| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.6 LAccepted-AOC PLOT NO 46 SUGANDHA VIHAR NEAR NEW ERA PROGRASSIVE SCHOOL RAMPUR DIST KORBA 495677 | KORBA | CHHATTISGARH | 495677 | L1 | Accepted-AOC L1 BIDDER IS TECHNO COMMERCIALLY ELIGIBLE | |
| 2 | Rejected-Technical | - | Rejected-Technical Rejected as Bidder is NOT L1 | |
| 3 | Rejected-Technical AT GURUDWARA NEAR UCO BANK PO SOUTH BLANDA TALCHER DIST ANGUL | TALCHER | ANGUL | ODISHA | 759116 | - | Rejected-Technical Rejected as Bidder is NOT L1 | |
| 4 | Rejected-Technical AT BAGHUABOL CHHAK PO HATATOTA TALCHER ANGUL ODISHA PIN 759100 | ANUGUL | ODISHA | 759100 | - | Rejected-Technical Rejected as Bidder is NOT L1 | |
| 5 | Rejected-Technical PLOT NO 733 BIJIPUR HOUSE NO 2 TAMANDO VILLAGE TOWN SPRINGVILLE GREEN CITY BHUBANESWAR KHORDHA ODISHA 752054 INDIA | KHORDHA | ODISHA | 752054 | - | Rejected-Technical Rejected as Bidder is NOT L1 |
Tender Value
₹11.1 L
EMD Value
₹14,000
Closing Date
31 Aug 2024, 5:00 pmClosed
Staff Officer(ENM), IB Valley Area
Office of Staff Officer(ENM), IB Valley Area
Providing with fixing of New Current Transformer and Potential Transformer of 33 KV grade in main sub station of SOCP IB Valley Area.
2024_MCL_315422_1
MCL/GM/IBV/ENM/etender/112181 Dated.19.08.2024
Open Tender
Electrical and Maintenance Works
Item Rate
15 days
SOCP, IB Valley Area
Please refer Tender documents.
5 documents required · 5 mandatory
₹14,000
21 Oct 2024
19 Aug 2024
2 Sept 2024
20 Aug 2024
31 Aug 2024
20 Aug 2024
20 Aug 2024 - 24 Aug 2024
Amount
Providing with fixing of New Current Transformer and Potential Transformer of 33 KV grade in main sub station of SOCP IB Valley Area.
Supply of Outdoor, Oilcooled Type Current Transformer, Copper Wound, CT Ratio : 50A/50A/5-5 A Rated system voltage-33 KV, Highest system voltage-36 KV Applicable Standard-IS:2705-1992 (Part -I-IV)/IEC- 185,IEC-60044 Class of Insulation-Class A. Basic Insulation Level-HV: 36 KV / 70 KV / 170 KV(P) LV:3 KV (rms.). Rated Short Circuit thermal current-20 KA for 3 Sec. Rated Dynamic current-50 KA (Peak). Core1(Metering) : Burden- 15VA, Accuracy class- 0.5. Core2(Protection) : Burden- 30VA, Accuracy class- 5P20. Type : COPPER WOUND. Insulating Oil:The oil shall meet the requirement of latest edition IS: 335 or equivalent IEC. Gurantee-01 year from the date of fitment.
Onsite Primary Injection & testing of 33KV outdoor current Transformers with NABL Accreated Equipments.
Installation of 33 KV Current Transformers(CTs) on base structure including cutting, hoisting and bolting and fixing in position etc.
Supply of Single phase, oil filled, self cooled, hermetically sealed, outdoor type voltage transformer, oil immersed, sealed type and self cooled suitable for the services indicated and conforming to the modern practices of design and construction. a)Highest System Voltage (KV rms)- 36 KV, Suitable for system frequency-50 Hz Voltage Ratio-(kV rms)- 33/√3 KV/110/√3 V Output burden (VA)-100 VA 1.2/50 microsecond lightning impulse withstand voltage (KVp)-170 KV 1 Minute dry & wet power frequency withstand voltage primary (KV rms)-70KV Rated voltage factor-1.2 continuous and 1.5 for 30 One minute power frequency withstand voltage for secondary winding (kV rms)-3.0 Application-Metering, Accuracy Class-0.5, IS:3156(Part-I to Part-III) Core The core shall be of high grade, non ageing, Electrical silicon laminated steel of low hysteresis loss and high permeability to ensure high accuracy at both normal and over voltages. Insulating Oil:The oil shall meet the requirement of latest edition IS: 335 or equivalent IEC. TESTING Type Tests: The Potential Transformer offered in the Bid should have been successfully type tested at NABL laboratories for the tests indicated as follow in line with the relevant standard and technical specification. These Type Tests should have been carried out within five years prior to the date of opening of tender. Gurantee-01 year from the date of fitment.
Installation of 33 KV Potential Transformers(PTs) on base structure including cutting, hoisting and bolting and fixing in position etc.
High voltage testing of CT/PT with NABL approved Equipments
Labour Charge for dismantling of old Current Transformer/Potential Transformer from existing overhead structure
Supply of 06 core, 2.5 Sq. mm armoured control flexible copper cable.
Laying of 6 core, 2.5 sq.mm copper cable on the existing perforated cable tray inside the cable trench including lifting of RCC slab and fixing on its position after the work.
Wiring connection and final Testing of complete installation CT/PT.
Total impact of GST plus Labour Cess [@ 1 % (BOCW Cess to be deducted from the RA bill as per the value of the work progress)] for the purpose of CTC
M/S INDUSTRIAL ENGINEERING WORKS
UNIVERSAL PROJECT AND MAINTENANCE
M/s Evergreen Electrical Works
M B POWER AND SOLUTION
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .