Electricity Transmission Circle, UPPTCL, 132 KV S/s Mohaddipur Old , Gorakhpur
WORK OF REWINDING , SERVICING OF COOLING FAN MOTOR M REPLACEMENT OF DEFECTIVE CONTACTORS, THERMAL O/L RELAY , MCBs , RWTI , ANNUNCIATOR OF 63/40 MVA 132/33 KV TRANSFORMER AT 132 KV S/S F.C.I. AND BHATHAT UNDER ETD-I , GORAKHPUR
2021_UPTCL_603492_1
E-Tender No. 36-ETC(G)/2021-22
Open Tender
Electrical Works
Item Rate
90 days
Gorakhpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
SE, ETC, Gorakhpur
₹2,000
1 Sept 2021
14 Jul 2021
21 Aug 2021
14 Jul 2021
20 Aug 2021
14 Jul 2021
Amount
Complete rewinding of 0.24 KW, 700 RPM , 3 Ø 415 V cooling fan motors of 63/40 MVA T/F at 132 KV S/s FCI & Bhathat . The work covers complete dismantling of all parts of fan motor its rewinding by super enamel copper wire of same specification and gauge , varnishing of complete motor body , changing of damaged front and rear side bearing with new ones of same size and standard make , oiling and greasing of all moving parts, reassembling of Motor and testing for normal running of cooling fan with all cost of men , materials , carriage and T&P etc. required for the Job.
Complete overhauling of the 0.24 KW, 700 RPM , 3 Ø 415 V cooling fan motors of 63/40 MVA T/F at 132 KV S/s FCI & Bhathat including dismantling of its motor, changing of damaged ball, bearing with new ones of same size and standard make , oiling and greasing of all moving parts, reassembling of Motor and testing for normal running of cooling fan with all cost of men , materials , carriage and T&P etc. required for the Job.
Complete rewinding of 1- Ø, 0.75 HP Exhaust Fan installed in battery room, control room etc. The work covers complete dismantling of all parts of fan motor its rewinding by super enamel copper wire of same specification and gauge , varnishing of complete motor body , changing of damaged front and rear side bearing with new ones of same size and standard make , replacement of broken fan blades , oiling and greasing of all moving parts, reassembling of Motor and testing for normal running of Exhaust Fan with all cost of men , materials , carriage and T&P etc. required for the Job.
Complete dismantling and replacement of following defective items of Transformer M.Box & RTCC panel by its rewiring with 2.5 mm2 / 10 mm2 / 4.0 mm2 copper wire as per requirement of lugs , ferrules , cable tie , cable duct etc. with all cost of man , T&P , materials , consumables for the completion of work.
Thermal O/L relay 0.45-0.67 Amp. (1NO+1NC)
Power Contactor coil voltage 9 Amp. , 230 V AC , 3 Main, 2 NO+2NC contacts Siemens / L&T / BCH /ABB/C&S/ HPL make.
MCB 6 Amp. /415 V Siemens / L&T / BCH /ABB/C&S/ HPL make.
MCB 40 Amp. /415 V, 3 ph , 4-pole Siemens / L&T / BCH /ABB/C&S/ HPL make.
Power Contactor coil voltage 415 V AC , 40 Amp., 3 Main, 1 NO+1NC contacts Siemens / L&T / BCH /ABB/C&S/ HPL make.
Annunciator of 40 MVA T/F M/s Pradeep Sales make 20 Window model P-352 suitable for RTCC Panel of 40 MVA 132/33 KV T/F.
LED Indication lamp fittings suitable Aux. supply 220 V AC.
WTI repeater (RWTI) M/s Perfect make / any standard make suitable for Perfect make WTI range 0-150° C, Aux. AC/DC.
V.P.Associates
Jai Laxmi Projects
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .