Tender Value
Refer Docs
EMD Value
₹60,000
Closing Date
15 Dec 2022, 4:00 pmClosed
Executive Engineer Electric Division UdhampurJPDCL
Executive Engineer Electric Division Udhampur JPDCL
Creation of 250 KVA substation, HT line on 9 mtr ST poles and LT line
2022_PDD_198808_1
ED/UDH/85 of 2022-23, dt. 08-12-2022
Open Tender
Electrical Works
Turn-key
60 days
Tandar Chenani in District Udhampur
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
Executive Engineer Electric Division UdhampurJPDCL
₹60,000
21 Dec 2022
8 Dec 2022
16 Dec 2022
8 Dec 2022
15 Dec 2022
8 Dec 2022
8 Dec 2022 - 13 Dec 2022
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11 KV line on 9 mr ST poles, 30 mm Sq. ACSR Conductor for creation of 250 KVA Sub Station for Degree College Chenani at Tandar.
9 mtr. Long ST Pole (ST-410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Braces
30 mm² ACSR Weasel Conductor
PG Clamps for 30 mm² ACSR Conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting of 9 mtr ST poles including crossarms/clamps with two coat of Aluminium Paint.
Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 250 KVA Sub Station for Degree College Chenani at Tandar.
11/0.433kV, 3-phase 250 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, Copper wound, and with LV Cable Box having detachable Aluminium Gland plate
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11kV GO, Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A
300 mm² 1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST-410 SP33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
LT distribution box for 250 KVA DTR with MCCB for incomer and SfU's for outgoing circuits.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Wedge connectors/PG Clamp
Danger Plates with Clamps
GI Barbed wire for Anti Climbing
3 phase HT Trivector meter with CT/PT unit
Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole
Painting of sub station ST poles/cross arms/clamps with one coat of Red oxide and two coats of aluminium paint
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line 3 phase 4 wire LT 30mm sq. On 9 mtr long ST poles with Rabbit Conductor for creation of 250 KVA Sub Station for Degree College Chenani at Tandar.
9 mtr. Long ST Pole (ST-410 SP-33)
G.I M Clamps for Shackle Insulator
50 mm² ACSR Rabbit Conductor
Shackle Insulator
Galvinized Nuts and Bolts.
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip25X3 mm
Painting of 8 mtr ST poles including crossarms/clamps with two coat of Aluminium Paint.
Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Supply of Aluminium Ladder 10 feet heavy duty
Supply of 11kV GO, Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
Supply of safety gloves as per releavant IS/ISI Marked (33000/7500 volts)
Supply of Aluminium Ladder 20 feet heavy duty
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for shifting /realignment of HT line passing over the site of Degree college at Tandar Chenani.
9 mtr. Long ST Pole (ST-410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Braces
30 mm² ACSR Weasel Conductor
PG Clamps for 30 mm² ACSR Conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting of 9 mtr ST poles including crossarms/clamps with two coat of Aluminium Paint.
Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Supply of Aluminium Ladder 10 feet heavy duty
Supply of Fibre Operating Rods 11 KV as per IS
Supply of safety helmets as per releavant IS/ISI Marked (ISI 2925))
Supply of 11kV GO, Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
DINESH KUMAR KHAJURIA
M R ENGINEERS & TRADERS
DIVY ELECTRICAL ENGINEERING
Parbat and Sons
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .