Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 1ST FLOOR SIDHARTH TOWER BALTI KHARKHANA BYELNE S J ROAD ATHGAON GUWAHATI KAMRUP ASSAM 781001 | KAMRUP METRO | ASSAM | 781001 | Admitted-Finance |
| 2 | Admitted-Finance 269 ATTOR NANGLA 2 FIROJPUR MOHANPUR SIHANI GATE GHAZIABAD GHAZIABAD UTTAR PRADESH 201206 | GHAZIABAD | UTTAR PRADESH | 201206 | Admitted-Finance |
| 3 | Admitted-Finance 18 19 MUNESWAR PURAM PARA ALAMNAGAR BIHIND ROSE CHILDREN ACADEMIC LUCKNOW UTTAR PRADESH 226017 | LUCKNOW | UTTAR PRADESH | 226017 | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹6,500
Closing Date
3 Jan 2022, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE ETC Shahjahanpur
Electy. Trans. Circle Shahjahanpur
Construction of 132KV Bay and associated works at 132KV S/S Asha under ETD Hardoi
2021_UPTCL_656515_1
56 ETC(S)/2021-22
Open Tender
Electrical Works
Fixed-rate
90 days
Hardoi
Please refer Tender documents.
2 documents required · 2 mandatory
₹885
A/c No. 0423002100107147 IFSC Code No. PUNB0042300
₹6,500
21 Mar 2022
14 Dec 2021
3 Jan 2022
14 Dec 2021
3 Jan 2022
14 Dec 2021
14 Dec 2021 - 1 Jan 2022
120 days
Amount
The following works are to be carried out for construction of 01 No. 132KV Bay and 01 No. 33KV Bay for 40MVA T/F at 132KV Substation Asha along with other associated works as per Technical Specifications with safety of men and material including the cost of all skilled labour, Misc. Consumables, T&Ps as per details given below :
Erection of following Lattice type main & auxiliary structures, their respective beams as per drawing/BOM is to be carried out by contractor. All the duly stacked members of structure are to be shifted from store to work site, tightening of nuts, bolts, washers, fastening of beams applying standard practice. Beams are to be fastened on the proper alignment with existing columns including cost of all labour, T&P etc. for proper completion of work.
Main and Auxiliary structure:
AXM (03 SetX0.8438 MT/Set=1.6876 MT)
BBL (02 SetX0.51054 MT/Set=1.021 MT)
BCT (03 SetX0.1832 MT/Set=0.5496 MT)
BTI (02 SetX0.60882 MT/Set=0.60882 MT)
CCM (02 SetX0.35872MT/Set=0.71744 MT)
CGM (01 SetX0.31457MT/Set=0.31457 MT)
ABL (01Set x 0.35992MT/Set=0.35992 MT)
ALP (19 SetX0.1265 MT/Set=1.3915 MT)
Erection of equipments in proper alignment and with complete adjustment in switchyard on the erected structures as per manufacturers drawing or as per direction of supervising engineer, after leveling including shifting the equipments from store to working site etc. along with their junction boxes, control cubicles, and accessories and all related works to complete the erection work including cost of all labour, T&P, crane/Hydra etc.
HV Side (In 132KV Switchyard):
145 KV SF-6 Circuit Breaker including erection of structure and CB Poles
145 KV CT with Junction Box
145 KV Motorised Bus Isolator without earth switch and with Post insulator & complete adjustment
145 KV Motorised Tandem Isolator with Post insulator & complete adjustment
145KV Post insulator on ALP structure.
120KV Lightning Arrestor with Surge Counter
In BCU:
132/33KV Transformer C&R panel (SAS Type)
LV Side (In 33KV Switchyard):
36 KV Vacuum Circuit Breaker
36 KV CT with junction box
36 KV Bus Isolator with complete adjustment
30 KV Lightning Arrestor with Surge Counter
Opening of trench covers, Laying and dressing of following size control cable on the cable racks in trenches from Control and Relay panel to various equipments for AC/DC connection of C.B, C.T., PT, Isolators, junction boxes including Shifting of Cable Drums from store to Erection Site & Shifting Back the Balance Cables to Stores again placing back the opened trench covers.
2Cx2.5 Square mm
4Cx2.5 Square mm
6Cx2.5 Square mm
10Cx2.5 Square mm
Termination of various sizes above laid Control Cables as per cable schedule and interconnection diagram, Extending D.C. Supply from DCDB and A.C. Supply from ACDB to Control Panels & Equipments including Drilling of Holes wherever required, fixing of perforated cable tray, Providing & Fixing of different size Cable Glands, Ferrules & Crimping type Lugs including cost of all required skilled Technician, T&P for proper completion of work.
Diamond Earthing of Lightning Arrestors:
Excavation of Trench in Rectangular shape around L.A. structures for Diamond Earthing for 03 Nos. 120KV LAs by Fabrication of 06 Nos. 3 Meter long Electrodes with 36mm dia. M.S. Round having 150 mm long conical Shape, its Piercing Vertically in Ground with top 700 mm below ground level, Jointing Electrodes with 75×10 mm M.S. Flat by proper Welding. Two No. risers of 75×10 mm M.S. Flat shall be welded with existing main earth mat to Auxiliary structure, one separate riser will be taken from the laid earth mat to corresponding L.A. through surge counter for making of proper Mesh. Painting of the Shielding Mesh/Earthing Strips with anti-corrosive Paint and back filling of excavated trench including the cost of labour, T&P etc.
Excavation of Trench in Rectangular shape around L.A. structures for Diamond Earthing for 03 Nos. 30KV LAs by Fabrication of 06 Nos. 3 Meter long Electrodes with 32/36mm dia. M.S. Round having 150 mm long conical Shape, its Piercing Vertically in Ground with top 700 mm below ground level, Jointing Electrodes with 75×10 mm M.S. Flat by proper Welding. Two No. risers of 75×10 mm M.S. Flat shall be welded with existing main earth mat to Auxiliary structure, one separate riser will be taken from the laid earth mat to corresponding L.A. through surge counter for making of proper Mesh. Painting of the Shielding Mesh/Earthing Strips with anti-corrosive Paint and back filling of excavated trench including the cost of labour, T&P etc.
Laying, tensioning and Stringing of All three phases of 132KV Jack Bus having section length 102 Meter with Single ACSR Panther conductor along with fixing of suitable Bolted type Tension/Suspension fittings, making of Insulator string by jointing 70KN Porcelain Discs (10 Nos.) as per standard practice, Hoisting of Insulator string on AXM type beams including the cost of labour, T&P etc. for proper completion of work.
Making and dragging out of Vertical/Horizontal jumpers from equipments to equipments and vertically from Line to Main/Transfer/Jack Bus Bar with ACSR Twin Zebra/Panther conductor, fitting of suitable clamps/spacers including cutting, bending and straightening of conductor to give the proper shape including cost of all required consumable material, T&P, labour etc.
Earthing of main and auxiliary structure, equipments and Panels with the help of specified size M.S. flat along with cutting ,bending and straightening of M.S. flat to give it proper shape, painting of all type of joints, risers, strips, with one coat of red oxide primer and two coat of green enamel paint in all side of surfaces as per drawing of earthing and standard practice including cost of all required consumable material, T&P, labour etc.
(A) Earthing with 75X10mm M.S. Flat.
(B) Earthing with 50X6mm M.S. Flat.
(C) Earthing with 25X6mm M.S. Flat.
Supply, installation & commissioning of LED street light luminaries 150 watt Aluminum Die Cast (GST extra). Transportation upto site, insurance etc. and any other job requested to properly execute the complete work.
Dismatling of ACDB along with disconnection of control cables, removal of earthing strip from equipment and again erecting this ACDB on another site as per instruction of SDO/JE and connecting control cables.
Dismatling of 33 KV Fuse set, 33 KV Bus isolator, ACDB and 33/0.4 KV station T/F from the plinth along with removal of earthing strip from equipments, disconnection of jumpers from 33 KV main bus and power cable from station T/F.
Erection of following equipments as per instruction manual of various equipments and technical specification including shifting of material/equipment from previous site to new erection site including all other associated work to complete the job.
33 KV Bus Isolator
33 KV Fues set
Shfting & erection of 33/0.4 KV station T/F at the new plinth by crane.
Termination of power cable by providing proper size of aluminum lugs its crimping & connecting with equipment including cost of lugs and all other associated works.
PROVIDING & FIXING OF MATERIAL
Bolted type single tension fitting suitable for panther conductor with duly made of LM6 aluminium alloy complete with GI nuts and bolt and spring/plain washer. As per sample.
Single suspension fitting suitable for panther conductor with duly made of LM6 aluminium alloy complete with GI nuts and bolt and spring/plain washer. As per sample.
PG clamp duly made of LM6 aluminium alloy suitable for panther-panther complete with 4 no. 16x90mm size GI nuts and bolt and spring/plain washer. As per sample.
PG clamp duly made of LM6 aluminium alloy suitable for Moose-Panther complete with 4 no. 16x90mm size GI nuts and bolt and spring/plain washer. As per sample.
lodhi switchgear enterprises
M/s S.S. Refregeration
TAJ ENTERPRISES
Bharat Trading Corporation
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .