| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.1 LAccepted-AOC | ₹16.1 L Quoted ₹16.2 L | L1 | Accepted-AOC LOWEST BIDDER |
| 2 | L2₹17.3 L+₹1.1 L (6.91%)Rejected-Finance MATHOSHREE PLOT NO 55 SR NO 787 A BEHIND ASHWANI HOSPITAL GOVIND NAGAR NASIK 422 009 | NASIK | NASHIK | MAHARASHTRA | 422009 | ₹17.3 L+₹1.1 L (6.91%) | L2 | Rejected-Finance HIGHER BIDDER |
| 3 | L3₹17.4 L+₹1.2 L (7.65%)Rejected-Finance NH 17 MAIN ROAD BINAGA BAZAR KARWAR 581307 | KARWAR | UTTARA KANNADA | KARNATAKA | 581307 | ₹17.4 L+₹1.2 L (7.65%) | L3 | Rejected-Finance HIGHER BIDDER |
| 4 | L4₹21.4 L+₹5.3 L (32.5%)Rejected-Finance CHATAI SHEEP WARD NO 07 NEW MARKET ROAD AHIWARA DURG CHHATTISGARH 490036 | DURG | CHHATTISGARH | 490036 | ₹21.4 L+₹5.3 L (32.5%) | L4 | Rejected-Finance HIGHER BIDDER |
| 5 | L5₹21.9 L+₹5.7 L (35.2%)Rejected-Finance | ₹21.9 L+₹5.7 L (35.2%) | L5 | Rejected-Finance HIGHER BIDDER |
Tender Value
₹21 L
EMD Value
₹42,000
Closing Date
19 Oct 2021, 6:00 pmClosed
SH A K SINGH SE CWE NAVY VASCO
CWE NAVY VASCO VASCO DA GAMA GOA 403802
SPECIAL REPAIRS TO HT VCB 11 KV PANEL AT MDSS NSRY NAVAL BASE KARWAR UNDER GE SB KARWAR
2021_MES_451395_3
85392/E8
Open Tender
Civil Works
Item Rate
180 days
CWE NAVY VASCO
AS PER TENDER DOCUMENTS
9 documents required · 9 mandatory
₹500
Yes
GE (SB) KARWAR
₹42,000
Yes
27 Nov 2021
4 Oct 2021
21 Oct 2021
4 Oct 2021
19 Oct 2021
5 Oct 2021
Amount
Disconnecting the electric supply and taking out non functional VCB of any description and any make of rating 11 KV, dismantling / opening of the VCB for servicing / overhauling, taking out old spout and mechanical repairing spring charger motor, coil, tripping spring rod all logs spring, defective spout, same shall be refixed properly to the HT panels after carrying out work as specified under as directed. (a) Cleaning of CR Panel (b) Cleaning breaker and CT bushing and spout (c) Checking/repairing/rectification of breaker (d) Cleaning and tightening of breaker and tulip panel, breaker insulator. (e) Cleaning and heating all panel by hot air gun for removing moisture. (f) Carrying out contact Resistance Measurement test (g) Carrying out time test (h) Carrying out Insulation resisitance test Note : All spares required for replacement shall be measured and paid separately under respective item of schedule here-in-after as supply only.
Supply and fix in repair spout from 11KV VCB bus bar compartment for 11KV VCB bus bar VD4 type all as specified and as directed.
M&L for taking out VCB bus bar from the 11KV VCB bus bar compartment and cleaning the bus bar with CTC liquid and replacement of the insulating material sleeve,same shall be fixing properly to the HT panel all as specified and as directed.
Taking out carefully old panel heater and Supply and fixing new heater all as specified and as directed.
Taking out carefully old rusted bolt and nut and Supply and fixing new bolt and nut size M12X90MM should be made up of material stainless steel all as specified and as directed.
Calibration process carried out of all relay and meter including to inject primary/secondary injection by using testing transformer, Time delay testing of overcurrent breaking test, earth fault breaking test and auto breaking monitored withstanding capacity of relays all as specified and as directed.
Calibration process carried out of current transformer including to inject primary/secondary injection by using testing transformer, monitored withstanding capacity of current transformer all as specified and as directed.
Checking of all circuit as per drawing of HT 11 KV panel find out the fault in circuit and rectification of fault shall be carried out for defective part of circuit and made it functional of circuits all as specified and as directed.
Cleaning inside and outside of all HT VCB panels and carried out painting all as specified and directed
Supplying of following spare parts for 11KV indoor type VCB VD4 breaker type as specified under:-
(a) 11 KV Vacuum interrupter VGS 1250 A
(b) EL2 mechanism
(c ) Clsoing coil
(d) Tripping coil
(e) BB1 Auxillary switch
(f) BB2 Auxillary switch
(g) Closing/Tripping coil bracket assembly
(h) Limit Switch
(j) Shock absorber
(k) Pole Epoxy shroud
(l) Racking Mechanism
(m) Numeric IDMT Relay, Aux volt-110 V DC Parameter, high set inrush detector, thermal protection, 2 stage EF protection, negative sequence, TCH 4 pole, 3 O/C + 1 E/F protection relay for VCB
DURGAI ELECTRICALS
ANKIT SHIP REPAIRERS AND SUPPLIERS
M/S SANTOSH CONSTRUCTION CO
SHRI SULAI ELECTRICALS
YASHRAJ ELECTRICALS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .