
30 May 2022, 3:00 pmClosed
DIRECTOR IISER PUNE
IISER Pune Dr Homi Bhabha Road , Pashan Pune 411008
Providing Isolation Transformer and dedicated earthing for Biology wing ground,1st and 2nd floor main building IISER Pune
2022_IISRP_689381_1
04/ IISER/PUNE/2022 23
Open Tender
Electrical Works
Works
90 days
IISER PUNE
as per NIT
3 documents required · 3 mandatory
₹1,180
DIRECTOR IISER PUNE
₹94,000
17 Jun 2022
18 May 2022
31 May 2022
18 May 2022
30 May 2022
18 May 2022
Amount
Please Note that Quoted rates are inclusive of all taxes,labor,transportation etc. Nothing extra shall be paid separtely
MV Cable Laying: Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Upto 35 sq. mm
MV Cable Laying: Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Above 185 sq. mm and upto 400 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Upto 35 sq. mm (clamped with 1mm thick saddle)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Above 185 sq. mm and upto 400 sq. mm (clamped with 25/40x3mm MS flat clamp)
Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power flexiable cable of 1.1 KV grade of 1 c x 70 sqmm size direct in ground ( depth more than 150 mm ) including excavation, PVC pipe , protective covering and refilling the trench etc as required & complete.
Laying of one number PVC insulated and PVC sheathed / XLPE power flexiable cable of 1.1 KV grade of 1 c x 95 sqmm size direct in ground ( depth more than 150 mm ) including excavation, PVC pipe , protective covering and refilling the trench etc as required & complete.
MV Cable Jointing & End Termination : Supplying and making indoor end termination with brass compression gland and aluminum / copper lugs, for following size of PVC insulated and PVC /XLPE sheathed , aluminum / copper conductor cables of 1.1kV grade as required. : Size - 3 1/2 C x 240 sq.mm Aluminium ,XLPE Armourd Cable
MV Cable Jointing & End Termination : Supplying and making indoor end termination with brass compression gland and aluminum / copper lugs, for following size of PVC insulated and PVC /XLPE sheathed , aluminum / copper conductor cables of 1.1kV grade as required. : Size - 3 1/2 C x 70 sq.mm Aluminium ,XLPE Armourd Cable
MV Cable Jointing & End Termination : Supplying and making indoor end termination with brass compression gland and aluminum / copper lugs, for following size of PVC insulated and PVC /XLPE sheathed , aluminum / copper conductor cables of 1.1kV grade as required. : Size - 4 C X16 sq.mm Copper ,XLPE Armourd Cable
MV Cable Jointing & End Termination : Supplying and making indoor end termination with brass compression gland and aluminum / copper lugs, for following size of PVC insulated and PVC /XLPE sheathed , aluminum / copper conductor cables of 1.1kV grade as required. : Size - 4 C X10 sq.mm Copper ,XLPE Armourd Cable
MV Cable Jointing & End Termination : Supplying and making indoor end termination with brass compression gland and aluminum / copper lugs, for following size of PVC insulated and PVC /XLPE sheathed , aluminum / copper conductor cables of 1.1kV grade as required. : Size - 4 C X 4 sq.mm Copper ,XLPE Armourd Cable
MV Cable Jointing & End Termination : Supplying and making indoor end termination with brass compression gland and aluminum / copper lugs, for following size of PVC insulated and PVC /XLPE sheathed , aluminum / copper conductor cables of 1.1kV grade as required. : Size - 4 C X 2.5 sq.mm Copper ,XLPE Armourd Cable
MV Cable Jointing & End Termination : Supplying and making indoor end termination with brass compression gland and aluminum / copper lugs, for following size of PVC insulated and PVC /XLPE sheathed , aluminum / copper conductor cables of 1.1kV grade as required. : Size - 3 C X 2.5 sq.mm Copper ,XLPE Armourd Cable
MV Cable Jointing & End Termination : Supplying and making indoor end termination with PVC compression gland and aluminum / copper lugs, for following size of PVC insulated and PVC /XLPE sheathed , aluminum / copper conductor cables of 1.1kV grade as required. : Size - 1 Core x 25 Sq.mm Copper Flexible FLRS Cables ( Green Outersheath )
MV Cable Jointing & End Termination : Supplying and making indoor end termination with brass compression gland and aluminum / copper lugs, for following size of PVC insulated and PVC /XLPE sheathed , aluminum / copper conductor cables of 1.1kV grade as required. : Size - 1 Core x 70 Sq.mm Copper Flexible FLRS Cables ( Green Outersheath )
MV Cable Jointing & End Termination : Supplying and making indoor end termination with PVC compression gland and aluminum / copper lugs, for following size of PVC insulated and PVC /XLPE sheathed , aluminum / copper conductor cables of 1.1kV grade as required. : Size - 1 Core x 10 Sq.mm Copper Flexible FLRS Cables ( Green Outersheath )
MV Cable Jointing & End Termination : Supplying and making indoor end termination with brass compression gland and aluminum / copper lugs, for following size of PVC insulated and PVC /XLPE sheathed , aluminum / copper conductor cables of 1.1kV grade as required. : Size - 4 C X 25 sq.mm Copper ,XLPE Armourd Cable
MV Cable Jointing & End Termination : Supplying and making indoor end termination with PVC compression gland and aluminum / copper lugs, for following size of PVC insulated and PVC /XLPE sheathed , aluminum / copper conductor cables of 1.1kV grade as required. : Size - 1 Core x 16 Sq.mm Copper Flexible FLRS Cables ( Green Outersheath )
MV Cable Jointing & End Termination : Supplying and making indoor end termination with PVC compression gland and aluminum / copper lugs, for following size of PVC insulated and PVC /XLPE sheathed , aluminum / copper conductor cables of 1.1kV grade as required. : Size - 4 Core x 4 Sq.mm Copper Flexible FLRS Cables
MV Cable Jointing & End Termination : Supplying and making indoor end termination with PVC compression gland and aluminum / copper lugs, for following size of PVC insulated and PVC /XLPE sheathed , aluminum / copper conductor cables of 1.1kV grade as required. : Size - 1 Core x 95 Sq.mm Copper Flexible FLRS Cables ( Green Outersheath )
MV Cable Jointing & End Termination : Supplying and making indoor end termination with brass compression gland and aluminum / copper lugs, for following size of PVC insulated and PVC /XLPE sheathed , aluminum / copper conductor cables of 1.1kV grade as required. : Size - 3 C X16 sq.mm Copper ,XLPE Armourd Cable
Supply, loading, transportation unloading at site, storages at site ,shifting from storage place to site, of 1100 Volts grade XPLE insulated over all FRLS outersheathed , Aluminium / copper conductor, un armoured / armoured LT power cables as per IS 7098(Part 1) of following sizes.( Note :- Cable shall be considered flat armoured type for armoured cable ) 3 1/2 C x 240 sq.mm Aluminium ,XLPE Armourd Cable
Supply, loading, transportation unloading at site, storages at site ,shifting from storage place to site, of 1100 Volts grade XPLE insulated over all FRLS outersheathed , Aluminium / copper conductor, un armoured / armoured LT power cables as per IS 7098(Part 1) of following sizes.( Note :- Cable shall be considered flat armoured type for armoured cable ) 3 1/2 C x 70 sq.mm Aluminium ,XLPE Armourd Cable
Supply, loading, transportation unloading at site, storages at site ,shifting from storage place to site, of 1100 Volts grade XPLE insulated over all FRLS outersheathed , Aluminium / copper conductor, un armoured / armoured LT power cables as per IS 7098(Part 1) of following sizes.( Note :- Cable shall be considered flat armoured type for armoured cable ) 4 C X16 sq.mm Copper ,XLPE Armourd Cable
Supply, loading, transportation unloading at site, storages at site ,shifting from storage place to site, of 1100 Volts grade XPLE insulated over all FRLS outersheathed , Aluminium / copper conductor, un armoured / armoured LT power cables as per IS 7098(Part 1) of following sizes.( Note :- Cable shall be considered flat armoured type for armoured cable ) 4 C X10 sq.mm Copper ,XLPE Armourd Cable
Supply, loading, transportation unloading at site, storages at site ,shifting from storage place to site, of 1100 Volts grade XPLE insulated over all FRLS outersheathed , Aluminium / copper conductor, un armoured / armoured LT power cables as per IS 7098(Part 1) of following sizes.( Note :- Cable shall be considered flat armoured type for armoured cable ) 4 C X 4 sq.mm Copper ,XLPE Armourd Cable
Supply, loading, transportation unloading at site, storages at site ,shifting from storage place to site, of 1100 Volts grade XPLE insulated over all FRLS outersheathed , Aluminium / copper conductor, un armoured / armoured LT power cables as per IS 7098(Part 1) of following sizes.( Note :- Cable shall be considered flat armoured type for armoured cable ) 4 C X 2.5 sq.mm Copper ,XLPE Armourd Cable
Supply, loading, transportation unloading at site, storages at site ,shifting from storage place to site, of 1100 Volts grade XPLE insulated over all FRLS outersheathed , Aluminium / copper conductor, un armoured / armoured LT power cables as per IS 7098(Part 1) of following sizes.( Note :- Cable shall be considered flat armoured type for armoured cable ) 3 C X 2.5 sq.mm Copper ,XLPE Armourd Cable
Supply, loading, transportation unloading at site, storages at site ,shifting from storage place to site, of 1100 Volts grade XPLE insulated over all FRLS outersheathed , Aluminium / copper conductor, un armoured / armoured LT power cables as per IS 7098(Part 1) of following sizes.( Note :- Cable shall be considered flat armoured type for armoured cable ) 1 Core x 25 Sq.mm Copper Flexible FLRS Cables ( Green Outersheath )
Supply, loading, transportation unloading at site, storages at site ,shifting from storage place to site, of 1100 Volts grade XPLE insulated over all FRLS outersheathed , Aluminium / copper conductor, un armoured / armoured LT power cables as per IS 7098(Part 1) of following sizes.( Note :- Cable shall be considered flat armoured type for armoured cable ) 1 Core x 70 Sq.mm Copper Flexible FLRS Cables ( Green Outersheath )
Supply, loading, transportation unloading at site, storages at site ,shifting from storage place to site, of 1100 Volts grade XPLE insulated over all FRLS outersheathed , Aluminium / copper conductor, un armoured / armoured LT power cables as per IS 7098(Part 1) of following sizes.( Note :- Cable shall be considered flat armoured type for armoured cable ) 1 Core x 10 Sq.mm Copper Flexible FLRS Cables ( Green Outersheath )
Supply, loading, transportation unloading at site, storages at site ,shifting from storage place to site, of 1100 Volts grade XPLE insulated over all FRLS outersheathed , Aluminium / copper conductor, un armoured / armoured LT power cables as per IS 7098(Part 1) of following sizes.( Note :- Cable shall be considered flat armoured type for armoured cable ) 4 C X 25 sq.mm Copper ,XLPE Armourd Cable
Supply, loading, transportation unloading at site, storages at site ,shifting from storage place to site, of 1100 Volts grade XPLE insulated over all FRLS outersheathed , Aluminium / copper conductor, un armoured / armoured LT power cables as per IS 7098(Part 1) of following sizes.( Note :- Cable shall be considered flat armoured type for armoured cable ) 1 Core x 16 Sq.mm Copper Flexible FLRS Cables ( Green Outersheath )
Supply, loading, transportation unloading at site, storages at site ,shifting from storage place to site, of 1100 Volts grade XPLE insulated over all FRLS outersheathed , Aluminium / copper conductor, un armoured / armoured LT power cables as per IS 7098(Part 1) of following sizes.( Note :- Cable shall be considered flat armoured type for armoured cable ) 4 Core x 4 Sq.mm Copper Flexible FLRS Cables
Supply, loading, transportation unloading at site, storages at site ,shifting from storage place to site, of 1100 Volts grade XPLE insulated over all FRLS outersheathed , Aluminium / copper conductor, un armoured / armoured LT power cables as per IS 7098(Part 1) of following sizes.( Note :- Cable shall be considered flat armoured type for armoured cable ) 1 Core x 95 Sq.mm Copper Flexible FLRS Cables ( Green Outersheath )
Supply, loading, transportation unloading at site, storages at site ,shifting from storage place to site, of 1100 Volts grade XPLE insulated over all FRLS outersheathed , Aluminium / copper conductor, un armoured / armoured LT power cables as per IS 7098(Part 1) of following sizes.( Note :- Cable shall be considered flat armoured type for armoured cable ) 3 C X16 sq.mm Copper ,XLPE Armourd Cable
Supply, installation, testing and commissioning of Chemical earthing using electrode of size 76 mm minimum diameter, minimum 03 meter long and connected with 50x5 mm copper internal strip, material of conustruction COPPER, complete with existing excavation / bore, civil work for chamber, cast iron cover size 450 x 450 mm, with backfill compound as requred to fill earth pit up to mark. the earth resistance shall be as per IS 3043
Supply, installation, testing and commissioning of copper strip of size 50 x 5 mm for test link at earth pit as required.
Providing boreing / drilling bore well of 150mm dia for casing / strainer pipe , by suitable method, including drilling in all strata, including hiring & running charges of all equipments, tools, plants and machinenaries required for the job, all complete as per direction of Engineer in charge.
Making joint on copper strip with two nos MS nutbotlds, spring washer, plane washer having distance of 20 mm from each other. Breazing of joint suitable material for homogenious joint. Work shall be completed as per instruction of Engineer in charge.
Supply and fixing of Earthing strip 25x5 mm copper conductor with insulators for mounting, 300 mm in length and min 4 bore for cables termination on surface as complete.
Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required.
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 meter below ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
EARTHING SYSTEM : Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
EARTHING SYSTEM: Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
EARTHING SYSTEM :Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
EARTHING SYSTEM :Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required.
EARTHING SYSTEM :Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut,bolt, spring, washer excavation and re-filling etc. as required.
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB where 3 phase outlets are required.) 4 way (4 + 12), Double door
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB where 3 phase outlets are required.) 8 way (4 + 24), Double door
MCCB,MCB&DB'S Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C"curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
MCCB,MCB&DB'S Supplying and fixing 63 A rating, 240/415 V, 10 kA, "C"curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. FOUR pole
MCCB,MCB&DB'S Supplying and fixing 16 A rating, 240/415 V, 10 kA, "C"curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Tripal pole
MCCB,MCB&DB'S Supplying and fixing 32 A rating, 240/415 V, 10 kA, "C"curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Tripal pole
Supplying and fixing following 40 A rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DBcomplete with connections, testing andcommissioning etc. asrequired. 40A
Supplying and fixing following 63 A rating, Four pole, (Three phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DBcomplete with connections, testing andcommissioning etc. asrequired. 63A
Supplying and fixing TP sheet steel enclosure on surface/ recess along with 415 V "C" curve 4POLE MCB complete with connections, testing and commissioning etc. as required for following rating.32A MCB,4POLE 10KA,D-CL
Supplying and fixing TP sheet steel enclosure on surface/ recess along with 415 V "C" curve 4POLE MCB complete with connections, testing and commissioning etc. as required for following rating.63A MCB,4POLE 10KA,D-CL
Supply and installation of MCCB enclosuser box with 250 A 4 pole 36 kA MCCB having required accessories, mouting , handle etc as complete, enclosuer should be suitable for termination of 3.5 c x 300 sqmm cable at both end of MCCB. Duly painted and having wall mounting arrangment . cable entery top and bottom, as complete.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed including medium class PVC conduit as required. 2 X 4 sq. mm + 1 X 4 sq. mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed exsisting medium class PVC conduit/trunking etc as required. 2 X 4 sq. mm + 1 X 4 sq. mm earth wire
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 20 mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 32 mm
Supply and laying of PLB pipe/conduit 40 mm dia in open duct / tray / on surface with clamp / in ground as complete.
Supply & fixing following modular switch/ Socket on the exisiting modular plate & switch box including connection but excluding modular plate etc. as required 5/6 amps switch (For Power socket)
Supply & fixing following modular switch/ Socket on the exisiting modular plate & switch box including connection but excluding modular plate etc. as required : 15/16 amp switch (For Power socket)
Supply & fixing following modular switch/ Socket on the exisiting modular plate & switch box including connection but excluding modular plate etc. as required : 3 pin 5/6 amp socket outlet (For Power socket)
Supply & fixing following modular switch/ Socket on the exisiting modular plate & switch box including connection but excluding modular plate etc. as required : 6 pin 15/16 amp socket outlet (For Power socket)
Supply and fixing modular blanking plate on the exisitng modular plate & switch box with matching colour including connection but excluding modular plate etc as required.
Supply & installation of surface mounted DLP U- PVC adaptable trunking raceways, fabricated out of U-PVC to Off-White or approved shade as per IS 733 of thickness 2.0 mm for the base and sides with removable covers, complete with necessary bends, suitable sized junction boxes, internal angle, external angle, flat 90 degree angle , end caps and tees etc, Complete. (For every 1mtr distance cable tag has to be provided for each circuit in the raceways - as more that 1C FRLS copper wire is required for 1 Circuit) PVC RACEWAYS ( Along the wall), DLP U- PVC adaptable trunking . Size: 105x 50mm PVC Raceways for Power & Data with above specifications
Supplying and fixing following Modular base & cover plate ( Clip on support for mounting switches etc) on existing DLP U PVC trunking etc. as required. 2/3 module
Supplying and fixing following Modular base & cover plate ( Clip on support for mounting switches etc) on existing DLP U PVC trunking etc. as required. 4 module
Supplying and fixing following Modular base & cover plate ( Clip on support for mounting switches etc) on existing DLP U PVC trunking etc. as required. 6 module
Supply and fixing of seperation partition 85/105 mm in existing DLP U PVC trunking as required.
UPS SYSTEM NECESSARY WORK UPS & Battery rack installation, testing and commissioning of 100KVA rating UPS with ,15Min battery backup , with static & manual bypass Input Voltage: 3 Ph 415 Volts, ±10% Output : 3 -Phase-415Volts 4w 50 Hz ±1% , .( Note :- 100KVA UPS Dimesions 800X 800x2000mm Rack Size :- 1100x1000x2000mm UPS Make :- Numeric Archimode). Scope of work includes installation, commissioning and testing of existing UPS with transport, labour and reinstallation of UPS with its all accessories incluiding isolation transformer, power links, cables, switchgears with enclosuer etc as complete to make it functional. Installation should be done by Engineer of authorised service dealer or manufacture of said UPS. Work should be carried out with required safety, and prior approval of IISER Pune. Any charges payable to the UPS agency will be borne by the contractor.
UPS SYSTEM NECESSARY WORK : Supply, Installation, Testing and Commissioning with 12 V, min 120AH rating maintanance free type batteries complete with intercell connectors & copper cables, battery stand made out of Powder Coated MS Angles with adequate supports to carry the load of the batteries( for 15 Minutes battery rating 12 V, min 120AH X 42 nos. Battery make Amaron Quanta/Exide/Rocket ), including 2 poles DC Battery brekers . Installation should be done by Engineer of authorised service dealer or manufacture of said UPS. Work should be carried out with safety and prior approvals by IISER Pune. Any charges payable to the UPS agency will be borne by the contractor. ( detailed specifications attached with Annexure B ) Works includes supply, transport, shifting, loading , unloading, labour , taxes , warranty for 1 year of SMF batteries.
Supply, installation, testing and commissioning of 3 ph - 3 ph , 30 KVA , 400 V Isolation transformer with cabiner and protection switchgear etc as complete. Delta to Star Conversion. 3phase input-3 Phase output ,Input:- 400/415VAC,3Phase,3 wire . Output:- 440VAC,3Phase,4 wire Make : LEGRAND - NUMERIC / Vertiv / Eaton /neelkanth/voltamp
Excavation work by mechanical means (Hydraulic excavator)/ manual means in foundation trenches or drains (not exceeding 1.5m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms,lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within a lead of 50 m. Rate to include all royalties, taking statutory approvals as necessary to carry out the works etc., complete : - Excavation in ordinary rock
Excavation work by mechanical means (Hydraulic excavator)/ manual means in foundation trenches or drains (not exceeding 1.5m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms,lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within a lead of 50 m. Rate to include all royalties, taking statutory approvals as necessary to carry out the works etc., complete : - Hard rock (blasting prohibited)
Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge.: Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix)
Filling available excavated earth (excluding rock) in trenches, plinth,sides of foundations etc. in layers not exceeding 20cm in depth,consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
Reconstunction of Earthing chambers with demolishing of exisisting and making by using, bricks, cement, CI chamber cover of 450 mm x 450 mm, plastering of chamber wall, making finishing as required, excavation in ground as required, making levelling of surround ground , removing of bedries etc is in scope of agency.
Providing PCC for road after excavation work during road crossing. PCC 1:2:4 ( Cement:stonecrush:sand), to make exisitng road functional with good finishing as required and as complete.
Providing 15mm thick cement plaster of mix 1:4 (1 cement : 4 fine sand) at all levels.
Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels.
Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
Excavation of the cable trenches in hard rock not exceeding 1.5 metres in width, and lift upto 1.5 metres, including getting out the excavated soil and disposal of excavated soil as directed within a lead of 50 metres.
Excavation for cable trenches in soft soil, depth upto 1.2 m including dressing of sides lift upto 1.5 m, including getting out the excavated soil, refilling with sand and or good soil after laying of cable/ pipe etc in layers of 20 cm, ramming, watering and disposal of surplus excavated soil as directed, within a lead of 50 metres.
Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. Upto 35 sqmm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. Above 35 sqmm upto 95 sqmm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. Above 95 sqmm upto 185 sqmm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. Above 185 sqmm upto 400 sqmm
Supply, installation, testing and commissioning of Panel Volt meter , size 96x96 mm, having voltage range from 0 to 10 V, accuracy +/- 1 % ( 0.1 V ) on existing panel with required accessories as complete. Make L&T / HPL / Schindler
Supply and installation of Metal enclosuer box for panel meter having 96x96 size with protection MCBs, control wires of rating and mounting arragement. GA drawing and control circuit with all specifications should be submiited by the agency for approval before execution of job. Work shall be completed as instructed by Engineer in charge, IISER Pune.
BBP Electricals
OM POWER SYSTEMS
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .