| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.2 CrAccepted-AOC WZ 831 NANGAL RAYA PANKHA ROAD NEW DELHI 110046 | NEW DELHI | NEW DELHI | DELHI | 110046 | ₹1.2 Cr | L1 | Accepted-AOC AOC |
| 2 | L2₹1.3 Cr+₹11.5 L (9.84%)Rejected-Finance 1 225 5 6 SADAR BAZAR DELHI CANTT 110010 | NEW DELHI | DELHI | 110010 | ₹1.3 Cr+₹11.5 L (9.84%) | L2 | Rejected-Finance Due to not L1 Bidder |
| Sl No | Description | Qty | Unit | Tushar engineers L1 | M P TYAGI ENGINEERS AND CONTRACTORS L2 |
|---|---|---|---|---|---|
| 1.00 | Supply, installation & commissioning and testing including Lifting, Shifting & positioning of Floor Mounted, Bottom discharge, Air Cooled DX type CRAC units for server room application, equiped with most advanced technology, guaranteeing precise control of Data Centres and server room. The units shall be selected on the basis of following parameters:
i) 11 Tr. of minimum nominal Cooling Capacity @ 10900 CMH
ii) 30 Deg C / 36% RH of return air
iii) Supply air in between 15 - 17 Deg C
iv) 45 Deg C of Design Ambient temperature
v) Specific Power consumption shall be low as per site design conditions including compressor, evaporator fans and condensers
The Indoor unit shall comprise of Digital Scroll Compressor, Fibreglass corrossion resistant EC fans, Evaporator DX Cooling Coil with hydrophilic coating, Microprocessor controllers, TXV, Driers, G4 Filter, Suction and Discharge piping, Internal power and Control wiring, Crankcase heaters, Infrared Humidifier, Heaters, HP/LP Cutouts, Power and Control contactors, water leak detectors and Other Electrical accessories.
The Outdoor Condenser unit shall comprise of Condenser fans & motor, Condenser cooling coil (Copper coil with aluminium fins), Fan speed controller, Isolater switch. | 3 | Each Job | 14,00,000 ₹42,00,000 Lowest | 29,99,999 ₹89,99,997 |
| 1.01NOTES:- The unit shall be suitable for operation on 415 Volts, 50 Hz, 3 Phase, 4 Wire AC supply. Each unit should be having individual display panel, which shall display date, time, actual & set values, operating conditions, signal faults, collective faults, limiting values and PAC wellness alarm / service alarm to reduce the down time and unit memory shall hold the 400 most recent events with ID number, time and date stamp for each event. The dimensions of the unit shall not be more than 1200 mm x 890mm x 1970mm (L x D x H) Team Mode feature for PAC units controller for synchronising the Multiple No. of units to work as single system for all above units. Load sharing mode feature Cascading Effect etc and necessary Civil Work like tile Cutting and adjustment complete all as specified and directed including supply and connection/ fixing of the following items/ Accessories:- | |||||
| 2.00 | Supply and fixing of Indoor Unit stand duly painted with anti-corrosive paint along with vibration pads, fittings and accessories complete all as specified and as directed | 3 | Each | 15,000 ₹45,000 | 4,999 ₹14,997 Lowest |
| 3.00 | Suppy and fixing Outdoor Unit Stand - Choki type duly painted with anti-corrosive paint along with vibration pads, fittings and accessories complete all as specified and as directed | 3 | Each | 20,000 ₹60,000 | 4,999 ₹14,997 Lowest |
| 4.00 | Material and Labour for Initial charge of R-410a refrigerant gas & oil complete all as specified and as directed | 45 | KG | 1,700 ₹76,500 | 999 ₹44,955 Lowest |
| 5.00Supply and fixing of following Interconnecting Copper piping between indoor & outdoor unit with all fittings and accessories.@20 RMT per machine complete all as specified and as directed | |||||
| 5.01 | Hot Gas Line | 60 | RM | 1,800 ₹1,08,000 | 499 ₹29,940 Lowest |
| 5.02 | Liquid Line | 60 | RM | 1,700 ₹1,02,000 | 499 ₹29,940 Lowest |
| 6.00 | Supply & fixing of Interconnecting copper cabling of size 3Core x 2.5 sqmm between indoor & outdoor unit along with cable tray complete all as specified and as deirected. | 75 | RM | 1,500 ₹1,12,500 | 99 ₹7,425 Lowest |
| 7.00 | Supply & fixing of Incoming Copper Cabling of size 4C x 16 sqmm from Incoming Isolator to CRAC Unit (@5RMT/Unit) Complete all as specified and as directed. | 25 | RM | 2,000 ₹50,000 | 199 ₹4,975 Lowest |
Tender Value
₹1.2 Cr
EMD Value
₹1.9 L
Closing Date
3 Oct 2025, 10:00 amClosed
HQ CWE (U) Delhi Cantt-110010
HQ CWE (U) Delhi Cantt-110010
ADDITION AND ALTERATION TO THE EXISTING SERVER ROOM AT DIPAC UNDER GE (U) P AND M DELHI CANTT-10
2025_MES_717610_2
CWE (U)/D-12/2025-26
Open Tender
Civil Works
Works
180 days
HQ CWE (U) Delhi Cantt
Please refer Tender Documents
9 documents required · 9 mandatory
₹1,000
GE (U) P and M
₹1.9 L
Yes
6 Feb 2026
13 Sept 2025
10 Oct 2025
13 Sept 2025
3 Oct 2025
20 Sept 2025
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .