Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.8 LAccepted-AOC | L1 | Accepted-AOC BEING LOWEST | |
| 2 | L2₹22.9 L+₹9,819.60 (0.43%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST | |
| 3 | L3₹25.1 L+₹2.3 L (9.91%)Rejected-Finance | L3 | Rejected-Finance OTHER THAN LOWEST | |
| 4 | L4₹25.8 L+₹3.0 L (12.9%)Rejected-Finance NH 17 MAIN ROAD BINAGA BAZAR KARWAR 581307 | KARWAR | UTTARA KANNADA | KARNATAKA | 581307 | L4 | Rejected-Finance OTHER THAN LOWEST | |
| 5 | L5₹26.7 L+₹3.9 L (17.2%)Rejected-Finance 11 82 GROUND FLOOR BLOCK 11 KALYANPURI EAST DELHI DELHI 110091 | EAST DELHI | DELHI | 110091 | L5 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹27.2 L
EMD Value
₹54,340
Closing Date
18 Jul 2024, 6:00 pmClosed
HQ CWE Prayagraj
HQ CWE New Cantt Prayagraj
PROVISION OF 500 KVA TRANSFORMERS FOR OFFR MESS AND MD ACCN AREA AT VARANASI UNDER GE (EAST) PRAYAGRAJ.
2024_MES_660670_1
81880/E/E8
Open Tender
Civil Works
Item Rate
180 days
Varanasi
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE (East) Prayagraj
₹54,340
Yes
14 Oct 2024
19 Jun 2024
25 Jul 2024
20 Jun 2024
18 Jul 2024
4 Jul 2024
Amount
Supply, installation, testing and commissioning outdoor type transformer of capacity 500 KVA step down phase 50 Hz oil immersed, 11/0.433 KVA complete,air naturally cooled (ONAN type) with external cooling tubes/fins, level 2 type,5 star rated,double wound core type copper wound having no load voltage ratio 11 KV/433V corresponding to principal tapping, delta connected primary side (HV side) and star connected secondary side (LV side) in accordance with vector symbol DYN 11 (Vector, group-4) with neutral brought out on LV side and having tapping on HV side for constant output so as to alter/vary secondary voltage from +2.5% to ± 2.5% , ± 5% & ± 7.5 % to be changed by means of manual OFF LOAD tap changing rise should not exceed 45º C in oil and 55 º C when measured by the resistance method after continuous full load in and as ambient temperature 40 º C. The transformer oil having dielectric strength not less than 60 KV arrangements complete and confirming to IS : 2026 complete all as specified. The limit of temp rise after continuous full load sum as specified in SSR PR-I & IS-2026 shall be suitably adjusted to suit the minimum ambient temp prevelling at site including transport from store yard Varanasi Cantt. The transformer shall be completed with fitting and accessories all as following (a) Oil conservator tank with filling holes and cap filter type drain valve and oil level gauge (b) Silica gel breather with connecting pipe and first fill of dehydrating agent (c) Air Release valve plug
(d) 01 No 100mm dia type thermometer vapour pressure type having rating 0-120 degree centigrate with max temp indicator and resetting device incl max reading pointer washers (e) Thermometer pocket on tank cover (f) 04 Nos plain solid CI detachable rollers (g) 02 Nos Earthing terminals on tank cover to facilitate GI Earth Strip (h) Rating plate and terminal marking plate (j) First filling of oil confirming to IS 335 and tested upto 50KV/2.5mm dielectric strength (k) Lifting lugs/hook (l) Oil drain valve with plug (m) Cable end terminal boxes on LV and HV side consisting of 04 Nos porcelain bushing with nuts washers & bushing rod with one No cable gland suitable for existing size of LT cable on LV side including additional neutral separately brought out side LV cable end box with bush insulators for neutral earthing. 03 Nos HV porcelain bushings with nuts,washers and bushing rod with one No cable gland suitable for 3x95 sqmm H.T. cable on HV side complete all as specied and directed. (n) Explosive Vent (o) Two Nos GI tubing light grade 100mm dia 60cm long embedded in brick/wall on LT/HT side for drawing underground cable (p) Taking down cement plaster on brick or stone walls etc including raking out joints, hacking for key, scrubbing down with water etc of existing transformer foundation including rendering 10mm thick on fair faces of brick work or concrete surfaces on existing foundation in cement mortar ratio 1:6
Supplying & Fixing GI electrode chemical earthing of high conductive, corrosion resistant, CPRI tested maintenance free chemical earthing pit to achive earth resistance value less than or equal to 3 Ohm & EN voltage < 02 V,pipe in pipe technology based in which primary conductor (Pipe) having 40 MM dia and primary conductor is inserted into secondray conductor having 80 MM dia. The primary conductor is inserted into secondory conductor and space between secondary and primary conductor of earthing electrode should be crystalline compound. The length of this electrodes is min 3000 MM (3 meters) and earth pit's bore hole should be of dia 200 to 250 mm and min depth 3.50 meters. Length of electrode will be increase with connecting of 25 x 4 mm GI strip extra,and total depth should not less than 3.50 meters. Around the earth electrode earth pit borehole should be backfilled with minimum 50 Kg of ground enhencement compound ERIC Contains mixture of Silica sulphate,Alumina, Iron Oxide, titanium Oxide, Calcium Oxide,Sodium Oxide, Zink Oxide etc. ). including RCC earthing pit having 450 x 450 Cl chamber cover all as directed by Engineer-in-Charge. (Note : If less than 3 Ohm result has not acheived at site the contractor is responsible to do grid system to achieve the desired result and no extra payment shall be made to the contractor for making grid system) Make Remedies/MRS agency, Model G-80
Supply and fix cable jointing kit for 11 KV grade cable for out door termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 50 Sqmm to 95 Sqmm, complete all as specified and directed.
Excavating in post holes (or similar holes) each n.exc 0.5 Cum getting out soft and Loose soil returning filling in and ramming earth or broken rubble mixed with earth around in layers n.exc 25cm, watering and removing surplus soil to a distance n.exc 50mtr and making good surface, complete all as specified and directed.
M&L for cement concrete in 1:2:4 type B2 (40mm graded aggregate) as in find, filling and mass concrete, complete all as specified and directed.
S&F angle channel as in posts and struts in fencing including cutting tops to shape as directed drilling holes notching for wire etc, flat iron fillets (for securing wire mesh etc) including all necessary drilling, bolting or rivetting etc and similar work conforming to Fe-410-0 or Fe-310-0, complete all as specified and directed.
M&L for two coats of synthetic enamel paint on steel surfaces exc 10cm girth or width over one coat of red oxide including preparation of new surfaces, complete all as specified and directed.
Supply only chain link fencing MS galvanized fencing 50mm mesh, 2.2 mm dia gauge wire, complete all as specified and directed.
fixing only chain link fencing incl line wires mesh size and type of standards, rail, straining bolts etc incl provision of bldg wire, complete all as specified and directed.
M&L for excavation in tranches n. exc 1.5M wide and n.exc 1.5M depth for foundation etc or for shafts, wells, cesspits, manholes, pier holes etc. n. exc 10 Sqm on plan and n.exc 1.5M in depth and getting out, complete all as specified and directed.
M&L for cement concrete in 1:4:8 type D2 (40mm graded aggregate) as in fnd, filling and mass concrete, complete all as specified and directed.
M&L for Brick work with subclass ‘B’ bricks, straight or curved on plan exc 6m mean radius built in cement mortar 1:6 ratio, complete all as specified and directed.
M&L for providing cement concrete type BI 1:2:4 (20 mm graded aggredate) copings, complete all as specified and directed.
S&F cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint, complete all as specified and directed.
Supply and fix GI pipe 80 mm,light grade ISI marked including all fittings such as bends,Tees,sockets etc fixed on walls/poles or laid in trenches under road crossing/hard standing including taking down old/unserviceble existing pipe, complete all as specified and directed.
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 95 sq mm, complete all as specified and directed.
Supply, laying and testing cable with cable gland, XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of sizes 240 sqmm 3.5 core, complete all as specified and directed.
Yaduvanshi Traders (BID ID -3057430)
Avion Industries (BID ID -3066423)
ANKIT SHIP REPAIRERS AND SUPPLIERS (BID ID -3066387)
Bharat Sales Corporation (BID ID -3057726)
Electromech Engineers (BID ID -3057537)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .