Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹81.0 LAccepted-AOC NO 41 21 PERAMBUR BARRACKS ROAD PATTALAM CHENNAI 12 | 12 | L1 | Accepted-AOC Lowest rate tenderer | |
| 2 | L2₹83.1 L+₹2.0 L (2.49%)Rejected-Finance | L2 | Rejected-Finance High rate tenderer | |
| 3 | L3₹84.2 L+₹3.2 L (3.91%)Rejected-Finance | L3 | Rejected-Finance High rate tenderer | |
| 4 | L4₹84.8 L+₹3.8 L (4.63%)Rejected-Finance 39A FIRST MAIN ROAD BARATHI NAGAR AMBATTUR CHENNAI TAMIL NADU 600053 | THIRUVALLUR | TAMIL NADU | 600053 | L4 | Rejected-Finance High rate tenderer | |
| 5 | Not Admitted-Fee/PreQual/Technical/Finance | - | Not Admitted-Fee/PreQual/Technical/Finance Not qualified for AOC |
Tender Value
₹94.1 L
EMD Value
₹57,100
Closing Date
12 Oct 2020, 6:00 pmClosed
Superintending Engineer/CC
No.132, E.V.R.Salai, Kilpauk, Chennai-10.
Providing HT Supply, MV panel room and RMG, VCB Transformer platform arrangements for PTC building at Ashok Nagar in Chennai city
2020_TNPHC_181805_1
SE/CC/DB/1785/2020
Open Tender
Civil Works
Lump-sum
240 days
PTC Ashok Nagar in Chennai city
Please refer Tender documents
7 documents required · 7 mandatory
₹0
₹57,100
11 Nov 2020
1 Oct 2020
14 Oct 2020
1 Oct 2020
12 Oct 2020
1 Oct 2020
Amount
1.1) Earth work excavation for Foundation in all soils and sub-soils to the required depth (Including Refilling). a. 0 to 2 mts
3.1) Plain cement concrete 1:5:10 (One of cement, five of sand and ten of hard broken stone Jelly) for foundation
3.2) Plain cement concrete 1:2:4 (One of cement two of sand and four of HBS jelly) for foundation In Foundation basement
6.2) Brick work in Cement Mortar 1:5 (One of cement and five of sand) using Chamber burnt bricks of size 9”x4½X3” (23x11.4x7.5cm) for in foundation basement
9.2) Brick work in Cement Mortar 1:6 (One of cement and six of sand) using Chamber burnt bricks of size 9”x4½X3” (23x11.4x7.5cm) for super structure in the following floors a. In Ground floor
b. In First floor
13.1) Filling in foundation and basement and other similar works with Excavated earth
33) Plastering with CM 1:5 (One of cement and five of sand) 12mm thick
35)Plastering in CM 1;3, 10 mm thick
37.1) White washing three coats using clean shell lime slaked
39) Supply and fixing of MS grills
41) Painting New Iron work
Electrical Arrangement 74) Charges for Fixing fan
238) Supply and applying for Anticorrosive treatment
Annexure 2.15) Supplying and filling in foundation and basement with Stone Dust
8.2.3.1) Standardised concrete Mix M30 Grade Concrete for all RCC works a. In Foundation basement
b. In Ground floor
(c) In First Floor
14.3.2) Providing 40 mm thick precast slab a) Foundation and Basement
14.III.1) Providing 75 mm thick precast slab a) Foundation and Basement
18.1) Providing Form work and centering for reinforced cement concrete works a. Form work for Plinth beam, Grade beam, Raft beam
b.Plain surfaces such as Roof slab, floorslab, Beams, lintels, lofts, sill slab, staircase waist, portico slab and other similar works
c Form work for Small quantity and column using M.S. sheet
43.2.1) Fabrication of Mild steel / RTS grills (without cement slurry) for all sizes of rods.(BINDING WIRE insulated with PVC)
67.1.2) Wiring with 1.5 sqmm PVC insulated single core multi strand fire retardant flexible copper cable with ISI mark confirming IS: 694:1990 for 5 amps 5 pin plug socket point @ Switch Board Itself.(PVC Electrical Box )
68.1.2) Wiring with 1.5 sqmm PVC insulated single core multi strand fire retardant flexible copper cable with ISI mark confirming IS: 694:1990 for 5 amps 5 pin plug socket point @ Convenient Places.(PVC Electrical Box )
69.2) Supplying and fixing of 15 Amps 3 pin Plug (PVC Electrical Box )
70.5.2) S & F of Tube light fitting with 18 W LED tube light
74.1) Supply and fixing of 19mm dia steam pipe for down rod of fan
74.2) Supply and fixing of MS Conduit pipe for fixing the Tube light
75.2) Supply and delivery of Fan with ISI mark with Eletronic Dimmer a. 48" (1200 mm)
77.7) Run of 2 Wires of 2.5 sqmm PVC insulated single core multi strand fire retardant flexible copper cable with ISI mark confirming IS: 694:1990.
Street light 82.3.1) Supply and fixing of 30 W LED street light fitting complete with LED tubes
82.3.4) Supply and fixing of Street light fitting 25 W LED
82.5) Supply and fixing of 65 mm dia GI Pipe (Class B) with Suitable base Plate for supply and ffixing of 30W LED street light with Foundation
90.2) Providing additional strutting to centering of plain surface.
102) Wiring with 1.5 sqmm PVC insulated single core multi strand fire retardant flexible copper cable with ISI mark confirming IS: 694:1990.FOR ADMINISTRATIVE BLOCKS AND COMMUNITY CENTRE (PVC Electrical Box ) a) Light point with ceiling rose
b) Light point without ceiling rose
103) Wiring with 1.5 sqmm PVC insulated single core multi strand fire retardant flexible copper cable with ISI mark confirming IS: 694:1990 for Fan point. FOR ADMINISTRATIVE BLOCKS AND COMMUNITY CENTRE (PVC Electrical Box )
112.1) Supplying and fixing of Exshaust Fan 225mm dia
113.1) Supplying and Fixing of Rolling shutters of all sizes (Gear Operated)( 8 to 12 Sqm)
151.3.1) LT CABLING AND END TERMINATION Supplying and laying of following PVC armoured LTUG cable in a trench to be excavated(below GL) a) 3.5 c x 400 sqmm aluminium cable
b) 3.5 c x 300 sqmm aluminium cable
c) 3.5 c x 185 sqmm aluminium cable
d)3.5 x 95 sqmm aluminium cable
e) 3.5 x 25 sqmm aluminium cable
f) 4 x 10 sqmm aluminium cable
161.1.4) Supplying and fixing of brass cable gland suitable for following core sqmm PVC armoured LTUG cable. a) 3.5 c x 400 sqmm aluminium cable
b) 3.5 c x 300 sqmm aluminium cable
c) 3.5 c x 185 sqmm aluminium cable
d) 3.5 x 95 sqmm aluminium cable
e) 3.5 x 25 sqmm aluminium cable
f) 4 x 10 sqmm aluminium cable
161.4) Supply and providing cable end termination of following core Sqmm PVC LTUG Aluminium armoured cable a) 3.5 c x 400 sqmm aluminium cable
b) 3.5 c x 300 sqmm aluminium cable
c) 3.5 c x 185 sqmm aluminium cable
d)3.5 x 95 sqmm aluminium cable
e) 3.5 x 25 sqmm aluminium cable
f) 4 x 10 sqmm aluminium cable -
175.1.2) Supply and fixing of 8way single pole and neutral MCB sheet steel enclosure distribution board
175.1.6) MISCELLANEOUS ITEMS Supplying, Fixing and testing and commissioning of MCB in a sheet steel enclosure with earth connection 32A TPN 10 kA MCB (4 pole)
10/20/32A DP 10 KA MCB (2 pole)
63A TPN 10 KA MCB (4 pole)
207.3.1) Painting the new walls with two coats of approved best Emulsion paint
223.1) Supply and fixing of Weld mesh 75 x 25 mm 10 Gauge Including cost of material and labour etc. complete
255.2) Supplying and fixing of LED Lamp a) 9W bulb for Bath & WC
343.4.3) Supply and fixing of Mild steel Angles base plate including fabrication
832.5.2) Supplying and fixing in position of UPVC window of casement type( open) for all sizes
832.7) Supplying and fixing in position of UPVC Ventilator louvered ventilator type for all sizes
941.1) Safety accessories a) AC chargeable emergency lamp 2 x 11W PL lamp with all connected accessories.
b) 12mm rubber mat with ISI mark suitable for 11KV installation (6' x 3' x 1/2") - 1 Set consisting of 5 Nos to be supplied.
c) First aid box complete with all first aid medicines.
d)Shock treatment chart fixed in glazed frame (English and Tamil).
e) 4 Nos FIRE BUCKET MADE OUT OF 40 x40 x6 mm MS angle with necessary supports and filled with river sand
f) Supply of hand gloves 11KV grade.
g) Danger Board as required by the electrical authorities.
h) fire extinguisher Co2 4.5 Kg confirming to TAC norms.
RMG UNIT 970) 11 KV HT RMG UNIT - OUTDOOR TYPE Supply instalation testing and commessioning of 11KV, 630A, 500 MVA ,25KA , Three panel outdoor
970.1) HT PANEL (VCB) - Single panel 11 KV, 25 KA, 630 A, HT Outdoor Single Panel Vaccum Circuit Breaker Complete
HT CABLING AND END TERMINATION 970.2) Supply and laying of 3 core x 240 sqmm 11KV HT (E) XLPE armoured aluminium underground cable
970.3) Supplying and making indoor/outdoor cable end termination for 1185 - 240 Sq.mm 3 core, HT Cables Straight Through Joints 22KV or 11 KV (E) Screened XLPE Cables-EPKJ 5118 11KV
TRANSFORMER 970.6) Supply, installation and commissioning of 800KVA / 11KV / 433V, 3 phase, 50 Hz. Copper, double wound, oil cooled suitable for indoor / outdoor installation on suitable masonary / concrete pedestal with OLTC, RTCC panel and AVR
BUS DUCT 970.7) Supply, erection, testing and commissioning of 1250A, 415V, 3 phase and neutral copper MV busduct indoor type
970.8) Supply, erection, testing and commissioning of 1250A, 415V, 3 phase and neutral copper MV busduct outdoor type
970.9) Main MV Panel Board / Sub switch board - General Instructions 1. All Panel shall be made out of 14/16 SWG CRCA sheet steel.
971) Capacitor Panel Design, fabrication, supply and erection of following sub switch boards cubicle type floor mounting
973.1) CABLE TRAY Supply and fixing of perforated cable trays of sizes as given below made out of 16 SWG CRCA sheet steel a) 150 x 50 mm
983) EARTHING AND EARTH CONNECTION Earthing as per the ISI specification with an earth electrode of 2.1 mtr class 'B' GI pipe of dia
983.1) Providing and fixing 25mm x 3mm copper Flat on surface or in recess
983.2) Providing and fixing 25mm x 6mm copper Flat on surface or in recess
983.3) Supply and run of 2 of No.8 tin coated copper for earth connections
983.4) Plate earthing with copper plate of size 600 x 600 x 3 mm as per the ISI specification with an earth electrode of 2.1 mtr class 'B' GI pipe of dia
983.5) Coil earth to street light poles with No. 8 SWG GI wire
MICCROTECH ENGINEERING CORPORATION
ELECTRO TECH ENGINEERS
GRENEL POWERS PVT.LTD.
Bidder Name
GRENEL POWERS PVT.LTD.
MICCROTECH ENGINEERING CORPORATION
P MANICKAM AND CO
ELECTRO TECH ENGINEERS
stage.html
html • 0.05 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_217994.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .