| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.5 LAccepted-AOC GF AKRITI TOWER 19 B VIDHAN SABHA MARG LUCKNOW PIN 226001 | LUCKNOW | LUCKNOW | UTTAR PRADESH | 226001 | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹26.3 L+₹1.3 L (5.25%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | L3₹27.0 L+₹2.0 L (7.97%)Rejected-Finance FLAT NO 1004 BUILDING NO L 11 KEDAR HOUSING SOCIETY 10TH FLOOR SECTOR NO 21 TALOJA PHASE 2 PANVEL RAIGAD NAVI MUMBAI 410208 | NAVI MUMBAI | RAIGAD | MAHARASHTRA | 410208 | L3 | Rejected-Finance L3 | |
| 4 | L4₹28.4 L+₹3.4 L (13.7%)Rejected-Finance | L4 | Rejected-Finance L43 |
Tender Value
₹28.2 L
EMD Value
₹56,400
Closing Date
9 Sept 2024, 6:00 pmClosed
CWE JAIPUR
Military Engineer Services, HQ Commander Works Engineer, Kalyan Marg, Banipark, Jaipur-06
SPECIAL REPAIR REPLACEMENT OF FIRE FIGHTING SYSTEM AND FIRE ALARM SYSTEM OF P-48 BLDG AT MH JAIPUR UNDER GE JAIPUR
2024_MES_662278_1
CWE/JPR/82312/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
JAIPUR
As per NIT
8 documents required · 8 mandatory
₹0
₹56,400
Yes
17 Jan 2025
26 Jun 2024
11 Sept 2024
26 Jun 2024
9 Sept 2024
11 Jul 2024
26 Jun 2024 - 10 Jul 2024
Amount
Supply, instalation, testing and commissining of addressable analogue Optical type Smoke Detector with advanced optical chamber and smoke inlet design to provide resistance to entry of dust to provide immunity to false alarms, to protect aganist cable faults, dual bi-colour LED's with 360º view of status auto addressable with high noise rejection mounting base, two LED's etc. as required as approved by LPCB for EN54-7 & EN 54-17 standerd
Supply, instalation, testing and commissining of Heat Detectors Addressable analogue type fully digital communication protocol with high noise rejection Heat Detectors with two thermal senstivity level the two level corresponds to Rate of Rise (ROR) GRADE-I solid state design with sensing element combination of fixed type and rate of rise of temperature indicating LED with 360º mounting base etc. as required. as approved by LPCB for EN54-5 & EN 54-17 standerd.
Supply, instalation,testing and commissining of Fault isolation module to electrically isolate different sections of detector loops.
Supply, instalation,testing and commissining of Addressable type manual fire alarm boxes (MCP/Pull Station ) shall, on command from the control panel, send data to the panel representing the state of the manual switch and the addressable communication module status. Manual fire alarm boxes shall be constructed of Lexan with clearly visible operating instructions provided on the cover. The word FIRE shall appear on the front of the stations in raised letters, 1.75 inches (44 mm) or larger. etc. as required.
Supply, instalation,testing and commissining of microprocessor based loop UL/ EN54 addressable Fire Alarm Control Panel as per NFPA 72 approval. The Panel shall be able to give pin point location of addressable units via the address code for each unit. The Panel shall also be able to automatically switch off all control switches when-ever any Alarm is triggered. . The Panel shall have built in buzzer, SMF batteries for min. 8 Hrs.back up, battery charger, rectifier. Loop interface cards, communication module, compatible to connect repeater panel ,LCD unit to indicate Fire / Fault Signal of individual unit, option for external printer, to log all incoming data etc complete in all respect. 2 - Loop
Supply, instalation,testing and commissining of Active Repeater Panel for Fire Alarm System with piezo sounder, LCD alpha numeric character display with accept / reset buttons for alarm address of any sensor / field device. The Repeater Panel shall only provide field device address with room number. Analogue Output is not required. The Panel shall be connected to the Fire Alarm Panel.
Supply, installation testing and commisioning of following modules suitable for Addressable fire Alarm Control panel .
(a) Control modules with mounting box for tripping of AHU / pressurise fans and ventilators
(b) Monitor modules with mounting box to connect flow Switches with main fire panel
Supply, installation testing and commisioning of Hooter/Sounder horizontal two stage continous normal operation for atleast 50 minutes with sound level minimum 85 db audiable measured at 1.5m with sound output Variation of + 5 db mininum 1000m range suitable for addressable type fire alarm system with storb light etc. as specified
Supplying and drawing fire resistance Fire Alarm System FRLS Arm copper Cables 2C x 1.5 sq mm(Red) with nut,volts & waisher & clamps all connected accessories for fitment along with systems as IS standerd complete all as directed.
Excavation in trenches not exc 1.5 m wide and 1.5m in depth for taking out and laying of pipe in soft/loose soil complete all as specified and as directed.
Returning filling in including spreading levelling watering and well rammming in layers not exc 25cm complete all as specified and directed by the Engr-in-Charge
Removing excavated materiasl not exc 50 mtr and depositing where directed at a level not 1.5mtr above the starting point complete all as specified and direced by the Engr-in-Charge
Taking out UNSV MS pipe 150mm dia from wall up to 2nd floor with fittings complete all as specified and as directed by Engr-in-Charge. Note: Safety of labour will be the responsibility of contractor
Taking up old unserviceable MS flanged pipe of 100mm bore laid in tranches including removing old rubber gasket joints ,nuts ,bolts etc complete all as specified and as directed by Engr-in-Charge
Taking up old unserviceable MS flanged pipe of 150mm bore laid in tranches including removing old rubber gasket joints ,nuts ,bolts etc complete all as specified and as directed by Engr-in-Charge
Taking up old unserviceable MS flanged pipe of 200 mm bore laid in tranches including removing old rubber gasket joints ,nuts ,bolts etc complete all as specified and as directed by Engr-in-Charge
Taking up old unserviceable MS suction pipe of 80mm bore laid in floor including all fittings complete all as directed by Engr-in-Charge.
Supply and laying of MS ERW pipe 200mm nominal bore, medium grade, flanged type (each pipe of length 6 mtr length) conforming to IS 1239(Pt-I) complete all as specified and directed by Engr-in-Charge
Supply and laying of MS ERW pipe 150mm nominal bore, medium grade, flanged type (each pipe of length 6 mtr length) conforming to IS 1239(Pt-I) complete all as specified and directed by Engr-in-Charge
Supply and laying of MS ERW pipe 80mm nominal bore, medium grade, flanged type (each pipe of length 6 mtr length) conforming to IS 1239(Pt-I) complete all as specified and directed by Engr-in-Charge
Material and labour for flanged joints of MS pipes 200mm bore with rubber or fibre board gasket, nuts, bolts, etc complete all as specified and as directed by Engr-in-Charge
All as per item No.21 here-in-before but for150mm bore pipe
All as per item No.21 here-in-before but for100mm bore pipe
Supply and fixing stack clamps made of 50 x 5 mm flat iron and 16 mm dia round iron stay, including bolts and nuts and securing ends of stays to wall or roof for 150 mm dia of pipes including drilling hole to the walls complete all as specified & directed.
Supply and fixing in reapir 150 mm bore cast iron water type slim Non return valve, double flanged (class-'B) high pressure conforming to IS-5312 complete with nuts, bolts & washer gaskets etc complete all as specified and directed.
All as per item No.25 here in before but 80 mm bore
Supply and fixing in repair 200mm bore sluice valve ,class PN 1:6, ISI marked with brass spindle, both ends flanged jointwith 3mm thick rubber gaskit, hand wheel operated including gaskets nuts, both washer etc of required size complete all as specifed & directed,
All as per item No.27 here in before but 150 mm bore sluice valve
Supply and fixing in repair water pressure gauge suitable for 150mm dia pipe in the main line of pump including necessary dirlling welding, taping/threading of existing line etc complete all as directed by Engr-in-Charge.
Supply and fixing in repair gun metal gate valve (ISI marked) of 25mm bore screwed down high pressure with iron handwheel complete all as specified and directed.
Supply and fixing MS bend for 150mm bore pipe , flanged type with holes gasket nut bolts etc complete all as specified and directed.
All as per srl item No 31 above but for 80mm bore pipe
Supply and fixing in repair hose reel drum minimum 30m long of 36 mm dia (conforming to IS 5132) complete all as specified and directed by Engr-in-charge.)
Supply & Fix in replacement of single type fire hydrant landing valve type A Single headed outlet of 63mm dia confirmed to IS 5290 incl rubber gasket, nut & bolts etc. Make: Newage or eqvt as approved complete all as specified and directed.
Supply and Fix in replacement of Branch pipe gun metal 63mm instantaneous inlet, made threaded outlet, 20mm bore with nozzle for house real confirming to IS 8090 all as specified and directed
Supply and fix in replacement of 63mm dia 15 mtr long hose confirming to IS 636 complete with male and female coupling complete all as specified and directed. Note - Contractor should visit the site before quating the tender and any other misc items required for complete the job are deemed to be incl in to rate quated by contractor.
Supply and Fix in replacement of Hose box Out door type accomdated the one no house and one no branch pipe made out of minimum 1mm thick MS sheet with double door with 4mm thick plain sheet glasses and door frame made of 1.2 mm thick MS sheet painted fire red outside and brilliant white inside yard fixing nut bolts etc all as specified and directed
Supply and fixing in repair cabinet hose box of size 1200mmx950mmx420mm for keeping 2 nos hose pipe (20mm dia 30m long and 63mm dia 15m long ) with branch pipe hozzle, coupling etc double door with 4mm thick glasses and door frame made of 16 gauge MS sheet painted fire red outside and brilliant white inside yard all as specified and directed by Engr-in-Charge
Material and labour for sub main wiring for fire fighting MCP with two run of single core FRLSH PVC insulated and unsheathed multistranded copper conductor of size 1.5 sqmm and one run of FRLSH PVC insulated unsheathed multistranded stranded copper conductor of size 1.5 sqmm as earth lead drawing into and including rigid non metallic PVC conduit of size 20mm dia including taking down old unserviceable sub main wiring complete all as specified and as directed . Note: Two run of 1.5 sqmm cable ,one run of 1.5 sqmm cable and one run of conduit will be measured as single length.
M&L for cleaning, priming plaster in other surface & distempering of underground water sump of any capacity by pumping out all dirt water from sump,blocking the pipe line to the sump with jute bags at first manhole and cleaning the sump thoroughly with the help of wire brush and make good in disturbed surface after removing the sludge/silt and other foreign materials complete removing the blockage from sump including removing the sludge from the pump house premises and depositing away from cantonment area complete all as directed.
Material and labour for preparation of old painted surface of existing pipe lines incl all fittings of size upto 100mm dia of pipe applying one coat of synthetic enamel paint (red colour) with direction aero mark of flow complete all as specified and directed
All as per item no-41 as above here-in-before but pipe lines incl all fittings of size 150mm bore complete all as specified and directed.
All as per itemno-41 as above here-in-before but pipe lines incl all fittings of size 250 mm bore complete all as specified and directed.
Material and labour for preparation of old painted surface of existing fire fighting pump motor set of capacity from 50 HP to100 HP incl all fittings and applying one coat of synthetic enamel paint (red colour) complete all as specified and directed .
Material and labour for preparation of old painted surface of existing LT panel, box hose box of any size and applying one coat of synthetic enamel paint (red colour) complete all as specified and directed
Supply,fixing maintenance free battery 150AH,12 Volt including making connection with suitable size clamps nut bolt or clamp etc complete all as specified and as directed including taking down unserviceable one. Make : EXIDE/ AMRON / AMAR RAJA Note: Old batteries will be deposited to MES store.
Supply and fixing battery lead copper flexible cable PVC insulated 650 volt 2x25 sq mm single core of length 1.5 metre long with one side connected (welded / soldered) with male type battery terminal (as per existing) and other end connected with female type battery terminal (as per existing) including connections and testing all as specified and as directed.
Supply and fixing in repairs Sheet glass, ordinary quality 4mm thick and glazing with oil putty in square exc 0.5 sq. m in each panel of fire hydrant box complete all as specified and directed.
Material and labour for replacement of steel base frame for fire pump motor as per the existing size by fabricating the heavy channel of size as directed and painting the new steel base frame with one coat of red oxide and two coat of synthetic enamel paint complete all as specified
M&L for construction to brick masonary valve pit/ chamber of size 900 x 900 x 900 mm including necessary excavation and earth work, PCC, 15mm thick Plaster in CM 1:6 on inside and out side (above ground ), angle iron frame 40x40x6mm size including fabrication work, hold fast, MS sheet cover 3mm thick, duly painted with one coat of black bituminous paint of approved quality, handle and including provn of 40mm dia Godrej (freedom) lock complete all as specified and directed
All as per Item No. 50 above but size 1200x1200x900mm
Taking out the complete fire pump and motor /DG set from the existing damaged base frame and repairing the PCC foundation and fixing the same pump and motor/DG set on the new base frame with Nut and bolt of size 5/8" x 10" long and Nuts of same size fixed in PCC foundation and making all mechanical and electrical connection and testing complete all as specified and directed.
Supply and fixing fire fighting layout diagram,safty notice/instruction board in case of fire in hospital building, They will displayed on system the phone no of fire brigade, exist way with direction and fire action notice with guideline recommended every final exit point complete all as specified and directed. (a) Layout diagram of fire fighting installation as designed as approved.
(b) FIRE EXIT, direction with action board approved.
(c ) Fire safty notice board display phone no in case of fire at installation approved.
Outgoing:- (i) Star delta starter with relay,contractor, timer relay, lugs suitable for 40 HP pumpset motor -1 Nos ,Make: L&T or eqvt as approved (ii) Star delta starter with relay,contractor, timer relay, lugs suitable for 20 HP pumpset motor -1 Nos, Make: L&T or eqvt as approved (iii) MCCB capacity 63 Amp, 4 Pole ,36 KA-03 nos, Make: L&T or eqvt as approved (iv) MCB SPN, 6-32 A, 'C' curve, 10 kA, L&T, Cat No: BB20320C iv) Space only for accomodating MCCB upto 63 Amp 4 pole 25 kA - 01 No
M&L in replacement for earthing complete with galvanized steel earth plate electrode of size 60cmx60cmx6.0mm buried directly in ground, vertically to depth not less than 2.25mtr below normal ground level with top edge of the earth plate at depth not less than 1.5 metre below ground level surrounded from all sides with alternate layers of charcoal and common salt and connected to GI strip of size 32x6mm by means of GI bolts, nuts washers & check nuts electrode connected to main switch board or main control board or on poles or on transformer and GI pipe medium grade 20mm bore for watering, 40mm bore GI pipe medium grade for protection of GI strip upto test point including providing funnel and wire mesh GI frame and 10cm thick suitably reinforced RCC pit cover, PCC chamber pit with PCC (1:3:6) type C2 using 40mm graded stone aggregates complete including excavation and earth work in any type of strata, disposal of surplus soil to a distance not exceeding 50 mtr, all as specified ans shown in Electrical plate No. 3 of SSR Part-1, PCC pit shall be provided at least 50 cm away from the earth pit and not just on earth pit including testing on completion complete. Note:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (ii) Protection pipe and GI earthing wire upto test point or upto electric equipment from top of earth plate shall be included in the unit rate of this item. (iii) The earth testing arrangement should be done by the contractor as per direction of Engineer-in-charge.
M&L for servincing of diesel engine set for Pumpset of capacity 56 BHP,1500 RPM including taking out old air filter,oil filter, oil change, radiator and coonected pipe cleaning and re- assambling the same in original position with spray painting the disturbed part of engine set as per the existing colour of the body or as required on site and all as specified and directed. (Note :- Spare parts of diesal engine set will be measured and paid separately as under)
(a) fuel filter and ring
(b) Element for Lubrication oil filter.
(c ) Supply and filling engine oil 15W/ 40f make Castroll /Kirloskar /HP etc.
(d) Supply and filling water coolant (diluted) in radiator of make volve line or equivelent including removal of old water/ coolant, all as directed.
(e ) S&F in replacement, fan belt suitable complete all as specified and as directed.
(f) Set of high pressure pipe as per site requirement.
M&L for cement concrete 1:2:4 type B2, (using 40mm graded crushed stone aggregate) for unground sump as in foundation filling and mass concrete etc complete all as specified and directed.
Schedule of Credit
M/s Prakash Enterprises (BID ID -3061793)
M/s ASPIRE ENGINEERING ENTERPRISES (BID ID -3064884)
Shree Karni Electrovision (BID ID -3070615)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .